INSTRUCTION MANUAL
DIGITAL CLAMP METER
KEW2007R
1. Safety Warnings
This instrument has been designed, manufactured and
tested according to IEC 61010: Safety requirements for
Electronic measuring apparatus, and delivered in the best
condition after passed the inspection. This instruction
manual contains warnings and safety rules which must be
observed by the user to ensure safe operation of the
instrument and retain it in safe condition. Therefore, read
through these operating instructions before using the
instrument.
WARNING
● Read through and understand the instructions contained
in this manual before using the instrument.
● Keep the manual at hand to enable quick reference
whenever necessary.
● The instrument is to be used only in its intended
applications.
● Understand and follow all the safety instructions
contained in the manual.
● It is essential that the above instructions are adhered to.
Failure to follow the above instructions may impair the
protection provided by the instrument and test leads, and
may cause injury, instrument damage and/or damage to
equipment under test.
The symbol
indicated on the instrument means that the
user must refer to the related parts in the manual for safe
operation of the instrument. It is essential to read the
instructions wherever the symbol
appears in the manual.
DANGER is reserved for conditions and actions that
are likely to cause serious or fatal injury.
WARNING is reserved for conditions and actions that
can cause serious or fatal injury.
CAUTION is reserved for conditions and actions that
can cause injury or instrument damage.
● Marks listed below are used on this instrument.
User must refer to the manual.
Instrument with double or reinforced insulation
Indicates that this instrument can clamp on
bare conductors when measuring a voltage
corresponding to the applicable measurement
category, which is marked next to this symbol.
AC
DC
Ground (Earth)
This instrument is subject to WEEE Directive
(2002/96/EC). Please contact our dealer near
you at disposal.
Measurement Category
O
Circuits which are not directly connected to the mains
power supply.
CAT II
Primary electrical circuits of equipment connected
to an AC electrical outlet by a power cord.
CAT III
Primary electrical circuits of the equipment
connected directly to the distribution panel, and feeders
from the distribution panel to outlets.
CAT IV
The circuit from the service drop to the service
entrance, and to the power meter and primary over current
protection device(distribution panel).
This instrument is designed for CAT IV 300V / CAT III
600V. Test leads M-7066A with the supplied cap are
designed for CAT IV 600V / CAT III 1000V and without
the caps are for CAT II 1000V.
DANGER
● Never make measurements under the circumstances
exceed the designed measurement category and the
rated voltage of the instrument and the test leads.
● Do not attempt to make measurement in the presence of
flammable gasses. Otherwise, the use of the instrument
may cause sparking, which can lead to an explosion.
● Never attempt to use the instrument if its surface or your
hand is wet.
● Do not exceed the maximum allowable input of any
measuring range.
● Never open the Battery cover during a measurement.
● To avoid electrical shock by touching the equipment
under test or its surroundings, be sure to wear insulated
protective gear.
● Never measure current while the test leads are inserted
into the input terminals.
● Test leads to be used for voltage measurements shall be
rated as appropriate for Measurement Category III or IV
according to IEC 61010-031 and shall have a voltage
rating of 600V or higher.
● Barriers on the instrument body and the test leads
provide protection to keep your fingers and hands from
touching an object under test. Keep your fingers and
hands behind the barriers during measurement.
WARNING
● Never attempt to make measurement if any abnormal
conditions, such as broken case and exposed metal
parts are found on the instrument or test leads.
● Verify proper operation on a known source before use or
take action as a result of the indication of the instrument.
●
Firmly attach the caps to the test leads when
performing measurements in CAT III or higher test
environments. When KEW2007R and the test leads
are combined and used together, whichever is lower
category & voltage to earth either of them belong to
is applied.
● Do not rotate the Function Switch if the instrument and
the equipment under test are connected.
● Do not install substitute parts or make any modification to
the instrument. For repair or re-calibration, return the
instrument to your local KYORITSU distributor
CAUTION
● Use of this instrument is limited to domestic, commercial
and light industry applications. Strong electromagnetic
interference or strong magnetic fields, generated by
large currents, may cause malfunction of the instrument.
● Connect the test leads to the terminals firmly.
● This instrument isn’t water proofed. Keep away from
water.
● Do not pull or twist the test leads to prevent the risk of
damage.
● Power off the instrument after use. Remove batteries if
the instrument is to be stored and will not be in use for a
long period.
● Do not expose the instrument to the direct sunlight, high
temperature and humidity or dewfall.
● Use a cloth dipped in water or neutral detergent for
cleaning the instrument. Do not use abrasives or solvents.
NOTE
● The LCD shows some digits at the ACV and the DCV
ranges even while the test leads are open. In addition,
the LCD shows some digits instead of 0 when short-
circuiting the test leads. However, these phenomena
don’t affect measurement results.
2. Specification
Temperature: 23 ± 5°C, Humidity: 45 - 75%
ACA
(Auto-range)
Range
Display Range
Accuracy (sine wave)*1
600A
0.0, 0.4-629.9A
±1.5 %rdg±4dgt (45-65Hz)
±2.0 %rdg±4dgt (40-400Hz)
1000A
570-1049A
*1 : when the measured conductor is in the center of clamp jaw
Guaranteed accuracy : 0.8A -1000A,less than 1500A Peak
Input protective current : AC1200A
ACV
Range
Display Range
Accuracy (sine wave)
600V
0.0, 0.6-629.9V
±1.2 %rdg±3dgt (45-65Hz)
±1.5 %rdg±4dgt (40-400Hz)
Guaranteed accuracy : 1.0V - 600.0V,less than 900V Peak
Input protective voltage : AC/DC720V 10 sec
DCV
Range
Display Range
Accuracy
600V
0.0-±629.9V
±1.2%rdg±3dgt
Guaranteed accuracy : 0.0V - ± 600.0V
Input protective voltage : AC/DC720V 10 sec
ACV/DCV input impedance : approx. 10MΩ
Resistance / Continuity
(Auto-range)
Range
Display Range
Accuracy
600Ω
0.0-629.9 Ω
±1.3%rdg±5dgt
6kΩ
0.570-6.299 kΩ
±2.0%rdg±3dgt
Cont.
0.0-629.9 Ω
Bz threshold value <90Ω
Guaranteed accuracy : 0.0Ω - 6.000kΩ
Open-loop voltage : 3V or less
Input protective voltage : AC/DC600V 10 sec
●Measuring method :
⊿
Σ
modulation
●Over-range indication : OL
●Measurement cycle : 2.5 times per second
●Crest factor : less than 3 (45-65Hz)
Add ±0.5%rdg±5dgt to above specified accuracies.
(Applicable functions : ACA, ACV)
●Applicable Standards :
IEC 61010-1/ 61010-2-032/ 61010-2-033 (instrument)
Pollution degree 2, Indoor use, Altitude up to 2000m
CAT III 600V / CAT IV 300V
IEC 61010-031(Test leads Model 7066A)
w/ caps
CAT IV 600V / CAT III 1000V
w/o caps
CAT II 1000V
IEC61326 (EMC), EN50581 (RoHS)
●Withstand voltage : AC5160Vrms 5sec
between current sensor and enclosure or
circuit and enclosure
●IP rating : IP40 (IEC60529)
●Insulation resistance :
>100MΩ /1000V between enclosure and electrical circuit
Function
Switch
Current Sensor
Hold Key
LCD
V/Ω
Terminal
COM
Terminal
Trigger
Cap
Barrier of Test Leads
Barrier
Wrist Strap