6−3 Resistance Measurement
WARNING
●
Before attempting to make measurement, make sure that the
circuit under test is not live. The instrument is protected against a
voltage up to 600V.
●
Do not make measurement with the battery compartment cover
removed.
●
Keep your fingers and hands behind the barrier during measurement.
6−3−1 Resistance Measurement (Normal Mode)
①
Set the function selector switch to the "
Ω
/
" position.
②
Slide the terminal cover to the left. Plug the red test lead into the V/
Ω
terminal and the black test lead into the COM terminal.
③
Short the tip of the test leads and check whether the display reads "0".
④
Connect the tip of the test leads to the circuit under test. Take the
reading on the display.
NOTE
●
When shorting the tip of the test leads, the display may read a very
small resistance instead of "0." This is the resistance of the test
leads, not a fault.
●
If one of the test leads is open, the display reads "OL".