15
Stopping the AUPS Procedure
When shutting down the AUPS, switch off the ON/OFF switch (inverter section) first, and then switch of the AC
breakers, followed by the DC breakers.
3.2
Factory Settings
All AUPS systems are default set based on 12, 24, or 60 lead acid cells for 24VDC, 48VDC, or 125VDC
respectively. The defaults are as follows:
Parameter
Lead Acid*
VRLA
Nickel Cadmium
Delay (sec.)
Float Voltage
2.17 V/C
2.25 V/C
1.40 V/C
Equalize Voltage
2.33 V/C
2.27 V/C
1.55 V/C
Low DC Voltage
1.98 V/C
1.20 V/C
5
Low DC Voltage Reset
5% of the Low DC Voltage threshold
Low DC Current
1% of shunt size
5
Low DC Current Reset
Dependent on output current rating
Overload
Dependent on output current rating
5
Overload Reset
5% of the Overload threshold
Current Limit
110% of nominal output current
5
High DC Voltage
2.45 V/C
1.61 V/C
5
High DC Voltage Reset
5% of the High DC Voltage threshold
High Voltage Shutdown
2.50 V/C
1.65 V/C
20
Battery End of Discharge
1.75 V/C
1.10 V/C
5
End of Discharge Reset
5% of the End of Discharge threshold
Equalize Timer Mode
Automatic Equalize Off (Mode P0)
Equalize Time
8 Hours
Table 8
–
Rectifier Suggested Values per Battery Type
NOTE:
V/C
–
Volts per Cell, LA
–
Lead Acid, VRLA
–
Valve Regulated Lead Acid, NC
–
Nickel Cadmium