A36F - 3 PHASE - INSTRUCTIONS AND TROUBLESHOOTING
Page 19 of 21
MODE 1
§
DISPLAY indicates P01
This mode of operation automatically starts an equalize cycle every 7 days. The length of this cycle is
again determined by the timer setting. After the equalize period the timer will wait for another 7 days
and then restart.
MODE 2
§
DISPLAY indicates P02
This mode of operation automatically starts an equalize cycle every 14 days. The length of this cycle is
again determined by the timer setting. After the equalize period the timer will wait for another 14 days
and then restart.
MODE 3
§
DISPLAY indicates P03
This mode of operation automatically starts an equalize cycle every 30 days. The length of this cycle is
again determined by the timer setting. After the equalize period the timer will wait for another 30 days
and then restart.
MODE 4
§
DISPLAY indicates P04
This mode of operation automatically starts an equalize cycle when the d.c. voltage drops below the low
voltage setting for 30 seconds or longer. The battery voltage must rise above 2.01 to activate this mode.
THE SWITCH INDEX TIMER MODE “LED” WILL:
Ø
Ø
Light solid when the timer switch is in the two hour position, and the display must be indicating an
alarm voltage setting not the timer mode. In timer mode the led will be flashing.
Ø
Ø
Float/equalize “led’s” indicate the charge mode.
SHUNT BAR USED WITH ASSEMBLY S2A-178
UNIT OUTPUT CURRENT
SHUNT BAR RATINGS
0 to 20
25
25 to 40
50
45 to 85
100
90 to 170
200
175 to 330
400
335 to 665
800
670 to 1325
1600
1330 to 2600
3200