61
relevant bit will set 0.
Bit
Warning
a0
Battery disconnected
a1
Input Neutral loss
a2
Reserved
a3
Input phase abnormal
a4
Reserved
a5
Reserved
a6
Battery over charge
a7
Low battery
a8
Overload
a9
Fan failure
a10
EPO active
a11
Reserved
a12
Over temperature
a13
Charger failure
a14
Reserved
a15
L1 IP fuse broken
a16-a49
Reserved
a50
Locked in bypass after overload 3 times in 30min
a51
Converter current unbalance
a52
Battery fuse broken
a53
Inverter inter-current unbalance
a54-a56
Reserved
a57
Cover of maintain switch is open
Example:
Computer: QWS<Enter>
UPS: (1000000000000000000000000000000000000000000000000000000000000000
Meanings: The battery of UPS disconnected.
9.2.9 QFS
QFS means to request the latest fault occurred of the UPS. The command format is:
Computer: QFS<Enter>
If no UPS fail occurred:
UPS: (OK<cr>
If UPS fail occurred:
UPS: (KK PPP.P FF.F OOO.O EE.E LLL CCC.C HHH.H NNN.N BBB.B TTT.T b7b6b5b4b3b2b1b0<cr>
Data
Description
Notes
(
Start byte
KK
Fault code
K is a hexadecimal number 0 to F. The code please reference to 7.1.2
PPP.P
Input voltage when fail
P is an Integer number 0 to 9. The units is V.
FF.F
Input frequency when fail
F is an Integer number 0 to 9. The units is Hz.
OOO.O
Inverter voltage when fail
O is an Integer number from 0 to 9. The units is V.
Содержание G31 10K
Страница 37: ...37 ...