Appendix A: SGC Configuration Menu Structure
Configure/OK
Number of Cells
Lead Acid Type
5-6 (12V) / 10-12 (24V) / 20-26 (48V) / 53-62 (130V)
Nickel Cadmium Type
9-10 (12V) / 18-20 (24V) / 36-40 (48V) / 85-98 (130V)
Float Voltage
x.xx Volts per Cell
Equalize Voltage
x.xx Volts per Cell
Equalize Timer
Equalize Hours
1-145 Hours
Equalize Cycle
Manual|7 Days|14 Days|30 Days
Current Limit
50-110%
Temperature Compensation
Enable|Disable
Battery Test
Auto Battery Test
Everyday|7 Days|14 Days|21 Days|30 Days|60 Days
Manual Battery Test
Alarm Settings
Alarm Delay
1-255 Seconds
Ground Detection Delay
1-255 Seconds
DC Low Voltage
x.xx Volts per Cell
DC High Voltage
x.xx Volts per Cell
Low DC Current
0.5 - 12.5 Amps
AC Fail Voltage
AC Mains Low
1-12%
AC Mains High
1-12%
End of Discharge
x.xx Volts per Cell
High DC Shutdown
x.xx Volts per Cell
Summary Alarm
DC Low|DC High|AC Fail|Charger Fail|Neg. Gnd Fault|Pos. Gnd Fault|End of Discharge|Battery Fault|Low Current|High DC Shutdown
Change Serial Number
xxxxxx-xx
Default Settings
Load Default Settings
Input Mains
Mains Mode
120|208|240
Input Voltage xxxV
OFF
–
xx.x Amps