Operation - Troubleshooting Chart
Issue Description
Actions
Fan will not run
1. Check supply voltage
2. Check disconnect (s)
3. Verify control potentiometer setting
4. Verify wiring
5. Verify 0-10 VDC signal and polarity at fan
motor
6. Check fan motor
MUC will not run
1. Check supply voltage between the
24V
terminal and the
COM
terminal
2. Verify the
ENABLE
input has 24VDC
3. Check
Back Up
batteries
Red LED On (Fail Mode)
1. Check
PROVER
circuit
2. Check
MSTAT
circuit
3. Check
RPM
feedback circuit
4. Check fan operation
Green LED Flashing
1. Replace batteries
LED Chart
Green
Red
Indication
OFF
OFF
Not running
ON
OFF
Running normally
FLASHING
OFF
Running - Battery voltage level low
OFF
ON
Fail mode active - alarm condition present
OFF
FLASHING
Fail mode active - Audio muted
ON
ON
Back Up mode active - power loss