Participant Check Vitocontrol-S, Cascade Control
Participant Check
The participant check is used to
confirm communication between
the boiler controls and the
Vitocontrol-S, system control.
Requirements:
Vitocontrol-S, must be coded as
the error manager (default).
Refer to the Vitocontrol-S manual
address 79:01. The LON
participant number must be
assigned in each of the
Versatronik 502 gateway units.
Refer to the rotary dial setting
and ensure there are no
duplicates.
1. Press the OK and Menu
buttons simultaneously for
approximately 2 seconds. This
will allow the Service screen
to appear.
2. With the arrow down button,
select the Service Functions
menu option.
3. Select Subscriber Check if
not already highlighted and
press OK.
4. With the arrow up or down
buttons, select a subscriber
and press OK. The screen with
show the check is active and
will report back if it is okay or
not.
5. If the check was successful,
select a different user by
using the arrow up or down
buttons. Once selected press
OK and repeat the same
procedure as outlined in point
4.
6.
To exit the subscriber check,
press the return button
.
Rotary Switch Position
Participant Value
0 55
1 56
2 57
3 58
4 59
5 60
6 61
7 62
Service
Diagnosis
Actuator
Coding Level 1
Fault History
Service Functions
Terminate Service?
Service Functions
Participant Check
Service PIN
Participant Check
Subscriber 1
Subscriber 3
Subscriber 4
Delete List?
OK