background image

INSTRUCTION/OPERATING AND TROUBLESHOOTING MANUAL FOR MODEL EC 

Page 2 of 11 

 

This manual contains important safety and operating instructions for the La Marche Power Conversion Equipment. 
 
Before using this equipment, read all instructions and cautionary markings on  (1) unit, (2) battery, and (3) product using the battery. 
 

CAUTION:  To reduce risk of injury and/or damage to the batteries, use only the type of batteries specified on the charger.

 

 

Do not

 expose equipment to rain or snow. 

Do not 

operate equipment if it has received a sharp blow, been dropped, or otherwise damaged in any way; take it to a qualified serviceman. 

Do not

  disassemble  this  unit;  take  it  to  a  qualified  serviceman  when  service  or  repair  is  required.    Incorrect  re-assembly  may  result  in  a  risk  of 

electric shock or fire. 
 
To  reduce  risk  of  electric  shock,  disconnect  this  unit  from  the  AC  supply,  or  batteries  and  loads  before  attempting  any  maintenance  or  cleaning.  
Turning off controls will not reduce this risk. 
 
WARNING  –  THERE  IS  A  RISK  OF  EXPLOSIVE  GASSES  AND  WORKING  IN  THE  VICINITY  OF  A  BATTERY  IS  DANGEROUS.    SOME  BATTERIES 
GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION.  FOR THIS REASON, IT IS OF UTMOST IMPORTANCE THAT EACH TIME 
BEFORE USING THIS UNIT, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY. 
 
To reduce risk of battery explosion, follow these instructions and those published by the battery manufacturer and manufacturer of any equipment 
you intend to use in the vicinity of the battery.  
 
Review cautionary marking on all products. 
 

PERSONAL PRECAUTIONS:

 

1.

 

Someone should be within range of your voice or close enough to come to your aid when you work near a battery. 

2.

 

Have plenty of fresh water and soap nearby in case the battery electrolyte contacts skin, clothing, or eyes. 

3.

 

Wear complete eye protection and clothing protection.  Avoid touching eyes while working near a battery. 

4.

 

If the battery electrolyte contacts skin or clothing, wash immediately with soap and water.  If the electrolyte enters the eye, immediately 

flood the eye with running cold water for at least ten (10) minutes and get medical attention immediately. 

5.

 

Never smoke or allow a spark or flame in vicinity of a battery. 

6.

 

Be extra cautious, DO NOT drop metal onto a battery.  It might spark or short-circuit the battery or cause an explosion. 

7.

 

Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery.   A battery can produce  a 

short-circuit current high enough to weld these items causing severe burns. 

8.

 

NEVER charge a frozen battery. 

PREPARING TO CHARGE 

1.

 

If  it  is  necessary  to  remove  the  battery  connections,  always  remove  grounded  terminal  from  the  battery  first.    Make  sure  all  loads  are 
disconnected and unit is off, so as not to cause an arc. 

2.

 

Be sure the area around the battery is well ventilated while the battery is being charged. 

3.

 

When cleaning battery terminals, be careful to keep corrosion from coming in contact with eyes. 

4.

 

Study all the battery manufacturer’s specific precautions such as removing or not removing cell caps while charging, recommended rates of 
charge, and maintenance procedures. 

 

UNIT LOCATION 

 

Never place this unit directly above the standard flooded battery.  Gases from the battery will corrode and damage equipment.  A 

sealed maintenance free or valve regulated lead acid (VRLA) may be placed below this equipment. 

 

Never allow the battery electrolyte to drip on this unit when reading the specific gravity or filling the battery. 

 

Do not operate this unit in a closed-in area or restrict ventilation in any way. 

 

Do not set any battery on top of this unit. 

 

DC CONNECTION PRECAUTIONS 

Connect and disconnect DC output cables only after setting all of this unit's switches to off position and removing AC input supply. 

 

GROUNDING INSTRUCTIONS 

This battery charger should be connected to a grounded, metal, permanent wiring system; or an equipment grounding conductor should be run with 

circuit conductors and connected to equipment-grounding terminal or lead on battery charger.  Connections to battery should comply with all local 

codes and ordinances. 

 

CAUTION:  DO NOT PULL ON OUTPUT CABLES WHEN DISCONNECTING CHARGER FROM BATTERY. 

 

IMPORTANT SAFETY INSTRUCTIONS 

FOR THE 

LA MARCHE POWER CONVERSION EQUIPMENT 

Содержание EC

Страница 1: ...FOR MODEL EC Page 1 of 11 EC Engine Start Battery Charger INSTRUCTION MANUAL ECN DATE CPN106604 18985 4 11 16816 11 05 106 BRADROCK DRIVE DES PLAINES IL 60018 847 299 1188 FAX 847 299 3061 ISSUE DATE...

Страница 2: ...the eye with running cold water for at least ten 10 minutes and get medical attention immediately 5 Never smoke or allow a spark or flame in vicinity of a battery 6 Be extra cautious DO NOT drop meta...

Страница 3: ...Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Until the equipmen...

Страница 4: ...r cell equalize nickel cadmium cell The charger is factory tested and preset so that no field adjustments are necessary In normal operation the EC Charger maintains a constant battery voltage If the b...

Страница 5: ...rating 2 Check unit specifications with customer order 3 Check input connections input voltage and line breaker size 4 Check for shipping damage loose connections broken wires etc 5 Certain failures c...

Страница 6: ...operates but will not charge battery 1 Defective capacitor 2 Open cell in battery To check capacitor measure resistance with one capacitor lead disconnected it should read high resistance Check batter...

Страница 7: ...MENT REQUIREMENT GROUNDING FUSE CUSTOMER CONDUCTOR SIZE CONNECTION MINIMUM 1 14 14 3 14 14 4 14 14 5 14 14 6 14 14 10 14 14 15 12 12 20 12 12 25 10 12 30 10 10 35 8 10 40 8 10 45 8 10 50 8 10 60 6 10...

Страница 8: ...2000 2000000 Denotes all sizes larger than 0000 are expressed in MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ultimate drain in amperes LF Conductor loop feet MAX AMP Maxi...

Страница 9: ...4 Check front panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH T...

Страница 10: ...by purchaser 2 If the purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s...

Страница 11: ...sting performed by factory personnel Should it be necessary to return a piece of equipment or parts to the factory the customer or sales representative must obtain authorization from the factory If up...

Отзывы: