background image

Page 8 of 12

Page 68

5.8  Installer Parameters (continued)

Index 

Default

Parameter 

Description 

 1: EH 

Error History

History fault code (E0~E9) 

 2: cE 

OFF

Clear Error History 

Clearing of error History buffer 

 3: In 

OFF

System initialize 

System initialize to default 

 4: Fu 

GA

Flow unit 

gallon / liter

 5: St 

On

Heat storage function 

Heat storage function On/Off

 6: OH 

68°F (20°C)

Maximum Outdoor Temperature

 Range: (Minimum Outdoor Tempe 9°F) to 110°F 

 7: OL 

30°F (-1°C)

Minimum Outdoor Temperature

Range: -4°F to (Maximum Outdoor Temperature -9°F)

 8: FH 

0

Max fan 

Adjusts Maximum Fan Speed

Range: -30 - +30              Default 00   Note: Factory set - do not adjust

 9: FL 

0

Min fan 

Adjusts Minimum Fan Speed Range: -30 -+30 Note: Factory set - do not adjust

10: dr 

NO

Delete running time 

Delete running time

11: dI 

NO

Delete igniting times 

Delete igniting times

12: bt

0

Outdoor reset Boost Delay Time

When using the outdoor reset sensor, if a call for heat is longer than Boost delay time, 

the boiler will Boost to the maximum supply water temperature - see parameter 16CH.

 

 (0~120 min)

13: Ft

1 min

Delay time for heating burner 

operation

Burner does not operate during the delay time when the burner is turned off due to 

the temperature during heating operation. (0~20 min)

14: bo

15°F (10°C)

Burner ON differential

Heating temperature setting during heating operation –

Operate in burner ON temperature setting Range: 9 - 27°F (5 - 15°C)

15: OF

110°F (38°C)

Warm Weather Shutdown

This warm weather temperature setting will shut down CH Mode.

Range: 50 - 110°F (10 - 43°C).

16:cH

180°F (82°C)

Setting for Heating Maximum 

Temperature

Range: 9°F less than Minimum Temperature to 180°F

             5°C less than Minimum Temperature to 82°C

17:cL

130°F (54°C)

Setting for Heating Minimum 

Temperature

Range: 86°F to 9 degrees °F less than Maximum Temperature

18:dH

140°F (60°C)

Setting for Hot Water Maximum 

Temperature

Range: 120°F - 140°F (49°C to 60°C)

19:cb

100%

Heating Combustion Rate

Range: 50%~100%

20:db

100%

Hot Water Combustion Rate

Range: 50%~100%

21:PP

40 min

Boiler pump post burner limit 

run time

(Boiler Pump) 1 min - 60 min.  As long as TT is closed, boiler and system pump 

both run, even when boiler hits high limit. (TT is closed).

22:Po

5 min

Pump on Time

(Boiler Pump Repeat ON Time) Range: 1 min ~60 min (While TT is closed)

23:PF

0 min

Pump off Time

(Boiler Pump Repeat Off Time) Range: 0min ~60 min (While TT is closed)

24:SF

150°F (66°C)

Storage off temperature

Range: 140°F - 180°F (60°C to 82°C)

24:SF

105°F (41°C)

DHW Recirculation off temp 

(when DHW/Surface sensor is 

connected)

Range: 95°F - 140°F (35°C to 60°C) The range is automatically changed when 

DHW/Surface sensor is connected.

25:So

18°F (10°C)

Storage on 

Δ

temp

Range: 9°F - 36°F (5°C to 20°C)

25:So

9°F (5°C)

DHW Recirculation on temp 

(when DHW sensor or aquastat 

is connected)

Range: 9°F - 27°F (5°C - 15°C) The range is automatically changed.

26:dt

0 min

Smart DHW Priority Delay time

Range: 0 – 2 minutes. If Smart DHW Priority is ON (see parameter P36), a call for 

domestic hot water will be prioritized by the boiler for delay time value.  The boiler 

will turn heating back on as long as boiler can satisfy both domestic and heating 

demands otherwise, heating will remain off until domestic demand has ended.

27:PE

1 min

Internal Boiler Pump and system 

pump Post-Purge Time,

T/T Satisfied

Allows the user to set the boiler pump and system pump post purge time once 

the appliance CH set point and thermostat are satisfied.   Range: 1-5 minutes

28: 

HA

0-2

High Elevation Mode

High Elevation Mode: 0 - 2, 2 - 5, 5 - 8, 8 - 10  Default: 0 - 2

0 - 2: 0 - 2,000 ft

2 - 5: 2,000 - 5,000 ft

5 - 8: 5,000 - 8,000 ft

8 - 10: 8,000 - 10,000 ft

Installer Parameters

FT WALL MOUNTED AND FLOORSTANDING COMBI MODELS

Содержание FT Combi Series

Страница 1: ...de d marrage rapide compl te le manuel d installation et d utilisation du FT Combi L installation de la combinaison mur ou sol doit d abord tre conforme au manuel d installation et d utilisation de ce...

Страница 2: ...ll for CH DHW Internal Storage The DHW icon will appear on the screen Programming DHW Set Point 1 Press DHW button 2 Turn the Scroll Select dial to adjust to desired set point 3 Press the Scroll Selec...

Страница 3: ...to adjust desired set point 4 Press the Select Scroll dial to save your selection Page 4 The DHW icon will appear on the screen Note The DHW high set point can be adjusted to a maximum of 140 F An Ant...

Страница 4: ...elect Dial CH Button F C Calculated setpoint DHW Button Mode Button Call for CH DHW Internal Storage Page 4 of 12 Outdoor Sensor Outdoor Sensor Wall Mounted Combi Unit Floorstanding Combi Unit Outdoor...

Страница 5: ...To adjust outdoor reset follow these steps Page 5 of 12 Outdoor Reset varies the control set point based on the outdoor temperature The reset function works as shown in Figure CH Outdoor Reset When th...

Страница 6: ...lease the Scroll Select dial to save the setting 11 Turn the Scroll Select dial to 15 OF Warm Weather Shut Down 12 Press and release the Scroll Select dial to enter this program step 13 Turn the Scrol...

Страница 7: ...21 Turn the Scroll Select dial to desired Minimum CH Temperature 22 Press and release the Scroll Select dial to save the setting 23 Press and release the Mode button to power down the display 24 Press...

Страница 8: ...emperature Range 86 F to 9 degrees F less than Maximum Temperature 18 dH 140 F 60 C Setting for Hot Water Maximum Temperature Range 120 F 140 F 49 C to 60 C 19 cb 100 Heating Combustion Rate Range 50...

Страница 9: ...W recirc pump not running for recirc for 15 min Applies when not using DHW R sensor or aquastat pairs with P33 Range 1 60 min To run continuously between rC and rt If flow is detected rC timer resets...

Страница 10: ...n Normal Operation This example is a wall Model 140 with 3 Venting and using Natural Gas in Normal Operation This example is a floor Model 199 with 3 Venting and using Natural Gas in Normal Operation...

Страница 11: ...ack to Min Fire and adjust to bring CO2 up 9 If Max Fire is too high you will need to go back to Min Fire and adjust to bring CO2 down Combustion Setup Gas Inlet Port CO2 Adjustment NOTE FTCW199 Gas V...

Страница 12: ...position Normal Operation 13 Remove all test equipment re install the combustion port test plug 14 Fasten the boiler cover back onto the boiler Page 13 Customer Service and Product Support 800 900 92...

Отзывы: