LAC Ht40B Скачать руководство пользователя страница 8

 

8

4.2

 

Automatic / manual operation of controller 

Automatic operation 

of controlling requires the closed control loop. The user adjusts stp value and the controller regulates the 

output power that is supplied to system. 
At 

manual operation

 the user adjusts the required output power. 

Manual operation 

Manual operation is set by double pressing the key 

.  It must be allowed by setting parameter 

FKEY

 = 

 A-M

. Parameter 

FKEY

 

is found in 

configuration level

, menu 

 SYS

Important: 

 

When in manual operation the controller can not influence the output power that is set by a user. The behavior of the 
system is then fully under users control. 

 

When in manual operation,  

Man 

 blinks on lower display. 

 

The controller remains in the chosen mode of operation even after the power interruption. 

 

In manual operation the zero output power is set after the power interruption. 

 

In manual operation the output power is always set in % (0 to 100 for heating, -100 to 0 for cooling,   -100 to 100 for 
heating and cooling) and even in the case that the output is configured as the ON/OFF output. 

4.3

 

Parameters of the control output, PID controlling 

The controller Ht40B can be configured for ON/OFF as well as PID controlling and it enables: 

 

Heating controlling (the output 1). 

 

Cooling controlling (the output 2). 

 

Controlling of heating and cooling (the output 1 and 2). 

The description of principals of controlling is found on page 

16

Heating, ON/OFF controlling 

ON/OFF controlling of heating is set with the parameter 

ot1 

 = 

 ht2

. Parameter 

ot1 

 is 

found in 

configuration level

, menu 

out1

In 

operation level

 you set hysteresis of ON/OFF controlling, parameter 

hYS1

 
 
 

Heating, PID controlling 

PID controlling of heating is set with parameter 

ot1 

 = 

  ht

. Parameter 

ot1 

 is found 

in 

configuration level

, menu 

out1

In 

operation level

 you set PID parameters: 

 

Pb1A

It1A

dE1A

, If only 1 set of PID parameters is used (parameter 

ALGo

). 

 

Pb1A

It1A

dE1A

Pb1b

It1b

dE1b

, if both sets of PID parameters are used. 

 
 

Cooling, ON/OFF controlling 

You  switch  between  automatic 
and manual operation by double  
pressing the key „F“ 

In 

automatic  operation

  lower  display  shows  stp 

value. 
In 

manual  operation

  lower  display  shows  the  set 

output power in %. 

In 

automatic  operation

  you  set  stp  value  with  the 

arrow-keys. 
In 

manual operation

 you set the output power in % 

with the arrow-keys.  

Process value  is shown on 
upper display 

hYS1 

SP1 

SP1 

Содержание Ht40B

Страница 1: ...1 Ht40B 01 03 soft 4 11 rev 1 english version Ht40B PID controller Users manual LAC spol s r o tef nikova 116 664 61 RAJHRAD e mail info lac cz www lac cz...

Страница 2: ...t you need for your own work on the controller If you are a new user of the device focus on the following chapters Basic terms here it is explained the key functions displays and so on Basic mode the...

Страница 3: ...asing a value of parameter key for switching between automatic and manual operation see page 8 2 2 Information and error messages Information and error messages are indicated only in basic mode see pa...

Страница 4: ...t is necessary to set up its parameters properly For better understanding the parameters are sorted out to groups levels and menus Level is superior to menu menu is a part of level menu out1 The struc...

Страница 5: ...set for the output on lower display heading oFF is lit and the control output is switched OFF When in cascade controlling there is calculated stp value shown on lower display and heading CSCd blinks W...

Страница 6: ...munication line it is used for system Master Slave CSCD remote setting of stp value via communication line it is used for cascade controlling dIF Difference of remote stp value for system Master Slave...

Страница 7: ...set no You can view the result in user level 4 1 Controlling of stp value When the controller maintains stp value lower display shows stp value and upper display shows process value Setting of stp va...

Страница 8: ...f the control output PID controlling The controller Ht40B can be configured for ON OFF as well as PID controlling and it enables Heating controlling the output 1 Cooling controlling the output 2 Contr...

Страница 9: ...Aut CL setting parameters for cooling Parameter Aut you will find in operation level The control output must be set for PID controlling The controller explores the characteristics of system from swit...

Страница 10: ...ing of PID parameters oFF turning OFF of autotunning of PID parameters ht starting of autotunning of PID parameters heating CL starting of autotunning of PID parameters cooling L r Selection for setti...

Страница 11: ...are shown or the limits of signal output ot2 SGPr or ot2 SGdE To enter menu set YES on upper display and confirm Display Meaning Pb2A Proportional band of the output 2 Range 1 to 2499 C It2A Integral...

Страница 12: ...per display set via the arrow keys ConF and confirm If PASS appears on lower display configuration level is secured with the password In this case set the password via the arrow keys and confirm again...

Страница 13: ...1 Together with parameter rh 1 you also set the scale of displaying measured values for process input ranges Range 499 to rh 1 rh 1 Together with parameter rL 1 you also set the scale of displaying me...

Страница 14: ...alarm defined by the deviation from stp value SP1 Lat3 Setting for alarm latching oFF temporary alarm on permanent alarm SIL3 Setting for alarm silencing at the power up oFF alarm function is active...

Страница 15: ...ON OFF controlling o2Lo low limit of signalling for the output 2 o2hI high limit of signalling of the output 2 ALLo low limit of alarm ALhI high limit of alarm StP2 Parameter that is placed on the 2nd...

Страница 16: ...broken the control output is turned OFF the alarm output is activated Measuring range of process inputs In configuration level menu InP1 you can define the measuring range of the process inputs with p...

Страница 17: ...of the drawing Power limit function You can improve the quality of control by limiting of the output power Process value Time STP value Output power Time 100 State of control output Time ON OFF Time c...

Страница 18: ...the absolute value of temperature ot3 ALPr Alarm defined by the deviation from stp value ot3 ALdE Temporary permanent latched alarm Alarm can be temporary LAt3 oFF or permanent LAt3 on Temporary alar...

Страница 19: ...stp value Slave controllers can modify this value by difference parameter dIF Multi zone furnace Master controller Slave controller T R T R As MASTER conroller you can use also other controllers INDUS...

Страница 20: ...n ON of action unit is too e g in muffle furnace By configuration of 2 controllers as a cascade system you achieve that long lag time will be divided into 2 parts and thus you improve the quality of c...

Страница 21: ...ce rtd input 1 Range 350 ohms I1 Measured current current input 1 Range 20mA u1 Measured voltage voltage 1 Range 10V ConF By setting YES and confirming you enter the menu for setting all the parameter...

Страница 22: ...vel Sen1 dEC1 CAL1 rL 1 rh 1 CoMM bAud Addr ot1 Ct1 ALGo SPid PLLo S PL PLhI ot2 FKEY SP1L SP1h rAMP rtI P oP P Co P SE Ftr1 SP2 Ct2 SId2 ot3 Lat3 SIL3 SId3 hYS3 rErr dErt StP1 StP2 StP3 StP4 StP5 StP...

Страница 23: ...rence in environment of the controller Among the most harmful sources of interference are the following Equipment with inductive load e g electromotors winding of relays and breakers Thyristors and ot...

Страница 24: ...nect the unit to a supply power source check the level of supply voltage The controller is intended for use in industrial or in laboratory equipment measuring input InP1 Fuse T 1A 100 240 VAC 50Hz max...

Страница 25: ...ated from the ground of the controller For this output it is necessary to fix the wires in the way that in case of loosening the wire from the terminal the insulation would not be reduced between supp...

Страница 26: ...sary to fix the wires in the way that in case of loosening the wire from the terminal the insulation would not be reduced between supply voltage and safety voltage 230Vac 5A or 30Vdc 5A 1 2 3 4 5 6 7...

Страница 27: ...position of decimal point You will find the description of this parameter on page 16 This parameter is shown only for the process input rL 1 rh 1 parameters for setting of the scale of displaying val...

Страница 28: ...00 C r thermocouple R range 0 to 1760 C S thermocouple S range 0 to 1760 C b thermocouple B range 300 to 1820 C C thermocouple C range 0 to 2320 C d thermocouple D range 0 to 2320 C rtd sensor rtd Pt1...

Страница 29: ...on this controller with the exception on defects caused by mechanical or electrical wearing out of the outputs This warranty does not also apply to damage resulting from inappropriate transportation...

Страница 30: ...ning automatic setting of PID parameters 9 5 Operation level 10 6 Configuration level 12 6 1 Measurement 16 6 2 Controlling the control output 16 6 3 Alarm 18 6 4 System Master Slave 19 6 5 Cascade co...

Отзывы: