9.  After placing the appliance in operation, the 

Burner Safety Shutoff Device must be tested

To test: 

 

(a)  Close gas shutoff valve with burner 

operating.

 

(b)  The flame will go out and blower will 

continue to run for the post purge cycle. 

Three attempts to light will follow. Ignition 

will not occur as the gas is off. The ignition 

control will lockout, and will have to be 

reset by cycling the power before the unit 

will operate.

 

(c)  Open gas shutoff valve. Restart the 

appliance. The ignition sequence will 

start again and the burner will start. The 

appliance will return to its previous mode 

of operation.

6.6.2  High Altitude Adjustment and  

Set-Up

High altitude adjustment must not be made on 

appliances operating at elevations below 2500 ft. (762 m).

No orifice changes are required to adjust the 

Mighty Stack appliances for high altitude. High 

altitude adjustment is accomplished by adjustment 

of the air shutter. A CO

2

 or O

2

 analyzer is required to 

make these adjustments.

Start the adjustment process by checking the CO

2

 

in the “as installed” condition. Adjust the air shutter(s) 

so that the CO

2

 is about 8% or the O

2

 is about 6.8% 

for appliances operating on natural gas. For appliances 

operating on LP Gas adjust the air shutter(s) so that the 

CO

2

 is about 9.2% or the O

2

 is about 6.8%. 

If the appropriate CO

2

 / O

2

 levels cannot be 

achieved by adjusting the air shutter.  Contact the 

Technical Services Department at number shown on 

back page.

The amount of derate will vary depending on 

heating value of the fuel and the elevation at the 

installation site.

   Caution

Should any odor of gas be detected, or if the gas 

burner does not appear to be functioning in a 

normal manner, close main shutoff valve, do not 

shut off switch, and contact your heating contractor, 

gas company, or factory representative.

 Attention

Si vous sentez une odeur de gaz ou si le brûleur 

à gaz ne parait pas fonctionner de manière 

normale, fermez la vanne d’isolement, ne fermez 

aucun interrupteur, et appelez votre entreprise de 

chauffage, la compagnie de gaz ou un représentant 

du fabricant.

6.7  Shutting Down the Mighty Stack

1.  Switch off the main electrical disconnect switch.

2.  Close all manual gas valves.

3.  If freezing is anticipated, drain the Mighty Stack 

and be sure to also protect building piping from 

freezing.

 

This step to be performed by a qualified 

service person.

6.8  To Restart the Mighty Stack

If drained, follow 

Section 6.1

 in this manual for 

proper filling and purging.

1.  Switch off the main electrical disconnect switch.

2.  Close all manual gas valves.

3.  WAIT FIVE (5) MINUTES.

4.  Set the aquastat or thermostat to its lowest 

setting.

5.  Open all manual gas valves.

6.  Reset all safety switches (pressure switch, 

manual reset high limit, etc.).

7.  Set the temperature controller to the desired 

temperature setting and switch on electrical 

power.

8.  Burner will go through a pre-purge period and 

ignitor warm-up period, followed by ignition.

Содержание Mighty Stack MS-080

Страница 1: ...r death Improper installation and or operation will void the warranty For indoor installations as an additional measure of safety Laars strongly recommends installation of suitable Carbon Monoxide det...

Страница 2: ...16 4 4 Combined Water Heating potable and Space Heating 16 4 5 Freeze Protection 16 SECTION 5 Electrical Connections 5 1 Main Power 18 5 2 Field Wiring 18 SECTION 6 Operating Instructions 6 1 Filling...

Страница 3: ...in this manual or the Laars Heating Systems warranty may be voided The installation must conform to the requirements of the local jurisdiction having authority and in the United States to the latest e...

Страница 4: ...r concealed 1 4 Dimensions See Figure 1 1 5 Locating the Appliance The appliance should be located to provide clearances on all sides for maintenance and inspection It should not be located in an area...

Страница 5: ...mensional Data Air and vent connections may be on top or back of the Mighty Stack and are field convertible Size A B C D in cm in cm in cm in cm 199 33 0 84 4 10 5 13 8 75 22 300 39 0 99 4 10 6 15 15...

Страница 6: ...m 199 5 13 4 10 4 10 50 15 3 CA003101 CA003201 300 6 15 5 13 4 10 50 15 3 CA003102 CA003201 399 7 18 6 15 6 15 50 15 3 CA003103 CA003202 Table 1 Horizontal Vent Combustion Air Parameters Appliance Su...

Страница 7: ...communicating with the outdoors or when communicating to the outdoors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4000 Btu hr 5 5 square cm kW of total inp...

Страница 8: ...dered Category III In the U S the National Fuel Gas Code ANSI Z223 1 or in Canada the Natural Gas and Propane Installation Code CSA B149 1 defines a Category I vent system and includes rules and table...

Страница 9: ...living spaces common venting should not be applied and appliances should each be vented separately 2 2 4 Category III Vent When the Mighty Stack is vented with horizontal discharge it must be installe...

Страница 10: ...non mechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inches 91 cm to any other appliance to side of...

Страница 11: ...ith alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision cannot be met at the time of completion of installation the own...

Страница 12: ...0 feet 3 0m and high enough above the roof line to prevent blockage from snow When the combustion air is taken from the roof the combustion air must terminate at least 12 30cm below the vent terminal...

Страница 13: ...ventilateurs d t Fermer les registres des chemin es 4 Mettre l appareil inspect en marche Suivre les instructions d allumage R egler le thermostat de fa on continue 5 Faire fonctionner le br leur prin...

Страница 14: ...Laars Heating Systems Page 14 Figure 4 Venting...

Страница 15: ...upply is below sea level values 2 The maximum inlet gas pressure must not exceed 13 w c 3 2kPa The minimum inlet gas pressure is 5 in w c 1 2 kPa 3 Refer to Table 7 size supply 4 Run gas supply line i...

Страница 16: ...high enough to prevent scaling but low enough to prevent tube erosion For extremely soft or hard water cupro nickel tubes are available Contact a Laars representative if you have questions or concerns...

Страница 17: ...Mighty Stack Page 17 Figure 4 Suggested Plumbing Figure 5 Suggested Plumbing Three Units in first out last...

Страница 18: ...ode Canadien de l lectricit 1 re partie Canadian Electrical Code Part 1 CSA C22 1 au Canada N utilisez pas les tuyauteries d eau ou de gaz pour mettre la terre les pi ces m talliques de la chaudi re d...

Страница 19: ...Mighty Stack Page 19 Figure 7 Wiring Diagram ON OFF Water Heater...

Страница 20: ...tches this 24V from the input 6 4 Sequence of Operation The pump time delay relay will receive a signal to initiate The pump terminals on the field wiring terminals strip will energize a pump Once the...

Страница 21: ...mproper setup is not covered by the limited warranty 1 Using this manual make sure the installation is complete and fully in compliance with the instructions 2 Determine that the appliance and system...

Страница 22: ...justing the air shutter Contact the Technical Services Department at number shown on back page The amount of derate will vary depending on heating value of the fuel and the elevation at the installati...

Страница 23: ...functioning It is strongly recommended that a qualified service technician inspect the basic items listed below every year a Ignition control b Ignitor c Water temperature control d Automatic gas val...

Страница 24: ...emove the mounting screws and remove the transformer Replace transformer in the reverse order 7 2 8 Flow Switch The Mighty Stack uses a paddle type flow switch to ensure that the unit has water flow b...

Страница 25: ...ion of soot or corrosion on the outside of the heat exchanger can be easily removed Use a wire brush to remove loose soot and scale from the heat exchanger 9 NOTE While the heat exchanger is out of th...

Страница 26: ...gnition If the gas supply pressure is proper and the gas valves are functioning properly then burners should be inspected There should be no distortion or perforations in the burners outside of the ac...

Страница 27: ...utter Blower 2C5000 2C5000 2C5000 20 Assembly Filter Housing 40L3900 40L3900 40L3900 Assembly Removeable Filter 40L3800 40L3800 40L3800 Media Filter R2073200 R2073200 R2073200 21 Hose Duct Flexible 4...

Страница 28: ...r Copper R2C4100 R3C4100 R4C4100 Assembly Tube Heat Exchanger Cupro Nickel R2C4120 R3C4120 R4C4120 2 Header Inlet Outlet 2F4122 2F4122 2F4122 3 Header Return 2C4103 2C4103 2C4103 4 Chamber Header Heat...

Страница 29: ...0 E2056300 11 Block Terminal Double Row 16 Position E2327500 E2327500 E2327500 12 Jumper Terminal Block E0102000 E0102000 E0102000 13 Label Terminal Control Contacts H2339100 H2339100 H2339100 14 Harn...

Страница 30: ...Laars Heating Systems Page 30 Figure 9 Combustion Chamber Components...

Страница 31: ...Mighty Stack Page 31 Figure 10 Jacket Components...

Страница 32: ...Laars Heating Systems Page 32 Figure 11 Heat Exchanger Components...

Страница 33: ...Mighty Stack Page 33 Figure 12 Gas Train Components...

Страница 34: ...Laars Heating Systems Page 34 Figure 13 Control Panel Components...

Страница 35: ...Mighty Stack Page 35 Figure 14 Pump Assembly Components...

Страница 36: ...603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1110 Document 2155 Dimensions and sp...

Отзывы: