Operation
2.1
Initial Startup
Before applying AC power, be sure that the DC Breaker is turned off and output DIP switches are set correctly
see (Section 2.2). Once all connections have been made and verified, the AC power may be turned on. The
charger will automatically power up. There is a five second delay during startup while the charger automatically
detects the AC input voltage. Once the unit output ramps up, verify correct output voltage and then turn on the
DC Breaker.
2.2
Changing Settings
Below the Output Voltage display is a set of twelve DIP switches. These switches are used to change settings
of the charger. The function of each switch is shown in the image and table below.
Figure 6 - Configuration Switches (12V Charger)
Switch Battery Cells (12V)
Voltage Range (12V)
Battery Cells (24V)
Voltage Range (24V)
SW1
Disable Low Current Alarm
SW2
12NC
16.68 – 17.88
24NC
33.3 – 35.7
SW3
11NC
15.29 – 16.39
22NC
30.5 – 32.7
SW4
10NC
13.90 – 14.90
20NC
27.8 – 29.8
SW5
9NC
12.51 – 13.41
18NC
25.0 – 26.8
SW6
8NC
11.12 – 11.92
16NC
22.2 – 23.8
SW7
8LA
17.20 – 18.80
16LA
34.4 – 37.6
SW8
7LA
15.50 – 16.45
14LA
31.0 – 32.9
SW9
6LA
12.90 – 14.10
12LA
24.6 – 28.2
SW10
5LA
10.75 – 11.75
10LA
21.5 – 23.5
SW11
Not Used
SW12
Disable Internal Temperature Compensation
Table 1 - DIP Switch Settings