Page 28
4.8.2
Indoor Combustion Air
Read and Follow Sections 4.3 Guidelines First.
1. Insert the termination end cap into the intake air duct.
2. Provide two openings to allow for circulation of
combustion air as specified by ANSI Z224.1/NFPA 54.
In Canada refer to CAN/CSA B-149.1
NOTE: The FT needs fresh air for safe operation and
must be installed so there are provisions for
adequate combustion and ventilation air.
Model
FTCW140
FTCW199
Maximum Input (BTU/H)
140,000
199,000
Indoor make up air is provided, a mini
-
mum free area of 1 in 2 per 1,000 BTU/H
140 in2 13 1/4"
(W) x 13 1/4" (H)
199 in2 13 1/4"
(W) x 13 1/4" (H)
4.9
Vent / Air Pipe Termination
Vent Air Terminations:
After connecting terminals install vent screens on
both the vent and air inlet.
Two 3” vent screens are included with each unit.
Additional replacement screens are available for
purchase.
2” Vent Screen P/N - FT1508
3” Vent Screen P/N - FT1730
Vertical Vent Termination
• Direct Vent - Vertical Terminations
with Sloped Roof
Vent Screens
are required
Содержание FT Series
Страница 49: ...The FT Series Wall Mounted Combination Boiler Page 49 4 21 Control Board Electrical Diagram Control Board...
Страница 50: ...Page 50 4 22 Ladder Diagram F B level Air Pressure Sensor...
Страница 66: ...Page 66 6 2 Fault Tree Analysis 1 Flame detection...
Страница 81: ...Mascot FT Combination Boiler Page 81 Heat Exchanger Tank _ Feature Heat Exchanger Tank FTCW140...
Страница 83: ...Mascot FT Combination Boiler Page 83 Fan Gas Valve _ Feature Blower and Gas Valve FTCW140...
Страница 85: ...The FT Series Wall Mounted Combination Boiler Page 85 FTCW199...
Страница 91: ...The FT Series Wall Mounted Combination Boiler Page 91 Fan Gas Valve _ Feature Fan Gas Valve _ Feature FTCW199...