Page 114
Code Description
L or
H
Procedure
210
Invalid Postpurge time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
211
Invalid Power up with lockout setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
212
Invalid Preignition time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
213
Invalid Prepurge rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
214
Invalid Prepurge time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
215
Invalid Purge rate proving setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
216
Invalid Run flame failure response
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
217
Invalid Run stabilization time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
218
Invalid Stack limit enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
219
Invalid Stack limit response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
220
Unconfigured Delta T limit setpoint
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Содержание NTV1000
Страница 2: ......
Страница 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Страница 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Страница 37: ...NeoTherm Boilers and Water Heaters Page 33...
Страница 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Страница 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Страница 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Страница 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Страница 133: ...NeoTherm Boilers and Water Heaters Page 129 Fig 143 Heat Exchanger Components Fig 144 Burner Detail...
Страница 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Страница 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Страница 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Страница 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...