Pressure transmitter PASCAL CV4 

Type series CV4xxx 

  Questions about this device? H49 (0) 4408 804 - 444

 

LABOM Mess- und Regeltechnik GmbH   Im Gewerbepark 13   27798 Hude   Deutschland 

Tel.: +49 (0) 4408 804-0   Fax: +49 (0) 4408 804-100   e-mail: [email protected]   www.labom.com 

BA_080

Rev 1J8

Page 1/24

 

Operating Instructions 

 

1

 

General Information....................................................................................................... 2

 

1.1

 

General Safety Notes .............................................................................................. 2

 

1.2

 

Intended Use ........................................................................................................... 2

 

1.3

 

Conformity with EU Regulations .............................................................................. 2

 

2

 

Transportation and Storage .......................................................................................... 2

 

3

 

Installation and Commissioning .................................................................................. 2

 

3.1

 

Devices with Diaphragm Seal ................................................................................. 2

 

3.2

 

Mechanical Installation ............................................................................................ 3

 

3.3

 

Mount / dismount display ........................................................................................ 3

 

3.4

 

Electrical Connection .............................................................................................. 3

 

3.5

 

Device orientation ................................................................................................... 4

 

3.6

 

Adjustment of the display contrast .......................................................................... 4

 

4

 

Operation ........................................................................................................................ 4

 

4.1

 

Maintenance / Service ............................................................................................. 4

 

5

 

Disassembly ................................................................................................................... 5

 

6

 

User Manual ................................................................................................................... 6

 

6.1

 

Basics of the Operating Concept ............................................................................. 6

 

6.2

 

Display Mode / Measured Value Display ................................................................. 7

 

6.3

 

Menue Mode / Operating Menue ........................................................................... 10

 

6.4

 

The Menue Tree .................................................................................................... 13

 

 

Содержание PASCAL CV4

Страница 1: ...neral Safety Notes 2 1 2 Intended Use 2 1 3 Conformity with EU Regulations 2 2 Transportation and Storage 2 3 Installation and Commissioning 2 3 1 Devices with Diaphragm Seal 2 3 2 Mechanical Installation 3 3 3 Mount dismount display 3 3 4 Electrical Connection 3 3 5 Device orientation 4 3 6 Adjustment of the display contrast 4 4 Operation 4 4 1 Maintenance Service 4 5 Disassembly 5 6 User Manual ...

Страница 2: ...roducts on the market within the European Union You find the complete EU Declaration of Conformity document no KE_048 at www labom com 2 Transportation and Storage Store and transport the device only under clean and dry conditions preferably in the origi nal packaging Avoid exposure to shocks and excessive vibrations Permissible storage temperature 40 80 C 3 Installation and Commissioning Ensure t...

Страница 3: ...mp module When reconnecting the cable please take polarity red lead into account Otherwise the cable will not fit into the plug When mounting the display you can choose its orientation Complete the process by firmly reattaching the cover 3 4 Electrical Connection Complete the mechanical installation before you connect the device electrically Set up all electrical connections while the voltage supp...

Страница 4: ...w keys to adapt the contrast The setting is saved and the contrast screen closes as soon as the ESC key is released 4 Operation During operation take care that the device remains within its intended pressure and tem perature ranges No other monitoring is necessary Permissible ambient temperature 20 80 C Optionally you can order devices with an extended ambient temperature range of 40 80 C 4 1 Main...

Страница 5: ...arning Opening pressurized lines might cause severe injuries Danger of severe injuries or damage Relieve the process pressure before attempting to remove the device Shut off the pressure supply for all feed lines to the device and relieve the pressure in them Warning Hazardous deposits and residues might remain on opened process connec tions and removed devices Danger of injury After the device ha...

Страница 6: ...ce The gen eral functionality of the buttons is identical in all operating modes Figure 2 Control elements If you press and hold the up or down button it will automatically be triggered multiple times This allows to easily navigate through longer selection lists If you press and hold the ESC button you always return to the measured value display Button Function Select function increase decrease va...

Страница 7: ...lue is larger than the displayable number due to setting a fixed decimal point or an inappropriate unit the largest displayable number is shown flashing In this case please select a different setting of the decimal point or a different unit In display mode you can review the device data enter the menue or lock unlock the menue Button Function Scroll through the pages with device data ESC Return to...

Страница 8: ...e protection in combination with the lock icon Use the same key combination to unlock the menue again 6 2 3 Icons indicating device status In the top right corner of the display depending on the device status an NE107 conform icon is displayed The following icons are defined Error failure Critical error alarm current is activated The error description is indicated in the display It restarts after ...

Страница 9: ...Large dis play 1st value 2nd value unit The main value is shown at the maxi mum size best readability from a dis tance One additional value can also be shown Table 4 Display layouts You can define what information shall be shown in the layout s placeholders You can select the 1st value main value from the following data 1 Pressure with the selected unit 2 Pressure in per cent of the measuring rang...

Страница 10: ...olding the ESC button for at least one second OK ESC ESC OK ESC ESC long Figure 4 Navigating the operating menue In long menues and selection lists a scroll bar on the left side shows the position of the currently selected item Menue items that open a setting dialogue differ from submenues by three trailing points e g Lower range select via setting dialogue and System select via submenue If no but...

Страница 11: ...lue is saved Saving the value is confirmed with an in formation window and the new value is shown in view mode With ESC you leave the view mode and return to the menue OK ESC ESC OK OK ESC ESC menue view mode edit mode Figure 5 Procedure for value selection e g changing language from english to german 6 3 2 Setting a numeric value When setting numeric values the screen shows the following elements...

Страница 12: ... unless the parameter limit is reached The value is then set to the parameter limit You can set negative numbers by decreasing the value below zero When you press the ESC button you can cancel the entry at any time and return to the display of the set value Any change of the value is not saved With the OK button you confirm the set digit value and jump to the next digit When you confirm the rightm...

Страница 13: ...k of the measurement chain Communication Information and settings regarding HART communication System Device data and function such as factory reset Table 6 The main menue 6 4 2 Menue Quick Setup In Quick Setup basic configuration options are combined to make it possible to quickly configure key functions All functions of the quick setup can also be found at another posi tion in the menue tree The...

Страница 14: ...characteristic curve Therefore it is a special case of the lower adjustment see below 6 4 3 2 Position correction Using the function Position correction you can correct the offset error due to the installa tion position independent of the zero point offset In the corresponding submenue you will find the following entries Menue entry Description Pos corr on off Activate deactivate position correcti...

Страница 15: ...range value of the meas urement ranges 6 4 3 4 Current adjustment You can use the current adjustment if the reading at the end of the measurement chain re converted current value does not correspond to the measured pressure With this function you can compensate deviations in the output stage as well as the downstream measurement chain Proceed as follows example for 4 mA Select function Current adj...

Страница 16: ... mode Configuration of the screen layout and content see 6 2 4 Decimal point Select setting of decimal point to determine number of decimal places Backlight Switch backlight on off Table 10 Display menue 6 4 4 1 Submenue Units You can select the unit of every value shown on the display These settings do not affect the internal calculations of the device or HART communication The shown conversions ...

Страница 17: ... Pound force per square inch 1 psi 68 9 mbar atm Atmospheric pressure 1 atm 1013 mbar mmH2O Millimetre water column 1 mmH2O 0 0981 mbar mH2O Metre water column 1 mH2O 98 1 mbar inH2O Inch water column 1 inH2O 2 49 mbar ftH2O Foot water column 1 ftH2O 29 84 mbar Torr Torr 1 Torr 1 mmHg 1 33 mbar mmHg Millimetre mercury column 1 mmHg 1 33 mbar inHg Inch mercury column 1 inHg 33 86 mbar Table 11 Poss...

Страница 18: ... the output function linear inverse Lower range val Setting the pressure value that shall correspond to 4 mA start of range Upper range val Setting the pressure value that shall correspond to 20 mA end of range Alarm current Select the alarm current High 21 mA or low 3 6 mA Minimum current Limit of the lower output current 3 8 4 0 mA Maximum current Limit of the upper output current 20 21 mA Table...

Страница 19: ...ithin the nominal range of the device Please note that when the turndown is increased the measurement error also increases If you use a very small range you must therefore accept a significant measurement error We recommended a maximum turndown of 10 1 The lower range value must be below the upper range value For an inverse characteristic curve select the output function setting inverse 6 4 5 4 Mi...

Страница 20: ...ntil they are reset by the user The menue item that shows the min max value can also be used to reset it Some of the min max values are also directly accessible from the measured value display in the device data see 6 2 1 OK Figure 10 Display and resetting of the Min Max values 6 4 7 Menue Simulation In the Simulation menue you can simulate the pressure as well as the current to test the subsequen...

Страница 21: ... address between 1 and 63 will not automatically activate the constant current mode This must be done under the menue Current mode see 6 4 8 2 6 4 8 2 Current mode The current mode determines whether the output current of the device is set to respond proportionally to the measured value selection proportional or whether it should remain constant at 4 mA selection constant When the current mode con...

Страница 22: ...es capital letters and special characters For the selection the characters are arranged in the order shown below From the end of the list special character you are automatically guided back to the start number 0 Character set 0123456789 ABCDEFGHIJKLMNOPQRSTUVWXYZ _ 6 4 9 2 Factory reset When carrying out a factory reset all parameters are set to the state at the time of deliv ery This also include...

Страница 23: ...BA_080 Rev 1J8 Pressure transmitter PASCAL CV4 Page 23 24 ...

Страница 24: ...and layout 1st value Content for 1st value in the selected layout Content for further values up to four Decimal point Selection of the decimal places of the 1st value by specifying the decimal point Backlight Switch backlight on off Measurem Output Damping Setting the damping of the output signal Output function Setting the output function linear inverse Lower range val Setting of the pressure val...

Отзывы: