LAARS Heating Systems
Page 30
SECTION 9.
Modes of Operation
The Mascot II control allows the boiler to operate
in many different modes of operation. The mode must
be selected based upon the requirements of the
installation. The following sections describe the basic
operation of the Mascot II in each of the different
modes. Familiarize yourself with each mode and how
the operation of the boiler varies, depending upon the
installation and inputs the control is monitoring.
9.1 Hydronic Heating Demand
When using the Mascot II for hydronic heating a
call for heat must be supplied to the "T-T or Interlock"
terminal. Once the call is supplied the control starts the
boiler and system pumps, shifts the 3-way valve
position and begins the ignition process. The ignition
process consists of a prepurge, trial for ignition, and run
period. The prepurge period starts on a call for heat
once the fan RPM reaches a preset level. The trial for
ignition period follows once the start-up RPM of the fan
is reached. The trial for ignition period lasts 4 seconds
during which the direct spark ignition system and gas
valve are energized. At the end of the trial for ignition
period the flame signal is compared with the preset
flame threshold value. If the flame signal is higher than
the flame threshold the Mascot II enters "run". If the
flame signal is below the threshold the Mascot II returns
to prepurge and starts the ignition process over. In "run"
the Mascot II monitors the flame signal, call for heat,
safeties, and water temperatures and modulates as
needed between 100% and 20% of rate to satisfy the call
for heat.
9.2 Hydronic Heating with Outdoor Reset
Outdoor reset varies the control point setpoint
based on the actual outdoor temperature. The reset
function works as shown in
Figure 24
. When the
outdoor air temperature reaches the "high outdoor
temperature setpoint (HOD), the control point setting is
adjusted to the low boiler temperature setpoint (LBT).
When the outdoor air temperature reaches the low
outdoor temperature setpoint (LOD), the control
setpoint is adjusted to the CH/Outlet water setpoint
temperature. HOD, LOD and LBT can be adjusted by
accessing SETUP mode. CH setpoint is adjustable from
the USER menu structure.
9.3 Hydronic Heating Using External
Modulation Control
When using the Mascot II for hydronic heating
with external modulation control a call for heat must be
supplied to the "T-T" terminal. Once the call is supplied
the control starts the boiler and system pumps and
begins the ignition process. In "run" the Mascot II
NAME
FUNCTION
DEFAULT VALUE
CH on
Burner demand begins when the
5°F
differential
outlet water temperature reaches
"Outlet water temperature setpoint"
minus "CH on differential"
CH off
Burner demand ends when the
5°F
differential
outlet water temperature reaches
"Outlet water temperature setpoint"
plus "CH off differential"
DHW on
Burner demand begins when the
2°F
differential
outlet water temperature reaches
"Outlet water temperature setpoint"
minus "DHW on differential"
DHW off
Burner demand ends when the
7°F
differential
outlet water temperature reaches
"Outlet water temperature setpoint"
plus "DHW off differential"
Pump
Operates the pump for the overrun
1
overrun
time after the burner demand
minute
has ended
High
Locks the boiler out when the high
200°F
limit
limit temperature is reached
(requires manual reset)
Flame
Flame signals lower than the flame
0.8Vdc
threshold
threshold interrupt burner operation
Table 12. Default Control Settings.
Содержание Mascot II
Страница 6: ...LAARS Heating Systems Page 6 Figure 2 Location of Components...
Страница 27: ...Mascot II Boilers and Water Heaters Page 27 Figure 22 Wiring Diagram...
Страница 42: ...LAARS Heating Systems Page 42 Figure 28 Panel Assembly Door Top...
Страница 43: ...Mascot II Boilers and Water Heaters Page 43 Figure 29 Panel Assembly Door Middle...
Страница 44: ...LAARS Heating Systems Page 44 Figure 30 Panel Assembly Door Bottom...
Страница 45: ...Mascot II Boilers and Water Heaters Page 45 Figure 31 Base Jacket Assembly...
Страница 46: ...LAARS Heating Systems Page 46 Figure 32 Heat Exchanger Cabinet Fan...
Страница 47: ...Mascot II Boilers and Water Heaters Page 47 Figure 33 Heat Exchanger Burner Components...
Страница 48: ...LAARS Heating Systems Page 48 Figure 34 Pump Assembly Components...
Страница 49: ...Mascot II Boilers and Water Heaters Page 49 Figure 35 Plumbing Components...
Страница 50: ...LAARS Heating Systems Page 50...
Страница 51: ...Mascot II Boilers and Water Heaters Page 51...