The FT Series Wall Mounted, Combination Boiler
Page 27
4.8
Air Supply and Vent Connections
4.7.2 Direct Venting
The boiler uses 3˝ or 2˝ diameter exhaust and 3˝
or 2˝diameter intake air ducts. To ensure the draw
of air directly from and exhaust of air directly to the
outside of the building, create an airtight seal from
the boiler collar to the vent termination.
(For installations in Canada)
field-supplied plastic
vent piping must comply with CAN/CSA B149.1
(latest edition) and be certified by the Standard
For Type BH Gas Venting Systems, ULC-S636.
Components of this listed system must not be
interchanged with other vent systems or unlisted
pipes or fittings. All plastic components and
specified primers and glues of the certified vent
system must be from a single system manufacturer
and must not be intermixed with another system
manufacturer’s parts.
Tightening — Boiler Collar (Socket) to Vent
Pipe & Inlet Pipe
- Clean and dry your selected PVC, CPVC vent
pipe and boiler collar (socket).
- You can select to the size of vent pipe(2˝ & 3˝),
according to the installation conditions.
- Push the pipe into the collar (socket) until it
touches the bottom of the socket fitting.
- For 2” installations, install a field supplied 3” to
2” adaptor. Adaptor must be installed in vertical
section of piping only.
Combination Boiler Model
3˝ Combustion Air / Vent Pipe
2˝ Combustion Air / Vent Pipe
Max
Max
FTCW140/199
100´ (30M)
50´
*
(15M
*
)
Table 5. Maximum Vent / Air Pipe Lengths for either 3” or 2 “ Pipes
2” pipe connected, using an adapter
3” to 2”
adapter
is NOT
included.
3” pipe
4.8.1
Vent / Air Pipe Lengths
NOTE : For each elbow, reduce maximum allowable length
• 5 feet (1.5M) for each 3-inch 90-degree elbow
• 2.5 feet (0.75M) for each 3-inch 45-degree elbow
• 8 feet (2.4M) for each 2-inch 90-degree elbow
• 4 feet (1.2M) for each 2-inch 45-degree elbow
• Maximum of 6 elbows for 3” vent. Max of 4 elbows for 2” vent.
NOTE: When using a 2” vent pipe, DIP Switch 4 must be in the OFF position.
For 3” Pipe vent, the default setting for DIP 4 is ON.
Refer to Section 4.19
*
Propane models are limited to 25 equivalent feet of 2” vent
Содержание FT Series
Страница 49: ...The FT Series Wall Mounted Combination Boiler Page 49 4 21 Control Board Electrical Diagram Control Board...
Страница 50: ...Page 50 4 22 Ladder Diagram F B level Air Pressure Sensor...
Страница 66: ...Page 66 6 2 Fault Tree Analysis 1 Flame detection...
Страница 81: ...Mascot FT Combination Boiler Page 81 Heat Exchanger Tank _ Feature Heat Exchanger Tank FTCW140...
Страница 83: ...Mascot FT Combination Boiler Page 83 Fan Gas Valve _ Feature Blower and Gas Valve FTCW140...
Страница 85: ...The FT Series Wall Mounted Combination Boiler Page 85 FTCW199...
Страница 91: ...The FT Series Wall Mounted Combination Boiler Page 91 Fan Gas Valve _ Feature Fan Gas Valve _ Feature FTCW199...