WARNING

Fire and Explosion Hazard

n

Do not use open flame (matches, torches, candles,
etc.) in checking for gas leaks.

n

Use only approved leak detectors.

n

Failure to follow this warning can lead to fires or
explosions.

n

Fires or explosions can lead to property damage,
personal injury or loss of life.

Direct fired heaters discharge combustion by-products with
the heated air in to the area being heated.  These include
CO, CO

2

, NO, NO

2

, and Ethylene.  These gases can result in

harm to the worker or the plants.

This greenhouse heater has been specifically developed for
very low levels of these combustion by-products.  However,
it is necessary to have an exchange of air within the
greenhouse to avoid accumulation of these gases to a
harmful level over an extended period of operating time.

Greenhouses have a natural air leakage factor.  This natural
leakage is influenced by the design and physical condition
of the greenhouse as well as wind conditions and other
factors.  This natural leakage factor can not be relied upon
as being sufficient to provide the necessary air exchange
within the greenhouse.  Proper installation of this heater
must include provision for adequate air exchange as
follows:

I

Indoor Mounted Heater:

n

An exhaust fan capable of providing at least 

55

0

 

cfm of discharge air.

n

An inlet shuttered louver of at least 120 sq. in.

 

area.

n

The inlet shutters must be electromechanically

 

operated and electrically interlocked with the heater

 

such that the heater can not operate if the inlet

 

shutters do not open when heating is required.

n

Refer to Indoor Ventilation Requirements in this

 

manual. 

Outdoor Mounted Heater:

n

An exhaust shuttered louver of at least 64 sq. in.
area.

1.

Read all safety precautions and follow L.B. White
recommendations when installing this heater.  If
during the installation or relocating of heater, you
suspect that a part is damaged or defective, call a
qualified service agency for repair or replacement.

2.

Make sure the heater is properly positioned before use
and is hung level.  Observe and obey all minimum safe
distances of the heater to the nearest combustible
materials.  Minimum safe distances are given on the
heater nameplate and on page 4 of this manual.

3.

The heater may be used either indoors or outdoors.
For heaters intended for outdoor installation, the
heater is to be installed at least 18 inches above the
ground or to a height that would prevent snow
blockage of heater’s air inlet.  Refer to instructions
provided in the optional L.B. White outdoor mounting
and ducting kit, part number 23579.

4. The heater must have the proper gas regulator installed

for the application.  A regulator must be connected to
the gas supply so that gas pressure at the inlet to the
gas valve is regulated within the range specified on the
dataplate at all times.  Contact your gas supplier, or the
L.B. White Co., Inc. if you have any questions.

5.

The heater’s gas regulator (with pressure relief valve)
s h o u l d   b e   i n s t a l l e d   o u t s i d e   o f   b u i l d i n g .     A ny
regulators inside the buildings must be properly
vented to the outside.  Local, state and national
codes always apply to regulator installation.  Natural
gas regulators with vent limiting device may be
mounted indoors without venting to outdoors.

6.

All gas pressure regulators must be installed in strict
accordance with the manufacturer’s safety instructions.
These instructions accompany each regulator.

7.

Insure that all accessories that ship within the heater
have been removed from inside of heater and
installed.  This per tains to air diver ters, hose,
regulators, etc.

8.

Make certain that a sediment trap is installed at the
gas valve inlet to prevent foreign materials (pipe
compound, pipe chips and scale) from entering the
gas valve.  Debris blown into the gas valve may cause
that valve to malfunction resulting in a serious gas
leak that could result in a possible fire or explosion
causing loss of products, building or even life.  A
properly installed sediment trap will keep foreign
materials from entering the gas valve and protect the
safe functioning of that important safety component.

9.

Any heater connected to a piping system must have
an accessible, approved manual shut of f valve
installed within six feet (6 ft.) of the heater it serves.

10.

Check all connections for gas leaks using approved
gas leak detectors.  Gas leak testing is performed as
follows:

-- Check all pipe connections, hose connections,

fittings and adapters upstream of the gas control
with approved gas leak detectors.

-- In the event a gas leak is detected, check the

components involved for cleanliness and proper
application of pipe compound before fur ther
tightening.

-- Fur thermore tighten the gas connections as

necessary to stop the leak.

-- After all connections are checked and any leaks

are stopped, turn on the main burner.

-- Stand clear while the main burner ignites to

prevent injury caused from hidden leaks that could
cause flashback.

7

Installation Instructions

GENERAL

Содержание Therma Grow 120NG

Страница 1: ...s Manual and Instructions Therma Grow Greenhouse Heaters View this manual online at www lbwhite com 150 27595 REV B ATTENTION ALL USERS This heater has been tested and evaluated by C S A Internationa...

Страница 2: ......

Страница 3: ...s heater can result in Death Serious bodily injury or burns Property damage or loss from fire or explosion Asphyxiation due to lack of adequate air supply or carbon monoxide poisoning Electrical shock...

Страница 4: ...stributor dealer or the L B White Company Contact your local L B White distributor or the L B White Co Inc for assistance or if you have any questions about the use of the equipment or its application...

Страница 5: ...d electrically interlocked with the heater to prevent heater operation if air inlet and exhaust outlet do not open when heating is required Model Indoor Mounting Air Exchange Requirements 1 Burner Man...

Страница 6: ...lding and area before you return Properly trained service people must repair the leak check for further leakages and then relight the appliance for you WARNING n Do not use this heater for heating hum...

Страница 7: ...ipped with a manual reset high limit switch and an air proving switch Never operate this heater with any safety device that has been bypassed Do not operate this heater unless all of these features ar...

Страница 8: ...ground or to a height that would prevent snow blockage of heater s air inlet Refer to instructions provided in the optional L B White outdoor mounting and ducting kit part number 23579 4 The heater mu...

Страница 9: ...appropriate alarms 16 Take time to understand how to operate and maintain the heater by using this Owner s Manual Make sure you know how to shut off the gas supply to the building and also to the indi...

Страница 10: ...MI HD220 HD220 5B ENG BYNAME JIMI HD220 HD220 5B ENG BYNAME JIMI HD220 HD220 5B ENG BYNAME JIMI HD220 HD220 5B ENG BYNAME JIMI HD220 HD220 5B ENG BYNAME JIMI HD220 HD220 5B ENG BYNAME JIMI HD220 HD220...

Страница 11: ...consideration must be given to making sure the heater is located away from the people entering or exiting the greenhouse so they cannot accidentally knock the heater or tamper with the heater and its...

Страница 12: ...NTROL VALVE INLET REGULATORVENT GAS FLOW 1 Always use approved pipe thread compound suitable for use with L P gas or natural gas on the threaded connections 2 Assemble the components together accordin...

Страница 13: ...roximately 17 seconds After igniter warm up time has been achieved the motor will start again and shortly thereafter ignition will occur NOTE It is normal for air to be trapped in the gas hose on new...

Страница 14: ...Periodic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property damage 1 The area surrounding the heater shall be kept clear and free from combustible...

Страница 15: ...ent jumpered Replace the part immediately An alternate method for checking the components is to perform a continuity check 5 Do not jumper the air proving switch If jumpered the ignition control will...

Страница 16: ...m the switch which indicates the contacts of the switch have opened 4 Allow the switch cool down for about a minute before firmly pressing the red reset button on the switch 5 Check for electrical con...

Страница 17: ...further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that specified on the dataplate then the regulator controlling gas pressure to the heater req...

Страница 18: ...ocated at the end of the igniter leads See Fig 16 2 Loosen the screw securing the igniter shield and the igniter to the mounting bracket Remove the igniter and shield 3 Ensure the igniter is located s...

Страница 19: ...ition control Red light on ignition control is illuminated Ignition control sends flame sense current to flame sensor Ignition control module performs self safety check Internal components are tested...

Страница 20: ...ace thermostat Is heater connected to power supply No No No Yes Ensure heater is connected to power supply Check breakers Is transformer receiving proper voltage Check wiring for continuity between tr...

Страница 21: ...r proving switch been jumpered Yes No Remove jumper from switch Rapid Flash Reverse polarity Have electrician check neutral and hot wire connections that outlet heater is connected to Long Flash Two s...

Страница 22: ...sary No Is fan wheel plugged with dirt Is there an obstruction in blower outlet preventing air proving switch closure No Are 115 volts sent from ignition control terminal IND to motor relay No If impr...

Страница 23: ...e and component Repair or replace as necessary or replace ignition control Provide proper pressure to heater and check with a gauge Check for voltage to switch Check wiring and repair if defective If...

Страница 24: ...l Flame sense is low and that flame failure or improper operation can occur at any time See flame sensor related problems in three time flash pattern Four Times If HSI board does not reset then replac...

Страница 25: ...24 Electrical Connection and Ladder Diagram 115 Volt Supply 120 VOLT...

Страница 26: ...25 230 Volt Supply 120 VOLT...

Страница 27: ...ation Hot Surface Igniter Ignition device used on automatic ignition control systems Ignites gas by surface temperature rather than spark or flame Ignition Control Module Electronic printed circuit bo...

Страница 28: ...27 28 30 37 38 39 21 20 19 16 17 6 5 7 8 9 10 11 12 4 3 2 1 14 31 32 33 34 35 26 27 29 36 22 25 13 18 15 24 23 Parts Identification PARTS SCHEMATIC...

Страница 29: ...r Igniter Shield 572512 18 Bracket w Screws 570089 19 Flame Sensor 520139 20 High Limit Switch LP Gas 572501 Natural Gas 505566 21 Heat Chamber LP Gas 572499 Natural Gas 572500 22 Control Box w Cover...

Страница 30: ...of the equipment and in any event L B White s liability in connection with the equipment including for claims based on negligence or strict liability is limited to the purchase price Some states do no...

Отзывы: