9.
Technical and safety data
TECHNICAL SPECIFICATIONS idOil Solar alarm unit
Dimensions
200 mm x 400 mm x 132 mm (w x h x d)
Enclosure
Material: polycarbonate
IP rating: IP43 with two ventilation devices
Weight
8,0 kg
Operating environment
Temperature: -30ºC…+60ºC
Max. elevation above sea level 3,000 m
Relative humidity RH 100%
Battery
12 VDC, 7 Ah lead-acid battery
Power consumption
Max. 1,9 VA
Typical 0,1 mVA (on low-power mode)
Alarm indication
GSM text message AND/OR
Xenon beacon AND/OR
Potential free relay output (bistabe latching
relay)
Alarm and Communication Unit
idOIl-30 Battery or idOil-30 Battery 3G
(See chapter 3. System components)
Sensors
idOil-OIL and/or idOil-SLU and/or idOIl-LIQ
(See chapter 3. System components)
ATEX and IECEx
Ex classification
Special terms (X)
VTT 16 ATEX 018X
IECEx VTT 16.0005X
idOIl-30 Battery / idOil-30 Battery 3G
II (1) G [Ex ia Ga] IIB
Ta = -30 °C…+60 °C
Exi connection values
Um = 30 V DC, Uo = 14.5 V, Io = 78 mA,
Po = 367 mW, R = 243 Ω
Max. impedance of the current loop between
the control unit and a sensor
68 Ω
Manufacturing year:
Please see the serial number on the type
plate.
xxxxxxx x xxx xx YY x
where YY = manufacturing year
(e.g. 18 = 2018)
Installation and Operating Instructions | idOil Solar
54/58
DOC001599-EN-3