background image

 

___________________________________________________________________________________________ 

2

 

EA63-2.5

 

SECTION 1 : SPECIFICATION 

Sensing Input 

EMI Suppression 

  Voltage 

  90 

 130 Vac @ 120 Vac 

  Internal electromagnetic interference filtering

 

   

180 

 260 Vac @ 240 Vac 

 

   

1 phase 2 wire, DIP switch selectable 

Static Power Dissipation

 

  Frequency 

45/65 Hz, adjustment 

  Max.10 watts 

 

 

Output

 

Under Frequency Protection 

  Voltage 

Max. 50 Vdc @power input 120 Vac 

  Adjustable range 45 

 55 Hz 

   

Max. 63 Vdc @power input 240 Vac 

 

  Current 

Continuous 2.5A 

Voltage Thermal Drift 

   

Intermittent 4A for 60 sec. 

  Less than 3% at temperature range -

40 to +70 ˚C 

  Resistance 

Min. 25 ohms 

 

  Fuse Spec. 

Slow blow 5 x 20mm S505-3.15A / 250V 

Environment 

 

  Operating Temperature 

-40 to +60 

˚C 

External Voltage Adjustment

 

  Storage Temperature 

-40 to +85 

˚C 

  Max. +/- 15%  @ 5K ohms 1 watt potentiometer 

  Relative Humidity 

Max. 95% 

 

  Vibration 

1.5 Gs @ 5 

– 30 Hz 

Voltage Regulation

 

   

5.0 Gs @ 30 

– 500 Hz 

  Less than +/- 1% ( with 4% engine governing )

 

 

 

Dimensions 

Build Up Voltage

 

  101.0 (L) x 69.0 (W) x 22.0 (H) mm

 

  5 Vac residual volts at power input terminal 

 

 

Weight 

 

  107 g +/- 2%

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

TYPICAL 

FREQUENCY 

COMPENSATION 

CURVES (See Figure 1) 

1.  When  the  frequency  of  the  generator  is  lower 

than the factory setting, the rated phase voltage 
will  decrease  to  protect  the  regulator  or  exciter 
because of over exciter current. 

2.  Factory Setting

45 Hz

 

+/- 4% 

 

ATTENTION 

1.  AVR  can  be  mounted  directly  on  the  engine, 

genset, switchgear, control panel, or any position 
that  will  not  affect  operation.  For  dimension 
reference, please see Figure 2. 

2.  All  voltage  readings  are  to  be  taken  with  an 

average-reading voltmeter. 

Figure 1

 

Typical Frequency Compensation Curves 

 

Unit : mm 

Figure 2

 

Outline Diagram 

Содержание EA63-2.5

Страница 1: ...Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA63 2 5 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Basler AVC63 2 5 Use for reference only and not a genuine Balser product Use with Kutai EP200 Paralleling Module for parallel operation ...

Страница 2: ...External Voltage Adjustment Storage Temperature 40 to 85 C Max 15 5K ohms 1 watt potentiometer Relative Humidity Max 95 Vibration 1 5 Gs 5 30 Hz Voltage Regulation 5 0 Gs 30 500 Hz Less than 1 with 4 engine governing Dimensions Build Up Voltage 101 0 L x 69 0 W x 22 0 H mm 5 Vac residual volts at power input terminal Weight 107 g 2 TYPICAL FREQUENCY COMPENSATION CURVES See Figure 1 1 When the freq...

Страница 3: ...hing 2 3 3 Slowly adjust the regulator VOLT ADJ CW until the generator output voltage reaches the nominal value If used adjust the remote VOLT ADJ to set the generator voltage to the exact value desired RESULT Voltage should build up to rated value If voltage does not build up to rated value check generator for short or excessive load 2 3 4 Check regulator under normal operating and loading condit...

Страница 4: ...h high interrupting capacity 2 5 4 Excitation On Off Switch If used Operational Test Figure 4 Interconnection Diagram 120 240 V Nominal 1 phase 3 Wire Figure 5 Interconnection Diagram 120 208 V Nominal 3 phase 4 Wire Wye Connection Figure 6 Interconnection Diagram 277 480 V Nominal 3 phase 4 Wire Wye Connection Figure 7 Use only original supplied spare protection fuse for fuse replacement Appearan...

Отзывы: