Electrostatic Cell Removing and Re-installing
CAUTION
Always Ground the Cell before handling!
When you open the door to the Unit all power is cut off. It is possible however that
some residual electricity is still residing in the Filter Cell. So, the
FIRST
thing to do is
ground the voltage side of the cell. To do this take a Philips screw driver with an
insulated handle and
drag the screw driver across the plates.
This will dissipate any
residual charge.
Remove the ground screw.
The ground screw secures the
filter cell and provides the
ground needed to allow the
filter cell to function properly
Before removing the electrostatic cell you will need to unplug it from the high voltage
lead wire
.
The lead wire is attached to the cell and is accessed through the openening in
the top left of the cell box. The lead wire has an insulated boot which is lifted off the ion
stud. See Image Below
To re-install:
reverse these steps, be sure that the power line is with the cell frame and
avoid crimping the power.