INSTALLER’S MANUAL

SITTING

LACANCHE range hoods install horizontally at a minimum distance of :
  - 

65

 cm over electrical range.

  - 

80

 cm  over gas range.

Make sure hood is installed perfectly horizontal and cannot dip forward.
Use aluminum duct and choose shortest and straightest pathway. Do not connect to smaller diameter duct, 
use no roof caps or exhaust screens.

 

BAD

MEDIUM

GOOD

Attachment plate 

Front 

Plastic jack x 4

Extractor hood extension

Hottes - Ft 118a - GB - Rév 08 - Modifié le : 06/07/2015               10/28

Содержание L2HM 1000

Страница 1: ... L2HM 1000 L2HM 1100 L2HM 1200 L2HM 1300 L2HM 1500 L2HM 1600 L2HM 1700 L2HM 1700 L2HM 1800 L2HM 2000 L2HM 2100 L2HM 2200 L2HM 2400 LACANCHE KITCHEN RANGE HOODS Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 1 28 ...

Страница 2: ...THE HOOD 13 SETTING UP OF GROUPS 17 INSTALLING THE EXTRACTOR HOOD EXTENSION 20 INSTALLING MOUNTING CHANNEL COVERS 22 USER S MANUAL 23 USE 25 CLEANING AND MAINTENANCE 26 Note concerning the disposal of waste electrical and electronic equipment 28 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 2 28 ...

Страница 3: ...5 L2HM 2400 2400 1885 TECHNICAL DATA SHEETS MEASUREMENTS AND DIMENSIONS B A 7 3 5 80 Axe de sortie murale Hotte LHM Axe de sortie murale Hotte LHME Axe de sortie murale centrale Hotte LHM LHME Raccordement électrique Hotte LHM LHME 305 Axe de sortie centrale Hotte LHM 225 Axe de sortie centrale Hotte LHME 495 90 155 165 L 15 750 725 650 596 2400 100 70 1820 890 580 0 à 240 40 930 Hottes Ft 118a GB...

Страница 4: ... Exhaust duct diameter LU ÀRZ SUHVVXUH UDWLR L2HM 900 874 1 125 mm 327 m3 384 Pa L2HM 1000 874 1 125 mm 327 m3 384 Pa L2HM 1100 874 1 125 mm 327 m3 384 Pa L2HM 1200 878 1 150 mm 627 m3 383 Pa L2HM 1300 878 1 150 mm 627 m3 383 Pa L2HM 1500 878 1 150 mm 627 m3 383 Pa L2HM 1600 878 1 150 mm 627 m3 383 Pa L2HM 1700 874 2 2 x 125 mm 654 m3 384 Pa L2HM 1800 874 2 2 x 125 mm 654 m3 384 Pa L2HM 2000 874 2...

Страница 5: ...ough the hole in the base of the installed hood protrudes far enough to be connected to the fan s Electric connection Finish cable with an earthed 2 pole plug suitable for 230V 1N 50Hz Hood must be earthed Power input L2HM 900 1100 120 Watt when lit L2HM 1101 à 1601 235 Watt when lit L2HM 1701 à 2002 240 Watt when lit L2HM 2102 à 2202 470 Watt when lit Hottes Ft 118a GB Rév 08 Modifié le 06 07 201...

Страница 6: ......

Страница 7: ...2000 L2HM 2100 L2HM 2200 L2HM 2400 INSTALLER S MANUAL Appliances must be installed in a workmanlike manner in accordance with the instructions in this manual and locally applicable regulations This manual will be handed over to the user after installation Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 7 28 ...

Страница 8: ......

Страница 9: ... reservations on the delivery note and confirm them within 48 hours by registered letter with confirmation of delivery to the carrier Recommendations Check hood overhead clearance Install elbow over hood when mounting a complete range hood connected to a wall exit Do not connect exhaust duct to central ventilation system or service duct Choose shortest and straightest pathway for exhaust duct Q FD...

Страница 10: ... Make sure hood is installed perfectly horizontal and cannot dip forward Use aluminum duct and choose shortest and straightest pathway Do not connect to smaller diameter duct use no roof caps or exhaust screens BAD MEDIUM GOOD Attachment plate Front Plastic jack x 4 Extractor hood extension Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 10 28 ...

Страница 11: ...Preparing the extractor hood 7XUQ WKH H WUDFWRU KRRG RQWR LWV EDFN JXUH 1 2 Loosen the screws holding the front of the hood Item A JXUH 2 3CREW 1 A A A A 2 INSTALLATION Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 11 28 ...

Страница 12: ...INSTALLER S MANUAL INSTALLATION 3 Stand the extractor hood upright 5HPRYH WKH IURQW FRYHU E OLIWLQJ LW VOLJKWO DQG SXOOLQJ LW WRZDUG RX JXUH 3 3 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 12 28 ...

Страница 13: ...20 mm 2356 1799 XIS OF THE HOOD to position if back panel Installing hood 7UDFH DQG GULOO KROHV JXUH 4 2 Positioning and securing the two brackets to hood screw type M5 SETTING UP THE HOOD 4 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 13 28 ...

Страница 14: ...L SETTING UP THE HOOD 2356 1820 Axis of the hood Attach the trim back the hood before NOTE If a back cover is used install the back cover before mounting the hood 5 5 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 14 28 ...

Страница 15: ...d 7 7LJKWHQ WKH VFUHZV OLJKWO WR ÀDWWHQ KRRG WR WKH ZDOO 6 To level by tightening or loosening the 2 screws 6532570 and 6535377 7 End of the hood to the wall plate by tightening the screws 6535377 6532570 6535377 SETTING UP THE HOOD 6 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 15 28 ...

Страница 16: ...INSTALLER S MANUAL MANDATORY ATTACHMENTS SETTING UP THE HOOD 7 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 16 28 ...

Страница 17: ...panel ĸ Loosen black side cover screws Ĺ Loosen 8 screws ĺ Push blower unit s into cutout until they bottom with rotary switch facing forward and to the right Make sure locking lugs hold blower unit s securely in place Tighten screws item Ļ ĺ and Ĺ 8 9 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 17 28 ...

Страница 18: ...UH 10 Remove the 4 screws on media panels and drop media panels Media panel Prepare the extractor unit and use the locking brackets to position it item B JXUH 11 and 12 see assembling the unit s section 10 11 12 B Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 18 28 ...

Страница 19: ... the extractor unit s to the hood by tightening the 4 screws on either side of the XQLW J 13 see assembling the unit s section 3XW WKH VKHDWK LQ SODFH JXUH 14 GMXVW WKH JULS ULQJ JXUH 15 13 14 15 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 19 28 ...

Страница 20: ... and adjust the media hides sheath in boutonnièress provided for this SXUSRVH DQG DGMXVW WKH KHLJKW RI WKH SODVWLF F OLQGHUV E VFUHZLQJ RU XQVFUHZLQJ JXUH 16 7KHQ LQVHUW WKH H WUDFWRU KRRG H WHQVLRQ EHWZHHQ WKH FHLOLQJ DQG WKH MDFNV J 17 16 17 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 20 28 ...

Страница 21: ...force the jacks when tightening Replace the media cover and secure Replace the front facing of the extractor hood by performing the above operations in reverse order media façade Front panel caches beams Right and Left Cache front beam INSTALLING THE EXTRACTOR HOOD EXTENSION 18 Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 21 28 ...

Страница 22: ...OG FRYHU Ĺ LQ SODFH DQG IDVWHQ EDFN RI FRYHU XVLQJ D VWDLQOHVV VWHHO 0 VFUHZ QVWDOO WKLUG FRYHU ĺ QG IDVWHQ WR EORZHU XQLW PRXQWLQJ EUDFNHW Ļ XVLQJ VWDLQOHVV VWHHO 0 VFUHZV QVWDOO UHPDLQLQJ VFUHZV RQ FRYHUV ĸ and Ĺ INSTALLING MOUNTING CHANNEL COVERS Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 22 28 ...

Страница 23: ... DSSOLDQFH LV VHW XS PXVW EH FDUULHG RXW E D TXDOL HG installer Any changeover to a voltage other than that for which the appliance is set up must be carried out by a TXDOL HG LQVWDOOHU WARRANTY The warranty is stated on the sales contract Please contact your approved Dealer if any work has to be carried out under warranty This warranty excludes damage resulting from incorrect installation imprope...

Страница 24: ...ote concerning the disposal of waste electrical and electronic equipment 28 This range has the marking i e it meets the essential requirements of the Euro pean safety directives to which it is subject Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 24 28 ...

Страница 25: ... DLU SDWK LQWR WKH KRRG For normal operation Place pans on range so hood catches all vapor and smoke Avoid cross drafts Match fresh air intake to exhaust volume to avoid loss of performance Controls The control panel of each blower unit features a 5 position rotary switch 0 Off light I II and III blower speeds Select required blower speed CAUTION NEVER FLAME UNDER HOOD Hottes Ft 118a GB Rév 08 Mod...

Страница 26: ...HU WR GU Stainless steel casing Use special stainless steel cleaners ZIP INOX JOHNSON INOX PPZ INOX for instance Do not use abrasive cleaners Epoxy coated casing Sponge with soapy solution BEFORE ANY CLEANING OPERATION CHECK THAT THE APPLIANCE IS DISCONNECTED FROM THE SUPPLY CLEANING AND MAINTENANCE CAUTION Do not use a steam cleaner to clean the appliance Carefully read the precautions and recomm...

Страница 27: ...ser and replace tube Push diffuser back in place 8VH 3 FRPSDFW ÀXRUHVFHQW UHSODFHPHQW WXEHV IRU UDQJH KRRG PRGHOV 0 WR 1600 PL 11 W tubes for range hood models L2HM 900 L2HM 1700 to 2200 CLEANING AND MAINTENANCE Hottes Ft 118a GB Rév 08 Modifié le 06 07 2015 27 28 ...

Страница 28: ...municipal waste Appropriate systems of separate collection are available to users To meet these regulations as a manufacturer of electrical equipment Lacanche has joined and participates in the green scheme operated by ÉCO SYSTÈMES FRANCE It is by observing these regulations that users of electrical and electronic equipment avoid the potentially harmful effects on the environment and human health ...

Отзывы: