BA_060 Rev 1B6 Pressure transmitter PASCAL CS 

Page 3/20 

nal  range  might  cause  a  zero  point  offset.  In  this  case  a  zero  point  adjustment  might  be 
necessary. 

  

3.2  Electrical Connection 

Complete the mechanical installation before you connect the device electrically. 

Set up all electrical connections while the voltage supply is switched off. 

  

Permissible supply voltage:  

U

v

 = 14…30 VDC 

Permissible load:  

R

a

 = (U

v

 – 14 V) / 0,022 A 

 

  

4-pole connector 

8-pole connector 

(for switching outputs) 

Explanations 

 

  

(  )

(+)

(-)

n.c.

 

Pgm1

Pgm2

(+)

(-)

S1/S2

(+) o. (-)

S1

S2

(   )

 

(+) 

plus-side of supply 

(-) 

minus-side of supply 

n.c. 

Not connected 

S1/S2 

Common  pin  of  switching 
outputs (see below) 

S1 

switching output 1 

S2 

switching output 2 

Pgm 1/2 

programming pins 

 

  

Figure 1: Pin assignment for M12 circular connector (device side) 

  

3.2.1 

Connecting the switching outputs (optional) 

The  switching  outputs  are  potential-free. 
They  are  electrically  isolated  from  the  sup-
ply side (see Figure 2). 

Therefore  you  can  connect  the  load  on  the 
high-side (PNP-style) or the low-side (NPN-
style) as long as you use only one switching 
output. 

S1

S2

(+)

(-)

 

  

 

Figure 2: Switching outputs isolated from supply 

  

Due to the limited number of pins either the low-side or the high-side is combined internally 
and routed to Pin 5. Therefore you have to connect both loads as shown below if you want 
to use both switching outputs. 

  

Содержание PASCAL CS Series

Страница 1: ...Notes 2 1 2 Intended Use 2 1 3 Conformity with EU Regulations 2 2 Transportation and Storage 2 3 Installation and Commissioning 2 3 1 Mechanical Installation 2 3 2 Electrical Connection 3 3 3 Adjusti...

Страница 2: ...CE marking on the device certifies its compliance with the applicable EU Directives for placing products on the market within the European Union The following guidelines apply to these devices PED Dir...

Страница 3: ...c Not connected S1 S2 Common pin of switching outputs see below S1 switching output 1 S2 switching output 2 Pgm 1 2 programming pins Figure 1 Pin assignment for M12 circular connector device side 3 2...

Страница 4: ...itching unit 1 switching unit 2 output function hysteresis normally open hysteresis normally open switch point 40 of measuring range 80 of measuring range reset point 20 of measuring range 60 of measu...

Страница 5: ...nformation can be found in the relevant data sheet Permissible ambient temperature 20 85 C The measured value is shown on the four digit display The LEDs above the display indi cate the switch states...

Страница 6: ...ning Opening pressurized lines might cause severe injuries Danger of severe injuries or damage Relieve the process pressure before attempting to remove the device Shut off the pressure supply for all...

Страница 7: ...on Both LEDs flash rapidly Table 2 Feedback to operator when buttons are pressed The switching outputs are not affected by the LED flashing When there is no button pressed the output states are displa...

Страница 8: ...hen you are in the main menue rEt returns you to display mode At the end of a menue typically the rEt item you return to the first menue item by pressing the down arrow button again Similarly you can...

Страница 9: ...Each list contains the rEt item which allows you to return to the next higher menue level The middle button stores your selection Stor appears on the display to confirm that the value has been stored...

Страница 10: ...e shown With the opposite arrow button you can return to the previ ous value You confirm the selected digit with the middle button and proceed to the next digit You can cancel the value entry at any t...

Страница 11: ...he basic menue contains the following items Display Designation Description Measuring unit Setting the measuring unit via a parameter list Set zero point Teach lower range Setting the applied pressure...

Страница 12: ...uttons and confirm with the mid dle button This extra step prevents any unintentional zero shift while navigating the menue With the final confirmation the applied pressure is stored as zero point don...

Страница 13: ...e Resetting a pointer is confirmed by showing on the display Display Designation Description Value of min max pointer Value of min max pointer in the selected measuring unit Clear Reset the stored poi...

Страница 14: ...be displayed in two ways either by pressing the middle button in display mode or alternating with the measured value When displayed alternating with the meas ured value the display periods for the me...

Страница 15: ...enue SP The switch point menue contains the functions for setting the first and second switch point The menue items vary depending on whether you select a hysteresis or frame function Independently fr...

Страница 16: ...Hno When you select a frame function the menue items for switch point and reset point are replaced by the upper and lower frame limits The minimum difference of the frame limits is also 0 5 of the mea...

Страница 17: ...ally closed If the pressure is above the switch point is open At the lower range limit the switch is closed Frame normally open Inside of the frame the switch is closed At the lower range limit the sw...

Страница 18: ...umber of alphanumerical segments on the display hardware and soft ware versions are split into two separate items and serial number into four items 6 6 2 Reset to factory settings rES You can reset th...

Страница 19: ...BA_060 Rev 1B6 Pressure transmitter PASCAL CS Page 19 20...

Страница 20: ...ay direction 0 normal 180 rotated Setting the decimal places zero to three fixed decimal places or automatic Configuring the switching outputs only if available Switch point or upper frame limit of th...

Отзывы: