
The Series 500A/102A/152A/202A is easily controlled through the remote connector on
the input panel of the unit. Only the ENABLE/RESET, V PROGRAM and GND signals
are required for operation. The remaining signals are provided for status monitoring and
fault diagnosis. A schematic diagram showing the suggested interface circuit is shown in
Figure 4-1. This table is for a standard configuration.
Indicates a shorted O/P or a very large load capacitor.
OUTPUT
LOAD FAULT
2
Open collector. Indicates an output overvoltage.
Temperature fault or low input voltage condition.
OUTPUT
SUMMARY
FAULT LED
3, 6
Open collector. Indicates that the power supply is
reaching end-of-charge, i.e. the V PROGRAM set point.
OUTPUT
EOC LED
13
Open collector. Indicates that the power supply is
receiving an INHIBIT signal.
OUTPUT
INHIBIT LED
15
Control circuit return. Also chassis/earth ground
OUTPUT
GND
14
15V regulated. Can be used for user programming
applications 20mA max.
OUTPUT
+15V
9, 11
A +10 to 15V with respect to ground, disables the unit.
Open or ground allows operation. This input can be
used to disable charging during HV switch recovery.
INPUT
INHIBIT
10
0-10V analog of output charging voltage waveform.
OUTPUT
V
ANALOG
8
A 0-10V signal (with respect to ground) proportional to
the peak of the output charging voltage. Can be used to
drive a meter displaying peak output voltage.
OUTPUT
V
PEAK
7
A 0-10V signal with respect to ground at this pin
programs the output voltage proportionally from zero to
rated output.
INPUT
V PROGRAM
5
A high signal (+10 to 15V) with respect to ground
(pin 14) will enable the power supply. Latching faults
can be cleared by cycling this switch. Ground or open
disables the supply.
INPUT
ENABLE/RESET
1
DESCRIPTION
I/O
SIGNAL NAME
PIN
Table 4.1 Control Interface Connection For Standard 500A/102A/152A/202A Series
83-493-001 Revision G
4 - 1
Operations