KIEN1005G User’s Manual 201106
13
There is a grounding screw on the top panel of the KIEN1005G, which is for chassis
grounding. One end of the chassis grounding cable is connected with the grounding screw
and the other end of the cable is reliably earthed. (The cross section area of chassis
grounding cable should be more than 2.5mm
2
. The grounding resistance requirement: <5
Ω
)
The grounding part in the 5.08mm power terminal block is called surge grounding.
It is required to connect the chassis grounding part with the surge grounding part by an
18#AWG yellow‐green line as seen below
z
18#AWG
yellow
green
line
(Unit:
mm)