![Kyoritsu Electrical Instruments Works 5000 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/kyoritsu-electrical-instruments-works/5000/5000_instruction-manual_2017171014.webp)
― 12 ―
6-1 Continuous recording mode: Record at 1min. interval
Step1 : Power on
(1) Press "MENU/ENTER" button for 1sec. or more and power on the
instrument.
(2) Release the button when all indications are displayed on the LCD.
(3) When instrument is powered on, it becomes measurement mode.
Step2 : Check and change of set value
(4) Press "MENU/ENTER" button and make the instrument to menu
mode.
(5) Check Setting1:"SEt.1" is displayed on the LCD, and press
"MENU/ENTER" button.
(6) Present recording mode is displayed on the LCD. Confirm "LOG"
is displayed on the LCD, and press "RANGE/▼"button.
(When "dtc", "̲ ̲̄" and "CAP" is displayed on the LCD, change
the recording mode according to the procedure described in
clause 9-2.Change of set value.
Recording mode can be selected from:
LOG : Continuous recording mode
dtc : Event recording mode
̲ ̲̄ : Max.value recording mode
CAP : Capture recording mode
(7) Present recording interval is displayed on the LCD. Check the
interval of "1'00''"(1min.) is selected, and press "RANGE/▼
"button.
In case of change, follow the procedure described in clause
9-2.Change of set value.
Recording interval can be selected from:
1,2,5,10,15,20,30sec
1,2,5,10,15,20,30,60min.