A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING
Page 6 of 21
3.0 INPUT RATINGS
3.1
A.C. VOLTAGE
The units are rated for three phase inputs and are available in 208/ 240 or 480 v.a.c. three phase inputs.
3.2
INPUT FREQUENCY RANGE
57 to 63 Hz. (60 HZ nominal)
47 to 57 HZ. (50 HZ nominal)
3.3
INPUT CURRENT - (Refer to TABLE 1) (Based on 100% load)
4.0 TYPICAL ELECTRICAL SPECIFICATIONS
Refer to TABLE 1 for a.c. input draw, heat losses (based on 85% eff, & .9pf at rated load). Refer to 7.0
installation instructions for proper wire size.
24 VOLT DC OUTPUT
AC INPUT
MODEL NUMBER
DC AMPERES
208
240
480
CASE NO.
HEAT DISSIPATION BTU/HR.
A36F-200-24V
200
20
17
9
43
6,100
A36F-300-24V
300
29
25
12
43
9,400
A36F-400-24V
400
40
33
17
43
12,300
48 VOLT DC OUTPUT
AC INPUT
MODEL NUMBER
DC AMPERES
208
240
480
CASE NO.
HEAT DISSIPATION BTU/HR.
A36F-100-48V
100
20
17
9
43
3,700
A36F-200-48V
200
39
34
17
43
6,100
A36F-300-48V
300
59
51
25
44
9,400
A36F-400-48V
400
78
68
34
44
12,300
Table 1
5.0 STANDARD FEATURES
5.1
INPUT PROTECTION
§
AC BREAKER
A three-pole circuit breaker opens all three legs of the a.c. service. Refer to parts list for rating.
5.2
OUTPUT PROTECTION
D.c. fuse or d.c. breaker positive or negative ground.
Current limiting is adjustable from 90% to 115% of rated load, limits the D.C. Output current.
Factory set at 115% of rated output. Refer to parts list for rating.