LAARS’ ProtoNode Startup Guide
Page 36 of 43
Appendix C.
Vendor Information - Laars
Appendix C.1. Sola Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks
Point Name
Modbus
Register
BACnet
Object
Type
BACnet
Object
ID
N2 Data
Type
N2
Point
Address
Lon Name
Lon SNVT
Demand source
40007
AI
1
AI
1
nvoXDemSrc
SNVT_count_inc_f
Outlet sensor
40008
AI
2
AI
2
nvoXOutletSensor
SNVT_count_inc_f
Firing rate
40009
AI
3
AI
3
nvoXFiringRate
SNVT_count_inc_f
Fan speed
40010
AI
4
AI
4
nvoXFanSpeed
SNVT_count_inc_f
Flame signal
40011
AI
5
AI
5
nvoXFlameSignal
SNVT_count_inc_f
Inlet sensor
40012
AI
6
AI
6
nvoXInletSensor
SNVT_count_inc_f
DHW sensor
40013
AI
7
AI
7
nvoXDHWSensor
SNVT_count_inc_f
S5 sensor
40014
AI
8
AI
8
nvoXS5Sensor
SNVT_count_inc_f
Stack sensor
40015
AI
9
AI
9
nvoXStackSensor
SNVT_count_inc_f
4 - 20 mA remote ctl input
40016
AI
10
AI
10
nvoXRemCtlInput
SNVT_count_inc_f
Active CH setpoint
40017
AI
11
AI
11
nvoXAct_CH_SP
SNVT_count_inc_f
Active DHW setpoint
40018
AI
12
AI
12
nvoXAct_DHW_SP
SNVT_count_inc_f
Active LL setpoint
40019
AI
13
AI
13
nvoXAct_LL_SP
SNVT_count_inc_f
Analog modulation input
40022
AI
14
AI
14
nvoXAnaModInput
SNVT_count_inc_f
Burner control status
40033
AI
15
AI
15
nvoXBrnrCtlStat
SNVT_count_inc_f
Lockout code
40035
AI
16
AI
16
nvoXLockoutCode
SNVT_count_inc_f
Alarm reason
40036
AI
17
AI
17
nvoXAlmReason
SNVT_count_inc_f
Hold code
40041
AI
18
AI
18
nvoXHoldCode
SNVT_count_inc_f
CH status
40065
AI
19
AI
19
nvoXCH_Status
SNVT_count_inc_f
CH setpoint source
40066
AI
20
AI
20
nvoXCH_SP_Src
SNVT_count_inc_f
CH heat demand
40067
AI
21
AI
21
nvoXCH_HeatDmnd
SNVT_count_inc_f
CH burner demand
40068
AI
22
AI
22
nvoXCH_BrnrDmnd
SNVT_count_inc_f
CH requested rate
40069
AI
23
AI
23
nvoXCH_ReqRate
SNVT_count_inc_f
DHW status
40081
AI
24
AI
24
nvoXDHW_Status
SNVT_count_inc_f
DHW Priority Count
40083
AI
25
AI
25
nvoXDHW_PriCnt
SNVT_count_inc_f
DHW heat demand
40084
AI
26
AI
26
nvoXDHW_HeatDmnd
SNVT_count_inc_f
DHW burner demand
40085
AI
27
AI
27
nvoXDHW_BrnrDmnd
SNVT_count_inc_f
DHW requested rate
40086
AI
28
AI
28
nvoXDHW_ReqRate
SNVT_count_inc_f
DHW pump status
40101
AI
29
AI
29
nvoXDHW_PmpStat
SNVT_count_inc_f
LAARS’ ProtoNode Startup Guide
Page 37 of 43
DHW Pump Idle Days Count
40105
AI
30
AI
30
nvoXDHW_PpIdDyCt
SNVT_count_inc_f
System pump status
40106
AI
31
AI
31
nvoXSysPmpStatus
SNVT_count_inc_f
System Pump Idle Days Count
40108
AI
32
AI
32
nvoXSysPmpIdDyCt
SNVT_count_inc_f
Boiler pump status
40109
AI
33
AI
33
nvoXBlrPmpStatus
SNVT_count_inc_f
Boiler Pump Idle Days Count
40111
AI
34
AI
34
nvoXBlrPmpIdDyCt
SNVT_count_inc_f
Burner run time
40131/40132
AV
35
AO
35
nvi/nvoXBrnrRunTime
SNVT_count_inc_f
DHW pump cycle count
40135/40136
AV
36
AO
36
nvi/nvoXDHWPmpCycCnt SNVT_count_inc_f
System pump cycle count
40137/40138
AV
37
AO
37
nvi/nvoXSysPmpCycCnt
SNVT_count_inc_f
Boiler pump cycle count
40139/40140
AV
38
AO
38
nvi/nvoXBlrPmpCycCnt
SNVT_count_inc_f
Controller Cycle Count
40143/40144
AI
39
AI
39
nvoXCtllerCycCnt
SNVT_count_inc_f
Controller run time
40145/40146
AI
40
AI
40
nvoXCtllerRunTim
SNVT_count_inc_f
Lead lag master status
40161
AI
41
AI
41
nvoXLdLgMstrStat
SNVT_count_inc_f
Lead lag slave status
40162
AI
42
AI
42
nvoXLdLgSlavStat
SNVT_count_inc_f
Lead Lag Master Setpoint Source
40163
AI
43
AI
43
nvoXLdLgMstSPSrc
SNVT_count_inc_f
Lead Lag Master Pump Demand
40164
AI
44
AI
44
nvoXLdLgMstPpDmd
SNVT_count_inc_f
Outdoor temperature
40171
AI
45
AI
45
nvoXOutdoorTmp
SNVT_count_inc_f
CH setpoint
40212
AV
46
AO
46
nvi/nvoXCH_SP
SNVT_count_inc_f
CH TOD setpoint
40213
AV
47
AO
47
nvi/nvoXCH_TOD_SP
SNVT_count_inc_f
DHW Demand Switch
40449
AV
48
AO
48
nvi/nvoXDHW_DmdSwitc SNVT_count_inc_f
Outlet high limit setpoint
40465
AV
49
AO
49
nvi/nvoXOutltHiLimSP
SNVT_count_inc_f
Lead Lag setpoint
40547
AV
50
AO
50
nvi/nvoXLeadLagSP
SNVT_count_inc_f
Leadlag modulation sensor
40559
AV
51
AO
51
nvi/nvoXLdLgModSensr
SNVT_count_inc_f
Warm weather shutdown setpoint
40629
AV
52
AO
52
nvi/nvoXWrmWthrShtSP
SNVT_count_inc_f
Lead Lag active service
40769
AI
53
AI
53
nvoXLdLgActSrvc
SNVT_count_inc_f
Slave 1 State
40771
AI
54
AI
54
nvoXSlv1State
SNVT_count_inc_f
Slave 1 firing rate
40773
AI
55
AI
55
nvoXSlv1FirRat
SNVT_count_inc_f
Slave 2 State
40775
AI
56
AI
56
nvoXSlv2State
SNVT_count_inc_f
Slave 2 firing rate
40777
AI
57
AI
57
nvoXSlv2FirRat
SNVT_count_inc_f
Slave 3 State
40779
AI
58
AI
58
nvoXSlv3State
SNVT_count_inc_f
Slave 3 firing rate
40781
AI
59
AI
59
nvoXSlv3FirRat
SNVT_count_inc_f
Slave 4 State
40783
AI
60
AI
60
nvoXSlv4State
SNVT_count_inc_f
Slave 4 firing rate
40785
AI
61
AI
61
nvoXSlv4FirRat
SNVT_count_inc_f
Slave 5 State
40787
AI
62
AI
62
nvoXSlv5State
SNVT_count_inc_f
Slave 5 firing rate
40789
AI
63
AI
63
nvoXSlv5FirRat
SNVT_count_inc_f
Slave 6 State
40791
AI
64
AI
64
nvoXSlv6State
SNVT_count_inc_f
LAARS Heating Systems