SECTION 1 : SUMMARY 

EA06 is equipped with 3 separate sensing inputs (1-2, 
3-4, 5-6 terminals R.S.T phase), which can survey from 
single  up  to  three  phase  voltages  and  check  the 
average voltage from Y, YY or 

 wiring accordingly to 

the generator requirement or user preference. 
 
 

The AVR is equipped with adjustable under frequency 
protection  and  over  voltage  protection  to  prevent 
generator from overloading and over excitation. 
 
The  3  LED  each  represents  (Green)  normal  operation, 
(Red) under frequency and (Yellow) over excitation. 
 
The  built  in  EMS  filter  helps  to  prevent  possible 
interference from the AVR to the generator.

SECTION 2 : SPECIFICATION 

Sensing Input (1-2, 3-4, 5-6) 

EMI Suppression 

  Voltage 

100 

 290 Vac / 270 

 520 Vac

 

  Internal electromagnetic interference filtering

 

 

1 or 3 phase, selectable by wiring

 

 

  Frequency 

50/60 Hz 

Static Power Dissipation

 

 

  Max.5 watts 

Power Input (+, 2)

 

 

  Voltage 

50 

 280 Vac 

Over Excitation Protection

 

  Frequency 

50/60 Hz 

  25 

 55 Vdc @ 0.1 

 20 sec 

 

 

Excitation Output (+ , 

–)

 

Under-Frequency Knee Point Thermal Drift 

  Voltage 

Max. 63 Vdc @power input 220 Vac 

  Adjustable range 42 

 62 Hz 

  Current 

Continuous 6A 

 

   

Intermittent 7A for 10 secs. 

Voltage Thermal Drift 

  Resistance 

10 

 100 ohms 

  Less than 3% at temperature range -40 to 

+70 ˚C 

  Fuse Spec. 

Slow blow 5 x 20mm S505-6.3A / 250V   

 

Environment

 

External Voltage Adjustment

 

  Operating Temperature 

-40 to +60 

˚C 

  Max. +/- 5%  @ 100K ohms 1/2 watt potentiometer 

  Storage Temperature 

-40 to +80 

˚C 

 

  Relative Humidity 

Max. 95% 

Voltage Regulation

 

  Vibration 

1.5 Gs @ 5 

– 30 Hz 

  Less than +/- 1% ( with 4% engine governing ) 

   

5.0 Gs @ 30 

– 500 Hz 

 

 

Build Up Voltage

 

Dimensions 

  5 Vac 25 Hz residual volts at power input terminal 

  150.0 (L) x 115.0 (W) x 41.0 (H) mm 

 

 

Soft Start Ramp Time 

Weight 

  4 s/- 10% 

  440 g +/- 2%

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ATTENTION 

1.  AVR  can  be  mounted  directly  on  the  engine,  genset, 

switchgear,  control  panel,  or  any  position  that  will  not 
affects operation. For  dimension  reference, please  see 
Figure 1. 

2.  All  voltage  readings  are  to  be  taken  with  an 

average-reading  voltmeter  Meggers  and  high-potential 
test  equipment  must  not  be  used.  Use  of  such 
equipment could damage the AVR. 

3.  Secure  all  wiring  connection.  Do  not  install  AVR  at  a 

place with high vibrations to prevent loose connections. 
For safety do not touch the heat sink while in operation. 

4.  Improper  setting  of  under-frequency  protection  could 

cause the output voltage of the unit to drop or become 
unstable under with changes in load. Avoid making any 
changes to the U/F setting unless necessary. 

41.0

20.5

87.0

115.0

122.0

150.0

4

3

2

1

0

B

+

6

5

EA06

   5.3

 

Figure 1

 

Outline Drawing 

Содержание EA06

Страница 1: ...Dist Kaohsiung City 80664 Taiwan EA06 Generator Automatic Voltage Regulator Operation Manual Suitable for Single or Three Phase Self Excited Brushless Generator Compatible replacement for Mecc Alte UVR6 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ...rmittent 7A for 10 secs Voltage Thermal Drift Resistance 10 100 ohms Less than 3 at temperature range 40 to 70 C Fuse Spec Slow blow 5 x 20mm S505 6 3A 250V Environment External Voltage Adjustment Operating Temperature 40 to 60 C Max 5 100K ohms 1 2 watt potentiometer Storage Temperature 40 to 80 C Relative Humidity Max 95 Voltage Regulation Vibration 1 5 Gs 5 30 Hz Less than 1 with 4 engine gover...

Страница 3: ...ent 3 7 1 Slowly and precise adjustment of STAB potentiometer can change the respond time between the AVR and generator Inadequate adjustment will cause voltage instability and over adjusting will cause sudden overly voltage variation under heavy load 3 7 2 Analogue type multi voltmeter is suggested when adjusting the voltage stability Adjust the STAB potentiometer until the pointer on the multi v...

Страница 4: ...oint B Severely deformed generator output wave form C Capacitive load over ratio Power factor in lead D Change the AVR and restart E Under over excitation voltage protection Overload protection SECTION 5 FIELD FLASHING When the regulator is installed correctly but the generator is failed to generate power Besides carbon brushes were worn out here are two possible causes below 5 1 The polarity of f...

Страница 5: ...5 R 60HZ 1 3 2 0 B N T Field VR S R S T N T N R S winding 3 4 6 5 60HZ 1 0 2 B VR R S T N Auxiliary Field 3 T 4 5 6 N R S 60HZ 0 1 2 B Auxiliary winding VR Field R T S N winding R S T N Auxiliary Field T N R S Auxiliary winding 3 5 4 6 0 1 2 60HZ B VR Field T N R S Figure 5 3 phase 240 277 Vac Figure 6 1 phase 120 240 Vac With auxiliary winding 3 4 6 5 0 1 2 VR 60HZ B R S T N Field T N R S 3 4 6 5...

Страница 6: ...3A 3 VR Terminal SR7 1 1 N T S R 5 6 2 4 3 Field Auxiliary B 0 winding 60HZ VR N S T R 4 3 5 6 4 4 S Field S winding Auxiliary T N 0 1 3 4 5 2 6 5C 4 5 B 60HZ VR 3 1 3A SR7 Terminal 5 6 T N 4 5C Auxiliary winding R S N T R 4 6 5 0 2 3 1 5C 4 5 60HZ B VR 1 3 3A Field Terminal SR7 R 5 6 S T R N 4 5C 2 3 5 2 3 5 Figure 14 1 phase 120 240 Vac Figure 15 1 phase 120 240 Vac With auxiliary winding Field ...

Отзывы: