The boiler must be installed and function outdoors. For installation use only original LAMBORGHINI parts.
FLUE EXHAUST TYPES
DOUBLE PIPE OUTLET KIT
To install the double pipe kit insert the funnel
1
(supplied with the
boiler) in the fan. Insert the diaphragm
3
between the adhesive seal
2
and the 5 mm spacer
4
. Fix the double pipe flue exhaust
5
with
the screws and insert the supplied silicon hood
6
. The latter must
rest on the upper part of the boiler to prevent water infiltrating.
Warning:
The boiler can only be fitted with the high double
pipe flue exhaust kit.
CONCENTRIC FLUE EXHAUST KIT
To install the concentric kit insert the funnel
1
(supplied with the
boiler) in the fan. Insert the diaphragm
3
between the adhesive seal
2
and the 5 mm spacer
4
. Fix the bend
5
with the screws and insert
the supplied silicon hood
6
. The latter must rest on the upper part of
the boiler to prevent water infiltrating.
FAN-FORCED DRAUGHT FLUE EXHAUST KIT
To install the forced draught kit insert the funnel
1
(supplied with the
boiler) in the fan. Insert the diaphragm
3
and the adhesive seal
2
.
Fix the flanged section
4
with the screws and insert the silicon hood
5
. The latter must rest on the upper part of the boiler to prevent
water infiltrating.
LOW DYNAMIC HEAD FORCED-DRAUGHT EXHAUST KIT
(ONLY LAMBY 20)
To install the low dynamic head forced draught kit insert the funnel
1
(supplied with the boiler) in the ventilator; insert the diaphragm
3
(Ø 78) and the adhesive seal
2
. Fix the flanged funnel
4
with the
screws and insert the silicon hood
5
. The hood must rest on the
upper part of the boiler to prevent water infiltrating. Rest the
diaphragm
6
(Ø 53) on the base of the hood
1
before installing the
fume outlet flue pipe.