MANUFACTURER’S WARRANTY 

 
All La Marche Manufacturing Co. equipment has been thoroughly tested and found to be in proper operating condition upon 
shipment  from  the  factory  and  is  warranted  to  be  free  from  any  defect  in  workmanship  and  material  that  may  develop 
within  one  year  from  date  of  purchase.    In  addition  to  the  standard  one  (1)  year  warranty,  La  Marche  warrants  it’s 
magnetics and power diodes on a parts replacement basis only for nine (9) more years under normal use. 
 
Any part or parts of the equipment (except fuses, DC connectors and other wear-related items) that prove defective within 
a  one  (1)  year  period  shall  be  replaced  without  charge  providing  such  defect,  in  our  opinion,  is  due  to  faulty  material  or 
workmanship and not caused by tampering, abuse, misapplication or improper installation.  Magnetics are warranted for ten 
(10) years after date of purchase.  During the last nine (9) years of this ten (10) year warranty period, the warranty covers 
parts replacement only, and no labor or other services are provided by La Marche, nor is La Marche obligated to reimburse 
the owner or any other person for work performed.  
 
Should a piece of equipment  require major component replacement or repair during the first year of the warranty period, 
these can be handled in one of two ways: 

1. The equipment can be returned to the La Marche factory to have the inspections, parts replacements 

and testing performed by factory personnel.  Should it be necessary to return a piece of equipment or 
parts to the factory, the customer or sales representative must obtain authorization from the factory.  
If upon inspection at the factory, the defect was due to faulty material or workmanship, all repairs will 
be  made  at  no  cost  to  the customer  during  the  first  year.   Transportation  charges  or  duties  shall  be 
borne by purchaser. 

 
2.  If  the  purchaser  elects  not  to  return  the  equipment  to  the  factory  and  wishes  a  factory  service 

representative to make adjustments and/or repairs at the equipment location, La Marche's field service 
labor rates will apply.  A purchase order to cover the labor and transportation cost is required prior to 
the deployment of the service representative. 

 
In  accepting  delivery  of  the  equipment,  the  purchaser  assumes  full  responsibility  for  proper  installation,  installation 
adjustments  and  service  arrangements.    Should  minor  adjustments  be  required,  the  local  La  Marche  sales  representative 
should be contacted to provide this service only. 
 
All  sales  are  final.    Only  standard  LaMarche  units  will  be  considered  for  return.    A  25%  restocking  fee  is  charged  when 
return is factory authorized.  Special units are not returnable. 
 
In  no  event  shall  La  Marche  Manufacturing  Co.  have any  liability  for  consequential  damages,  or  loss,  damage  or  expense 
directly or indirectly arising from the use of the products,  or any inability to use them either separately or in combination 
with  other  equipment  or  materials,  or  from  any  other  cause.    In  addition,  any  alterations  of  equipment  made  by  anyone 
other than La Marche Manufacturing Co. renders this warranty null and void. 
 
La  Marche  Manufacturing  Co.  reserves  the  right  to  make  revisions  in  current  production  of  equipment,  and  assumes  no 
obligation to incorporate these revisions in earlier models. 
 
The  failure  of  La  Marche  Manufacturing  Co.  to  object  to  provisions  contained  in  customers'  purchase  orders  or  other 
communications shall not be deemed a waiver of the terms or conditions hereof, nor acceptance of such provisions. 
 
The above warranty is exclusive, supersedes and is in lieu of all other warranties, expressed or implied, including any 
implied warranty of merchantability or fitness.  No person, agent or dealer is authorized to give any warranties on behalf of 
the Manufacturer, nor to assume for the Manufacturer any other liability in connection with any of its products unless made 
in writing and signed by an official of the manufacturer. 

 

 

Содержание A70B

Страница 1: ...EL A70B BATTERY CHARGER ECN DATE CPN42675 15349 08 8 02 14268 10 00 10571 12 96 16816 6 05 14575 2 01 13073 5 99 10411 9 96 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 3061 ISSUE DATE 6 90 1 92 and 1 95 INSTRUCTION DRAWING NUMBER P25 LA70B 1 ...

Страница 2: ...W THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in the vicinity of the battery Review cautionary marking on all products PERSONAL PRECAUTIONS 1 Someone should be within range of your voice or close enough to come to your aid when you work near a battery 2 Hav...

Страница 3: ...orrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading the specific gravity or filling the battery Do not operate this unit in a closed in area or restrict ventilation in any way Do not set a battery on top of this unit DC CONNECTION PRECAUTIONS Connect and disc...

Страница 4: ... the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Until the equipment is securely mounted care must be used to prevent the equipment from being accidentally tipped over NOMENCLATURE PLATES Each piece of La Marche Mfg Equipment shipped is identi...

Страница 5: ... features Microprocessor based control Soft start current walk in control Automatic start stop circuitry Automatic Sensing of Fully Charged Battery Automatic 12 hour override timer 3 Hour timing after 80 normal mode 6 Hour timing after 80 equalize mode DI DT rate of change sensing 3 Selectable constant current finish rates High DC output shutdown Low and high AC voltage shutdown Digital Display In...

Страница 6: ...itial battery voltage sensing is being disabled and the wrong battery could be being connected An On Off switch allows you to turn off the charger when disconnecting the battery during the charge cycle The lamps are as follows On Charge Lamp This indicates after the charger has successfully completed the autostart cycle and the input contactor has closed 80 Complete Lamp This LED indicator will fl...

Страница 7: ...sary a factory service representative should be contacted Because of the stability of design the unit needs no periodic adjustment This along with the rugged construction and conservatively rated components insures long life and trouble free operation The automatic start stop circuitry senses when a battery is connected and then slowly ramps the output current up to start the charge If the dischar...

Страница 8: ... lamp will light When the AC is restored the unit will turn on again and resume the charge where is left off A high voltage condition will also cause the failure light to come on 0001 Low AC voltage 0002 High AC voltage After starting the microprocessor immediately activates the 12 hour override timer This timer is independent of battery conditions and overrides all other timing functions The over...

Страница 9: ...ssary to turn on the on off switch and connect a battery After the on off switch is placed in the on position and prior to the battery connection all of the LED s on the front panel will flash until a battery is connected This is the lamp test mode The digital display will hold four 4 eight s 8888 until the proper battery is connected to the charger When the battery is finally connected the ON CHA...

Страница 10: ...shing of 80 light indicates a low current shutoff Usually this indicates the battery is fully charged If the charger turns off on rate the charge 80 COMPLETE light will turn on without flashing and the ON CHARGE light will turn off J If for some reason the AC input voltage falls below the factory set limit about 85 the FAILURE light will turn on and the battery charger will turn off The display wi...

Страница 11: ...er 97mV adjust P4 on the S2A 122A printed circuit board counterclockwise which lowers the output until 97mV across the shunt bar is indicated 5 If AC input fuse clears when the AC contactor pulls in make sure the correct AC fuses are being used time delay fuses If the correct AC fuses are being used disconnect J3 connector from the S2A 122A printed circuit board 6 Replace blown AC fuse turn on AC ...

Страница 12: ...terminals battery connected 3 Check AC voltage output on control transformer 4 If 120 Vac is present at AC contactor coil contactor may be defective 5 If 120Vac is not present disconnect 15 pin connector from the S2A 122A printed circuit board and jump pin 10 and pin 11 together If AC contactor pulls in defective S2A 122A printed circuit board Problem Failure light on CODE 0001 OR 0002 1 Check AC ...

Страница 13: ...no indication on display board Check voltage across capacitor C 1 on S2A 122A drive board Voltage should be approximately 12Vdc if voltage is zero replace both the S2A 122A S2A 146 p c boards If 12 volts is present replace the S2A 146 board TROUBLESHOOTING SCR DIODE MODULES A70B 3 PHASE 1 Disconnect power transformer secondary wire from top connection of module 2 Disconnect positive buss bar from ...

Страница 14: ... panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Filter resonating capacitors and control relays should be replaced 10th Year REPEAT ALL WITH THE ADDITION OF except replacing capacitors and control relays they should be replaced every 7 years 1 C...

Страница 15: ... 2 If the purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service labor rates will apply A purchase order to cover the labor and transportation cost is required prior to the deployment of the service representative In accepting delivery of the equipment the purchas...