The pipe to the 
bottom of the tank 
must not be routed 
through the roof.
This connection 
removes the self-
circulation function.

NOTE If the radiator 
is connected in 
this way there 
is a large risk of 
heat retention in 
the boiler and/or 
reduced heat to the 
radiator circuit.

Connecting to a tank

1. The pipe-runs shown on the diagram are optimised to 

minimise air-related operating interruptions. 

2. The hot water pipe to the by-pass valve can be 

connected in two ways.
A. Approx 30 cm from the top of the tank to prioritise 
domestic hot water. 
B. On the charge line connection to the tank to 
prioritise heating. The connection is directed down-
wards to prevent air rising to the radiators.

Connecting 2 tanks

The tanks must be located up against each other, and as 
close as possible to the boiler. The pipe-runs from the bot-
tom of the tanks are always laid close to the fl oor.

It is important that the fl ow to the tanks during charging 
and discharging is distributed equally. If the system is 
connected incorrectly, then charging will be cut off when 
tank 1 is full of hot water which will reach the boiler before 
the other tanks are completely fi lled. Tank 2 will be 
virtually unused.

If the system is connected incorrectly, the warm water and 
the heat will run out earlier than estimated after the burner 
has stopped, since tank 1 will cool down more quickly than 
the other.

If these requirements cannot be met, there are other 
connection options.

Equal pipe lengths

To achieve equal resistance, it is essential to use 
approximately the same pipe-lengths to the tanks, this is 
achieved by:

1. Connecting the charging circuit diagonally, A–A.

2. Connecting the radiator circuit diagonally, B–B.

In addition, the dimension of the pipes between the tanks 
must be large enough to facilitate self-circulation between 
the tanks. It is an advantage if the tanks are connected 
together in the centre, to further distribute the heat.

Connecting the by-pass valve

The hot water port is connected at B, which prioritises hot 
water, or at B

1

, which prioritises heating. 

Electrical immersion heater operation

When operating solely on the electrical immersion heater, 
it is an advantage only to heat the fi rst tank to prevent heat 
loss. Shut off the other tank using the valve at the bottom 
of the tank.

Laddomat 21-60 can 
easily be reversed for 
right-hand mounting.
Just move the 
thermometers to the other 
side.

Содержание 21-60

Страница 1: ... event of electrical power failure stopping the pump transfer the heat in the boiler to the tank through self circulation Operation Laddomat 21 60 functions fully automatically provided that pump start and stop is automated See page 3 The settings described in this User manual are normally made only once The Laddomat requires no special supervision or service Technical data Pump Laddomat LM6 stand...

Страница 2: ...2 Description of functions Operating phase Start up Final phase Self circulation Connection to bottom of boiler Connection to bottom of tank Connection to top of boiler ...

Страница 3: ... delivery temperature The lower the return temperature the longer the heat in the tank lasts Dimensioning Generous pipe dimensions and short lengths guarantee operating reliability even when the demand for heat is high This also allows effective self circulation in the event of power failure Recommended pipe dimensions at a maximum boiler to tank distance of 2 m Total length would then be 2 2 m 6 ...

Страница 4: ...ch the boiler before the other tanks are completely filled Tank 2 will be virtually unused If the system is connected incorrectly the warm water and the heat will run out earlier than estimated after the burner has stopped since tank 1 will cool down more quickly than the other If these requirements cannot be met there are other connection options Equal pipe lengths To achieve equal resistance it ...

Страница 5: ...5 NOTE See information on page 3 about the expansion vessel Connection suggestions Bottom connection of the expansion vessel gives reduced heat losses Alternative installation with open expansion vessel ...

Страница 6: ...mp which may result in stoppages Instructions for replacing the thermostat in Laddomat 21 60 Check that the pump is switched off Close the three shut offs Unscrew the cover opposite the pump Remove the cover with the spring plunger and thermostat from Laddomat 21 60 The thermostat is held in place on the plunger by an O ring Detach the thermostat from the plunger carefully using a screwdriver see ...

Отзывы: