Lakeshore 26220 Скачать руководство пользователя страница 16

Installation / Operation / Maintenance Manual   

 

 

 

 

 

10/28/2019 

16

 

5.

 

MOLDED CASE SWITCHES 

5.1.

 

GENERAL INFORMATION 

The  molded  case  switches  used  in  transfer  switches  are  the  standard  devices  supplied  by  molded  case  switch 
manufactures.  Figure 2 (page 16). 
 
Thermal  magnetic  or  magnetic  trip  units  may  be  installed  (Accessory  23)  for  thermal  overload  and  short  circuit 
protection.  When these trips are provided, a bell alarm contact is included inside the breaker to indicate to the transfer 
switch circuit that the breaker has tripped due to an overload.  This breaks the motor circuit and prevents the transfer 
switch from cycling between the Normal and Emergency positions.  
 
If either breaker trips due to overload, it can be reset by manually operating the transfer switch to a position so that the 
breaker resets.  After resetting, return the transfer switch to the proper position.  A shunt trip may also be provided.  This 
allows the breaker to be electrically tripped from a remote location and can also be reset manually. 
 

5.2.

 

INSPECTION AND MAINTENANCE 

Terminal lugs and trip units must be tight to prevent overheating.  Due to the inherent wiping action built into the 
moving contacts of all molded case switches, operating the switch several times under load will remove any high 
resistance  film  that  may  have  formed.    Under  normal  conditions,  additional  cleaning  of  contacts  is  not  required.  
However, should operating and/or atmospheric conditions make it desirable to clean the contacts further, the following 
procedure is recommended.  (Refer to Figure 2). 
 
Remove cover, arc chutes, and cable terminal assemblies.  Wipe contact surfaces with a clean, lint free cloth.  If surfaces 
are excessively oxidized or corroded, scrape lightly with a fine file before wiping. 
 
The auxiliary micro switches are mounted internally to the molded case switch.

 

 

Figure 2 

 

Содержание 26220

Страница 1: ...ALLING OPERATING AND MAINTAINING AUTOMATIC TRANSFER SWITCHES AS MANUFACTURED FOR FLORIDA POWER LIGHT WITH ELECTROMECHANICAL CONTROLS Lake Shore Electric Corporation 205 Willis Street Bedford OH 44146...

Страница 2: ...CUMENT IS THE PROPERTY OF Lake Shore Electric Corporation UNDER COPYRIGHT LAW DISTRIBUTION AND REPRODUCTION OF THIS DOCUMENT IN WHOLE OR IN PART IS PROHIBITED WITHOUT PRIOR WRITTEN PERMISSION FROM Lak...

Страница 3: ...ION OF THIS DOCUMENT IN WHOLE OR IN PART THIS DOCUMENT IS THE PROPERTY OF Lake Shore Electric Corporation UNDER LAKE SHORE ELECTRIC AND LIGHT COMPANY BEDFORD OHIO U S A FLORIDA POWER STYLE 2 225A 3P 3...

Страница 4: ...MENT IN WHOLE OR IN PART THIS DOCUMENT IS THE PROPERTY OF Lake Shore Electric Corporation UNDER LAKE SHORE ELECTRIC AND LIGHT COMPANY BEDFORD OHIO U S A FLORIDA POWER 277 480VAC 3P 3 4W 400A FPL230400...

Страница 5: ...hore Electric Corporation UNDER LAKE SHORE ELECTRIC APV 1 5 PROJ CUSTOMER SCALE AND LIGHT COMPANY CHK BEDFORD OHIO U S A FLORIDA POWER STYLE 2 400A 3P 3 4W 277 480 DRN DWG NUMBER APV DESCRIPTION REV B...

Страница 6: ...IS DOCUMENT IN WHOLE OR IN PART THIS DOCUMENT IS THE PROPERTY OF Lake Shore Electric Corporation UNDER LAKE SHORE ELECTRIC APV 1 5 M S NUMBER 0 283 408 090 PROJ CUSTOMER SCALE AND LIGHT COMPANY CHK BE...

Страница 7: ...NJURY AND EQUIPMENT DAMAGE DURING INSTALLATION AND USE OF THIS PRODUCT COMPLY WITH THE NATIONAL ELECTRICAL CODE NEC FEDERAL STATE AND LOCAL CODES AND ALL OTHER APPLICABLE SAFETY CODES MAIN UTILITY EME...

Страница 8: ...y or of fitness for purpose shall apply Lake Shore is not responsible for damage to its equipment through improper installation or use unauthorized repair or modifications or attempts to operate it ab...

Страница 9: ...SWITCHES 16 5 1 GENERAL INFORMATION 16 5 2 INSPECTION AND MAINTENANCE 16 6 TIMING RELAYS 17 7 VOLTAGE RELAYS 17 7 1 VOLTAGE SENSING CLOSE DIFFERENTIAL 17 8 TROUBLESHOOTING GUIDE 19 9 APPENDIXES 22 9 1...

Страница 10: ...Installation Operation Maintenance Manual 10 28 2019 10 PAGE INTENTIONALLY LEFT BLANK...

Страница 11: ...om 16 gauge insulated machine tool wire All control circuits are protected with fuses 2 DESCRIPTION OF OPERATION Normally the transfer switch operates on the preferred power source with the Normal mol...

Страница 12: ...s are made to the common bus at the terminals marked L1 L2 and L3 On three phase four wise transfer switches or single phase three wire transfer switches a neutral bus is provided NOTE Verify that pha...

Страница 13: ...panel A test of the automatic circuitry can be initiated by moving this load test switch to the test position This will cause the normal control circuits to de energize and give a signal to transfer...

Страница 14: ...evices 4 3 REQUIRED MAINTENANCE Please refer to the APPENDIX A for required maintenance on the operating mechanism necessary to maintain your exclusive one year Lake Shore Electric Corporation warrant...

Страница 15: ...enance Manual 10 28 2019 15 Figure 1 LEGEND 1 Manual Handle 2 Drive Arms 3 Adjustment Screw 4 Motor 8 Drive Drums 9 Spring 10 Drive Shoe Pivot 11 Drive Drum Keys 12 Drive Shoe 13 Drive Shore Lining 17...

Страница 16: ...ng return the transfer switch to the proper position A shunt trip may also be provided This allows the breaker to be electrically tripped from a remote location and can also be reset manually 5 2 INSP...

Страница 17: ...any phase falls below the drop out setting the output contacts revert to their de energized state and the LED turns off Pick up and dropout values are adjustable from 70 to 100 of nominal voltage via...

Страница 18: ...nter clockwise 3 Using a small slotted screwdriver turn the pickup potentiometer fully clockwise 4 Apply required level of pickup voltage to the unit 5 Turn the pickup potentiometer slowly counter clo...

Страница 19: ...frequency must be available and within the correct operating limits 3 Control fuses must be in proper working order 4 Control circuit voltage if transformers are used must be 110 to 125 volts 5 Connec...

Страница 20: ...of the ECT If this voltage is 120 Volts nominal check the ECT transformer and or return to step 2 4 Phase Failure Relay Not Functioning PFR Using an appropriately set voltmeter check the voltage on th...

Страница 21: ...ailure Relay Normal is defective and must be replaced If the voltage is zero continue to step 5 5 Load Test Verify that the Load Test Switch is in the NORMAL position 6 Defective T Timer Using an appr...

Страница 22: ...from the edge of the drive shoe indicating slippage Transfer switches utilizing smaller circuit breakers are equipped with a single friction drive arm as they require less force to activate On these...

Страница 23: ...rques are required to be checked every six months in order to maintain the Lake Shore Electric Corporation exclusive one year warranty I TORQUE SOCKET HEAD SCREWS Warning Whenever bus and cable connec...

Страница 24: ...anty I GENERAL ELECTRIC LUG TO MOLDED CASE SWITCH E150 LINE 30 IN LBS F225 LINE 90 IN LBS J600 LINE 60 IN LBS K1200 LINE 200 IN LBS II WESTINGHOUSE LUG TO MOLDED CASE SWITCH DA JA KA LB 6 8 FT LBS 1 4...

Страница 25: ...25 LINE 75 IN LBS J600 LINE 100 IN LBS K1200 LINE 100 IN LBS V WESTINGHOUSE TRIP TO MOLDED CASE SWITCH JA KA DA KCL LB 6 8 FT LBS MA MC 15 FT LBS NB NC LA LC LCL KB HKB JB 6 8 FT LBS VI EATON CUTLER H...

Страница 26: ...be acceptable The torque produced by a motor is approximately proportional to the square of the voltage applied that is a motor that is started at 90 of rated voltage will produce a torque of 90 2 1 o...

Страница 27: ...oltage unbalance condition Consider Figure 3 Triangle ABC represents a balanced voltage source Triangle ABD represents a three phase system in which one phase has dropped to 80 of its nominal voltage...

Страница 28: ...rvoltage relays provide against voltage unbalance when it is calibrated for an 87 drop out The Lake Shore Voltage Sensing Relay will drop out on a 4 voltage unbalance thus limiting the motor overheati...

Страница 29: ...as shown in Figure 6 This time delay helps avoid nuisance undervoltage indications as may occur during system transients The inverse time characteristic allows a 1 5 second delay before the relay de...

Отзывы: