background image

15 

 

 

4.

 

Find the firmware .bin file provided and upload it into the microSD card.  
 

5.

 

Safely remove the microSD card from the computer and insert it on the A39DS charger’s microSD card 

slot. 

 

6.

 

Update the firmware by entering the Settings menu: 

Menu 

à

 Advanced 

à

 Firmware Menu 

à

 Update Firmware 

 

7.

 

Enter  the  password  provided  (must  contact  La  Marche  Service  Department)  and  select  YES  when 

prompted to update the firmware. The charger will start to program itself. Do not interrupt the power or 

the board while it is programming! 

LCD Settings 

The “LCD Settings” option allows the user to control the LCD backlight. By default, the LCD backlight 

automatically turns off after two minutes. The user may also set it to be always on. 

 

à

 

 

 

 

 

Serial Number 

The “Serial Number” setting allows the user to change the serial number associated with the S2A-368S board. 

This serial number is the serial number of the A39DS charger and is set at the factory for new chargers. If a 

user receives a replacement S2A-368S board, the serial number will have to be set via calibration. 

In order to change the serial number used by the software, select “Serial Number” from the Settings menu and 
press the ENTER button. Each digit of the serial number is adjusted individually. Press the LEFT and RIGHT 

buttons to select digits. If the leftmost digit is selected, pressing left will exit the serial number setting and 

discard changes. Press the UP and DOWN buttons to increase and decrease the selected digit. 

 

à

 

 

 

 

 

Set Clock 

The “Set Clock” setting allows the user to program the real-time clock used by the software. This clock is used 

in the data logging to timestamp events. In addition, the clock can be reset which returns the clock to the date 

setting of software revision.   

 
Set to Default 

The “Set to Default” option resets all user-adjustable settings to the factory defaults. It is important to note that 

the factory defaults are not necessarily the correct settings for the specific DC system. Before the charger is 

shipped, adjustments are made at the factory using the same calibration procedure. If the charger is reset to 
default, these factory changes may be reset.  

 

 

>LCD Settings 

 

LCD Backlight 
AUTO OFF 2 Min 

>Serial Number 

 

Enter Serial # 
123456-01 

Содержание A39DS

Страница 1: ...on and Operation Manual This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com 106 Bradrock Dr Des Plaines 60018 1967 Tel 847 299 1188 F...

Страница 2: ...me in contact with any internal components Do not operate this charger outside the input and output ratings listed on the charger nameplate Do not use this charger for any purpose not described in the...

Страница 3: ...ger sent back for evaluation and repair CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for any physical damages rep...

Страница 4: ...1 Wall Mounting the A39DS 6 Enclosure Only 5 2 1 2 Floor Mounting the A39DS All Enclosures 6 2 2 AC Input Connections 6 2 3 DC Output Connections 8 2 4 Alarms 9 2 4 1 Understanding the Alarms Statuse...

Страница 5: ...16 4 3 Reset Alarms 16 4 4 Last 10 Events 16 4 5 Manual Start Zero Volt Battery Start 16 5 Service 17 5 1 Performing Routine Maintenance 17 5 2 Troubleshooting Procedure 18 5 3 Troubleshooting Chart...

Страница 6: ...ge when the battery is connected The current limit automatically defaults to 10 of the rated output and the charger timer defaults to 8 hours on start up The A39DS will Auto start upon connection of t...

Страница 7: ...s To enter a submenu use the ENTER button The BACK button returns to the previous menu When making a selection the ENTER button will store the value and step back The BACK button will not save the cha...

Страница 8: ...nd weight of the A39DS charger Refer to the tables below Output Voltage Frequency Ampere Rating 20 ADC 30 ADC 40 ADC 60 ADC 30 VDC 60 Hz 6 Case 175 lbs 79 4 kg 60 VDC 6 Case 130 lbs 59 kg 6 Case 190 l...

Страница 9: ...convection cooling so a clearance of at least 6in 152mm of free air must be maintained on the top bottom and both sides for cooling air Maintain 36in 914mm or more of clearance at the front of the ch...

Страница 10: ...times Secure the charger on bolts add appropriate mounting hardware and tighten securely Refer to the figures below for mounting dimensions and specifications NOTE All below dimensions are in inches...

Страница 11: ...the floor Place the charger on the bolts add appropriate mounting hardware onto the floor mounting anchor bolts and tighten securely Refer to Figure 2 for hardware specifications and floor mounting di...

Страница 12: ...lti tap charger is set for 120VAC input configuration feeder breaker should be double the size of the AC protection 120VAC configured multi tap chargers use both breaker poles in parallel Breaker Size...

Страница 13: ...ents Calculating Current Carrying Capacity of Wire Table 5 Wire Size Area Table NOTE These are recommended sizes per La Marche Standards The National Electrical Code NEC and Local Wiring Codes must be...

Страница 14: ...V The 60V model has a maximum output voltage setting of 60V The 90V model has a maximum output voltage setting of 90V The 150V model has a maximum output voltage setting of 150V NOTE All alarms automa...

Страница 15: ...tput 10 above the reading The current limit will be set to 10 as the default The charger will slowly ramp up to the target voltage this can take up to 10 seconds Charging LED will be lit 3 1 3 Setting...

Страница 16: ...nal features Figure 3 A39DS Front Panel The parameters viewable on the idle display are as follows Standard A39DS Display Sequence System DC Outputs Elapsed Time Logging Status Timer Setting Charger C...

Страница 17: ...the Settings Menu If YES is selected the display will read Saving Settings the menu will be exited and settings saved If NO is selected the user is prompted to Exit without Saving From this screen if...

Страница 18: ...tting or BACK to cancel Elapsed Time The Elapsed Time defaults to 8 hours on start up The charging time increments by 1 hour Select Elapsed Time and press then ENTER button Press the UP and or DOWN bu...

Страница 19: ...dvanced Security Password Enable Select YES and enter 0000 Navigate to Set Password Set password to desired four digit pin Make sure to save this new number as it will be necessary to access the menu...

Страница 20: ...umber will have to be set via calibration In order to change the serial number used by the software select Serial Number from the Settings menu and press the ENTER button Each digit of the serial numb...

Страница 21: ...ttery Start The Manual Start menu allows the user to start the charger when the battery voltage is lower than the minimum detection voltage This feature should only be utilized 1 when the battery is d...

Страница 22: ...l number and serial number Yearly 1 Confirm air vents are open Remove dust and debris from interior of unit 2 Verify all connections are tight 3 Perform a visual inspection on all internal components...

Страница 23: ...he field La Marche Service Technicians are available to help with troubleshooting or with scheduling charger service When calling for a service inquiry or for troubleshooting assistance be sure to hav...

Страница 24: ...Running Hot Inadequate Ventilation Ambient is Too Hot Battery Temperature Too High Insufficient Cool Down Between Charges Battery Power Demand Too Great Battery Needs to be Equalized Erratic Operatio...

Страница 25: ...P368SBLxx xxxxxx Update Firmware Enter Password 0000 Update Firmware Yes No LCD Settings LCD Backlight Always ON AUTO OFF 2 mins Serial Number xxxxxx xx Set Clock Set Clock xx xx xxxx xx xx xx Reset C...

Страница 26: ...ed and recharge it without clearing any protective devices ENVIROMENTAL Audible Noise Less than 65dBA at any point 5 feet from any vertical surface Operating Temperature 32 to 122 F 0 to 50 C Storage...

Страница 27: ...90V BD1 60 90 8 90 240 208 VAC 1 PH 6 300 A39DS 100 90V BD3 100 90 8 90 240 208 VAC 3 PH 8A 350 A39DS 150 90V BD3 150 90 8 90 240 208 VAC 3 PH 8A 565 A39DS 200 90V BD3 200 90 8 90 240 208 VAC 3 PH 72...

Страница 28: ...23 Appendix D Document Control and Revision History Part Number 148973 Instruction Number P25 LA39DS 1 Issue ECN 23419 10 23...