EA448B

 

SECTION 3: DIP SWITCH SETTING   

 
 
 
 
 
 

40

50

(50)

(60)

S

F

J1

J1

1 2 3

J2

1 2 3

J2

X1

X2

Power Input 

Connect working voltage, Max. 150Vac 

Z1

Z2

Auxiliary Power Input 

Connect Auxiliary voltage, Max. 150Vac 

50Hz

60Hz

Frequency Selection 

E+

E-

Excitation Output 

Connect to generator excitation field 
 

E1

E2

Sensing Input 

Connect sensing input voltage Max. 600Vac 
 

Sensing Input Voltage Selection 

1 OFF  2  OFF 

110Vac (95~140V) 

1 ON  2  OFF 

220Vac (170~260V) 

1 ON  2  ON 

380Vac (340~520V) 

 

S1

S2

Quadrature Droop Input 

Connect to generator CT 
 

1KΩ

External Voltage Adjustment 

Connect to external 1KΩ potentiometer   

Terminals must be shorted when not in used 

3Ph.

Three Phase Sensing Input 

Connect to Three Phase Sensing 

Module 

EXC.MAX.

Over Excitation Current Limiting 

Excitation output will be turn off when excitation 

current is over the setting value   

Min. 3.5A, Max. 10A 

V/Hz

Under Frequency Adjustment

 

Adjustment for Under frequency and LAM 
knee point 

STAB.

Stability Adjustment 

Under no-load operation, slowly adjust the 

STAB VR counterclockwise until the 

voltage is unstable, and then adjust it 

clockwise for about 1/5 circle 
 

VOLT

Voltage Adjustment 

Adjust Generator output voltage 

Adjustment range can be set by DIP SW 

STAT.

Quadrature Droop Adjustment 

Adjust the ratio of the idle power to the 

voltage drop, when used in parallel. 

Adjustment range is 0% to 7% 

J1

 

Connected

With LAM protection 

 

LAM

When Generator is loading the Engine speed will be 

reduced. When engine speed is lower than pre-set frequency 

threshold (V/Hz knee point), AVR will reduce voltage in 13% 

or 25% (set by J2). This will make the active power of loading 

reduce 25% to 45%, until engine speed reach pre-set value 

once again then voltage will resume to normal value. 

J1 Disconnected

Without LAM protection 

When J2 1

2 is shorted

Drop ratio 13% in LAM voltage 

When J2 2

3 is shorted

Drop ratio 25% in LAM voltage 

 

LED

LED will illuminate when AVR in normal operation 

ST6

ST1

ST2

VOLT

STAB.

V/Hz

EXC.MAX.

J1

J2

ST7

1 2 3

STAT.

X2

Z1

X1

Z2

E+

E-

E1

E2

50Hz 60Hz

LED

EA448B

ST1

Single Phase / Three Phase Sensing Selection

 

Shorted

Single phase sensing 

Open

Three phase sensing (must use with Three Phase Sensing Module) 

 

ST2

Response Time Selection 

Shorted

Slow 

Open

Fast 

Select response time according to Stability adjustment 

 

ST6

Instantaneous Compensation for Voltage

 

Shorted

For Generator less than 600 KVA 

Open

For Generator greater than 600 KVA 

 

ST7

  Keep shorted 

 

Содержание EA448B

Страница 1: ...ohsiung City 806037 Taiwan EA448B Generator Automatic Voltage Regulator Operation Manual Permanent Magnet Generator or A R E P or Auxiliary Winding Type Compatible with Leroy Somer R448 Use with KUTAI EPMG 1270 EPMG 2470 add on module can boost generator motor starting capacity Use for reference purpose only and not a genuine Leroy Somer product ...

Страница 2: ...lected Static Power Dissipation Max 4 watts Power Input X1 X2 Voltage 40 150 Vac 1 phase 2 wire Under Frequency Protection Frequency 40 500 Hz 50 Hz system knee point at 45Hz 60 Hz systems knee point at 55Hz Auxiliary Input Z1 Z2 Voltage 40 150 Vac 1 phase 2 wire Over Excitation Current limitation Frequency 40 500 Hz 3 5A to 10A EXC MAX Adjustable Excitation Output E E Voltage Thermal Drift 120V 1...

Страница 3: ...e and then adjust it clockwise for about 1 5 circle VOLT Voltage Adjustment Adjust Generator output voltage Adjustment range can be set by DIP SW STAT Quadrature Droop Adjustment Adjust the ratio of the idle power to the voltage drop when used in parallel Adjustment range is 0 to 7 J1 Connected With LAM protection LAM When Generator is loading the Engine speed will be reduced When engine speed is ...

Страница 4: ...Excited SHUNT Figure 3 Auxiliary and Harmonic Power Winding T1 T7 T2 T8 T3 T9 T4 T10 T5 T11 T6 T12 FIELD STATOR 12 wires marked T1 to T12 PMG X2 Z1 X1 Z2 E E E1 E2 60Hz 50Hz S2 S1 3Ph potentiometer 1k 1W External T1 1K EA448B Figure 4 PMG Winding ATTENTION 1 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in lo...

Отзывы: