background image

 

___________________________________________________________________________________________ 

4

 

EG3002 

SECTION 5 : WIRING CONNECTIONS 

DC Power

+

_

Cable A

Cable C

Magnetic

Pickup

Actuator

Idle

switch

CCW

VR1 5K

CW

Analogue

Input

Cable B

VR2

DROOP

DIF.

INT.

GAIN

RAMP

SW1-ON    600~1200HZ
SW2-ON  1200~2500HZ

SW4-ON  5000~9500HZ

SW3-ON  2500~5000HZ

POWER : DC12/24V

IDLE

1

2

3

ACT

4

5

6

7

MPU

9

ILS

8

10

11

~

+

REMOTE

SPEED POT

RUN SPEED

IDLE SPEED

SW5-ON  PT-PUMP

EG3002 

+

SW6-ON  Slow response 

SW

R

3

1

2

1K

3

1

2

CCW

CW

 

ATTENTION 

1.  The unit must be installed by qualified technical personnel. Improper installation, wiring or settings could lead 

to injury to personnel and/or damage to equipment. 

2.  This  unit  has  no  Over  Speed  Protection  function.  It  is  recommended  to  install  a  separate  over  speed 

protection device. 

3.  The battery connects directly to the controller with a fuse for protection. Use 20A slow-blow fuse. 

4.  Terminals 1, 2, 4, 5 must use 2.0 mm2 (14 AWG ) or larger wires. 

5.  Cables A, B, and C must be copper shielded cable of 26 AWG or larger. 

6.  In order to reduce noise interference copper shielding should be grounded on one end only. 

Содержание EG3002

Страница 1: ...06037 Taiwan EG3002 Electronic Engine Governor Controller User Manual Engine Start Smoke Limiting function IDLE Speed Setting For External Built in and PT Pump type actuators Newly added extreme slow response engine setting All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ... 10 000 Hz Voltage 1 120 Vac RMS Speed Temperature Shift Less than 3 at temperature range 40 to 80 C Frequency Adjustment Speed Adjustment pot 25 turn Environment Setting range 600 9 500 Hz With DIP Switch Operating Temperature 40 to 80 C Storage Temperature 40 to 85 C Remote Speed Potentiometer Terminals 6 7 9 Relative Humidity Max 95 Max 7 5 KΩ 1 watt potentiometer Vibration 5 5Gs 60 Hz Isochron...

Страница 3: ...signal from the load sharing controller Must be isolated from battery power Terminal 6 is ground of load sharing controller Terminal 8 is input signal from controller 1 2 Battery Input Connect to genset battery Use14 AWG wire or larger 3 IDLE Control Contact When shorted to terminal 2 unit will go to IDLE state 4 5 Output to Actuator Use 14 AWG wire or larger INT Integral Setting DIF Differential ...

Страница 4: ...N Slow response SW R 3 1 2 1K 3 1 2 CCW CW ATTENTION 1 The unit must be installed by qualified technical personnel Improper installation wiring or settings could lead to injury to personnel and or damage to equipment 2 This unit has no Over Speed Protection function It is recommended to install a separate over speed protection device 3 The battery connects directly to the controller with a fuse fo...

Страница 5: ...ill begin to make a clicking sound but will not be damaged 6 2 Trial Run 6 2 1 Engine will not start Refer to Section 7 1 Troubleshooting below for possible causes If the engine still will not start normally then increase Run Speed setting or Frequency Range SW setting to a higher range Run Speed should be set to minimum at this time 6 2 2 If engine starts normally then slowly adjust Run Speed to ...

Страница 6: ... until optimal settings are achieved 3 Engine speed instability can be divided into slow oscillations once every 2 to 5 seconds and rapid oscillations 2 to 8 times per second slow oscillation is usually because GAIN is too low and or INT is too high Rapid oscillations however can occur in two ways 4 2 4 times per second GAIN setting too high 4 8 times per second DIF setting too high 6 5 Remote Spe...

Страница 7: ...e then replace the MPU During engine start confirm that the input voltage to Terminals 10 11 is greater than 1 Vac If less than 1 Vac check the gap between the tip of the MPU and the flywheel teeth The distance should be 0 037 mm to 0 127 mm 3 Actuator fault failed disconnected etc 3 If the two items above are both normal then check whether Terminals 4 5 have a voltage output during cranking If th...

Страница 8: ...hether MPU is disconnected Must be directly connected to Terminals 10 11 Resistance of 10 1 000Ω is normal Check that MPU has been connected with shielded wire grounded at one end Repair wiring as required 4 Controller defective 4 With engine OFF apply power to the controller if actuator linkage moves or if there is a voltage output on Terminals 4 5 this indicates the controller is defective 7 4 E...

Отзывы: