14
S PL
Setting of limit between low and high values of power limit function.
Range: -499 to 2499 °C.
PLhI
Power limit function for the limiting of output power at high measured values, in %.
Range: 0 to 100 %.
out2
, output 2
Display
Meaning
ot2
Function of the output 2:
•
oFF
… output 2 is turned OFF.
•
CL
… cooling control, PID controlling.
•
CL2
… cooling control, ON/OFF controlling.
•
SGPr
… signalling when process value is beyond the defined limits, absolute value.
•
SGdE
… signalling when process value is beyond the defined limits, deviation from stp value SP1.
•
rSP
… signalling when remote set stp value is absent (Master / Slave, cascade controlling).
SP2
Stp value for the output 2
(deviation from stp value of the output 1).
Range: 0 to 1000 °C.
Ct2
Time cycle for switching of the output 2.
Range: 1 to 200 seconds.
SId2
The selection of active limits for alarm:
•
both
… low and high limit is active.
•
hI
… high limit is active.
•
Lo
… low limit is active.
out3
, alarm output
Display
Meaning
ot3
Function of the alarm output:
•
oFF
… alarm output is turned OFF.
•
ALPr
… alarm defined by the absolute value.
•
ALdE
… alarm defined by the deviation from stp value SP1.
Lat3
Setting for alarm latching:
•
oFF
… temporary alarm.
•
on
… permanent alarm.
SIL3
Setting for alarm silencing at the power-up:
•
oFF
… alarm function is active.
•
on
… alarm function is deactivated.
Sid3
The selection of active limits for alarm:
•
both
… low and high limit is active.
•
hI
… high limit is active.
•
Lo
… low limit is active.
hYS3
Hysteresis for switching for the alarm output.
Range: 1 to 249 °C.
SYS
, system parameters
Display
Meaning
FKEY
Function of the key „F“:
•
oFF
… the key „F“ has no function.
•
A-M
… the key „F“ is intended for switching between automatic and manual operation.
SP1L
The limit of low range for stp value.
Range: -499 to
SP1h
°C.
SP1h
The limit of high range for stp value.
Range:
SP1L
to 2499 °C.
rAMP
Ramp rate to stp value SP1 when in controlling to stp value.
If you set
oFF
, ramp function is OFF.
•
Range:
oFF
, 1 to 999 °C.
rtI
Setting of time for recovery of remote stp value.
Range: 1 to 99 seconds.
rErr
Response of the control output when time
rtI
is exceeded when in controlling Master / Slave.
•
oFF
… the control output is turned OFF.
•
SP1
… controlling to stp value SP1.
dErt
It makes the character of derivative value more accurate
. The more value is set, the more derivative value is damped down.
•
Range: 1.0 to 100.0 seconds.