Distance from Gas Meter or Last Stage Regulator

Model and

Gas Type

0-100'

0-31 m

100-200'

31-61m

200-300'

61-91m

200 natural

1¼"

3.2 cm

1¼"

3.2 cm

1¼"

3.2 cm

200 propane

1"

2.5 cm

1"

2.5 cm

1¼"

3.2 cm

300 natural

1¼"

3.2 cm

1½"

4.0 cm

1½"

4.0 cm

300 propane

1

2.5 cm

1¼"

3.2 cm

1¼"

3.2 cm

400 natural

1¼"

3.2 cm

1½"

4.0 cm

2"

5.0 cm

400 propane

1¼"

3.2 cm

1¼"

3.2 cm

1½"

4.0 cm

Notes:

1.  These figures are based on 1/2" (0.12 kPa) water column pressure drop.

2.  Check supply pressure and local code requirements before proceeding with work.

3.  Pipe fittings must be considered when determining gas pipe sizing

.

Table 7.  Gas Piping Size.

SECTION 3  Gas Supply and Piping

3.A  Gas Supply and Piping

Gas piping should be supported by suitable 

hangers or floor stands, not by the appliance.

This appliances’s gas train allows the user to 

pipe the gas from either the right side or the left side 

of the unit. As shipped, the right side of the gas train is 

capped off, and there is a manual valve on the left side. 

If desired, the manual valve on the left side of the gas 

train may be moved to the right side, and the cap on 

the right side may be moved to the left. 

Review the following instructions before 

proceeding with the installation.

1.  Verify that the appliance is fitted for the proper 

type of gas by checking the rating plate. All 

models are equipped to operate at elevations up 

to 10,000 feet (3050m). These appliances may 

be adjusted to operate properly at altitudes above 

2500 feet (see Section 6.5.2) and the input will be 

reduced if the heating value of the gas supply is 

below sea level values.

2.  Verify the inlet gas supply pressure.  

Min

Max

Natural Gas

3.5” W.C.

10.5” W.C.

Propane

8” W.C.

13” W.C.

3.  Refer to 

Table 7

, to size supply.

4.  Run gas supply line in accordance with all 

applicable codes.

5.  Locate and install manual shutoff valves in 

accordance with state and local requirements.

6.  A sediment trap must be provided upstream of 

the gas controls.

7.  All threaded joints should be coated with 

piping compound resistant to action of liquefied 

petroleum gas.

8.  The appliance and its individual shutoff valve 

must be disconnected from the gas supply piping 

during any pressure testing of that system at test 

pressures in excess of 0.5 psig (3.45 kpa).

9.  The unit must be isolated from the gas supply 

system by closing its individual manual shutoff 

valve during any pressure testing of the gas 

supply piping system at test pressures equal to or 

less than 0.5 psig (3.45 kpa).

10.  The appliance and its gas connection must be 

leak tested before placing it in operation.

11.  Purge all air from gas lines.

   WARNING

Do not use open flame to check for leaks. 

An open flame could lead to explosion, which 

could result in property damage, serious injury 

or death.

   AVERTISSEMENT

Ne recherchez pas les fuites avec une flamme 

nue. Une flamme nue peut provoquer une 

explosion qui peut causer des dommages 

matériels, de sérieuses blessures corporelles 

ou la mort.

NOTE

: This appliance and all other gas appliances 

sharing the gas supply line must be firing at 

maximum capacity to properly measure the inlet 

supply pressure. The pressure can be measured at 

the supply pressure port on the gas valve. Low gas 

pressure could be an indication of an undersized 

gas meter, undersized gas supply lines and/or an 

obstructed gas supply line.

Mighty Therm

2

  (200, 300, 400) Install & Operating

Содержание MIGHTY THERM2 MT2H

Страница 1: ...tion and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty For indoor...

Страница 2: ...sted Piping Diagrams 17 19 4 B 2 Hot Water Supply Piping Water Heater 20 4 B 3 Water Flow Requirements Water Heater 20 4 B 4 Combined Water Heating potable and Space Heating Water Heater 20 4 B 5 Free...

Страница 3: ...Le hydronique une chaudi re ou un chauffe eau doit tre install conform ment aux proc dures d taill es dans ce manuel ou le chauffage garantie peut tre annul e L installation doit tre conforme aux exi...

Страница 4: ...must include the serial number and model this information can be found on the rating plate installation date and name of the installer Shipping costs are not included in the warranty coverage Some ac...

Страница 5: ...is appliance and are field convertible Model A Combustion Air Connection B Vent Connection C Horizontal Cat III Vent Pipe Size in cm in cm in cm in cm 200 20 5 52 4 10 5 13 4 10 300 26 5 67 4 10 6 15...

Страница 6: ...ack of this appliance and are field convertible Model A Combustion Air Connection B Vent Connection C Horizontal Cat III Vent Pipe Size in cm in cm in cm in cm 200 20 5 52 4 10 5 13 4 10 300 26 5 67 4...

Страница 7: ...ry 1 Vent 6 15 2 Horizontal Category 3 Vent per UL 1738 venting system supplier s instructions 1 2 5 cm when b vent is used When vent and or combustion air connects to the back recommended clearance i...

Страница 8: ...th the outdoors or when communicating to the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4000 Btu hr 5 5 square cm kW of total input rating of all...

Страница 9: ...e shared vertical duct called a common vent Special care must be taken by the installer to ensure safe operation In the event that the common vent is blocked it is possible especially for fan assisted...

Страница 10: ...all appliances to be common vented for instructions warnings restrictions and safety requirements If safe operation of all appliances connected to a common vent cannot be assured including prevention...

Страница 11: ...a e l C G H Clearance to each side of centerline extended above meter regulator assy 3 ft 91 cm within a height of 15 ft 4 6 m m c 1 9 t f 3 t e l t u o t n e v r o t a l u g e r e c i v r e s o t e c...

Страница 12: ...on monoxide detector with an alarm is installed on each additional level of the dwelling building or structure served by the side wall horizontal vented gas fueled equipment It shall be the responsibi...

Страница 13: ...t least 3 feet 0 9m horizontally from the combustion air terminal and locate the vent terminal at least 1 foot 0 3m above the combustion air terminal see Figure 4 2 C 3 Vertical Vent Terminal When the...

Страница 14: ...d extraction comme les hottes de cuisini re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse maximale Ne pas faire fonctionner les ventilateurs d t Fermer...

Страница 15: ...alues 2 Verify the inlet gas supply pressure Min Max Natural Gas 3 5 W C 10 5 W C Propane 8 W C 13 W C 3 Refer to Table 7 to size supply 4 Run gas supply line in accordance with all applicable codes 5...

Страница 16: ...of the boiler or at the time of boiler installation 4 A 3 Water Flow Requirements Boiler A hydronic heating closed loop application recirculates the same fluid in the piping system As a result no new...

Страница 17: ...in the hangers It is recommended that padding be used when rigid hangers are installed This appliance can be used with several different types of readily available storage tanks A pump draws water fr...

Страница 18: ...Page 18 Figure 6 Hydronic Piping Multiple Boilers Low Temperature System Figure 7 Hydronic Piping One Boiler Multi Temperature System LAARS Heating Systems...

Страница 19: ...Page 19 Figure 8 Hydronic Piping Primary Secondary Reverse Return Figure 9 Hydronic Piping Primary Secondary Reverse Return Low Temperature Mighty Therm2 200 300 400 Install Operating...

Страница 20: ...water conditions more than 17 grains per gallon use a non pump mounted heater with a properly sized field installed pump Table 9 specifies water flow rates for water heaters which will enable the user...

Страница 21: ...2 15 11 87 132 170 0 6 1 4 2 3 12 8 6 400 23 35 45 2 0 4 5 7 4 30 19 15 87 132 170 0 6 1 4 2 3 17 11 8 Notes 1 S soft water 1 to 7 5 grains hardness 2 N normal water 7 6 to 17 grains hardness 3 H hard...

Страница 22: ...1 THROUGH 7 5 7 6 THROUGH 17 OVER 17 2 3 4 Figure 11 Water Heater Piping Multiple Heaters One Tank SUPPLY RECIRC CWMU CAUTION THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING CHECK WITH...

Страница 23: ...URE REDUCING VALVE PUMP PRV TPRV Figure 13 Water Heater Piping Multiple Heaters Multiple Tanks CAUTION THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND VALVING CHECK WITH LOCAL CODES AND ORDINANC...

Страница 24: ...ng water level and must be full at all times In accordance with ANSI ASME CSD 1 Section CW 210 and The National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 10 3 5 a water tube boiler shall have a water...

Страница 25: ...K GY V BK GY BK GY BK V W BR BK BR BLK BR BLK R G G W W POWER BK BK BK BK BK BK BL R BL R STAGE 1 GAS VALVE IGN FS E0253400 VAL IGN 240 L1 PSW GND F1 F2 24 VAC TH FC IGN 120 L2 FLOW SWITCH FIELD INTER...

Страница 26: ...BL R W W Y BLK GY V BK GY BK GY BK V W V W BR R BR BK BR BLK BR BLK R BK R BK BR BK BR R Y R G G G G BK W W W POWER BK BK BK BK BK BK BK BK BL R BL R BK STAGE 2 GAS VALVE STAGE 1 GAS VALVE IGN FS E025...

Страница 27: ...K BK BK BL R BL R STAGE 2 GAS VALVE STAGE 1 GAS VALVE IGN FS E0253400 VAL IGN 240 L1 PSW GND F1 F2 24 VAC TH FC IGN 120 L2 HIGH TEM PERATURE LIM IT M ANUAL RESET AQUASTAT FLOW SW ITCH FIELD INTERLOCK...

Страница 28: ...highest point in the circulating loop then the system is ready for operation 14 Refer to local codes and the make up water valve manufacturer s instructions as to whether the make up water valve shoul...

Страница 29: ...OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space hea...

Страница 30: ...and operates using the boiler outlet sensor system supply boiler outlet Using the system Sensor The system sensor can be used to control the setpoint of a primary loop in a primary secondary system or...

Страница 31: ...n to Air Flow Blocked Vent Pressure Switch Air flow and blocked vent status are continuously monitored by the appliance s ignition control at the control s PSW terminal At the start of an ignition seq...

Страница 32: ...r Safety Shutoff Device must be tested To test a Close gas shutoff valve with burner operating b The flame will go out and blower will continue to run for the post purge cycle Three attempts to light...

Страница 33: ...6 Low water cutoffs when installed on a residential hot water heating system the probe should be removed and cleaned every five years When installed on a commercial application the probe should be re...

Страница 34: ...he threads on the pipe nipples for reuse Apply new tape or pipe dope to the pipe nipples threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas and reinst...

Страница 35: ...closing the manual gas valve on the heater 3 Disconnect and remove the wires conduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the...

Страница 36: ...cycling is caused when the load on the boiler system swings rapidly causing frequent cycling between call for heat and satisfied conditions This condition is greatly reduced on two stage units If sho...

Страница 37: ...Air Shutter Blower 2C5000 2C5000 2C5000 19 Assembly Filter Housing 2C3800 2C3800 2C3800 20 Media Filter R2073200 R2073200 R2073200 21 Clip Retaining Filter Media F2022300 F2022300 F2022300 22 Hose Duc...

Страница 38: ...R4C4100 Assembly Tube Heat Exchanger Copper Nickel R2C4120 R3C4120 R4C4120 61 Header Inlet Outlet 2F4122 2F4122 2F4122 62 Header Return 2C4103 2C4103 2C4103 63 Chamber Header Heat Exchanger 2C4001 2C4...

Страница 39: ...T RE0240900 RE0240900 RE0240900 95 Switch Limit High Temperature Hydronic E2304800 E2304800 E2304800 Switch Limit High Temperature Volume Water E2324200 E2324200 E2324200 96 Transformer 24 120 V 50VAC...

Страница 40: ...Page 40 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 22 23 24 25 26 27 28 29 30 31 31 31 31 31 32 20 21 19 Figure 19 Combustion Chamber Components LAARS Heating Systems...

Страница 41: ...Page 41 Figure 20 Jacket Components 40 41 42 48 51 43 44 45 46 47 49 50 52 53 54 54 55 Mighty Therm2 200 300 400 Install Operating...

Страница 42: ...Page 42 60 62 63 63 64 64 73 65 66 67 70 68 72 69B 69A 69A Volume Water Heater Emersion Well This Side Boiler Emersion Well This Side 61 71 Figure 21 Heat Exchanger Components LAARS Heating Systems...

Страница 43: ...Page 43 80 81 85 84 84 86 87 ON OFF 80 82 83 85 86 86 2 STAGE Figure 22 Gas Train Components Mighty Therm2 200 300 400 Install Operating...

Страница 44: ...0 559 1583 Headquarters 20 Industrial Way Rochester NH USA 03867 603 335 6300 Fax 603 335 3355 9 Brigden Gate Halton Hills Ontario Canada L7G 0A3 905 203 0600 Fax 905 636 0666 www Laars com Litho in U...

Отзывы: