SECTION 3 : OPERATOR PANEL 

3.1  General 

The  operator  panel,  which  is  normally  accessible 
from  the  outside  of  a  panel  or  door,  provides  a 
means  for  being  alerted  to  specific  conditions, 
receiving 

functional 

help, 

programming 

and 

parameter monitoring. 

3.2  Display Window 

The ATS-380 controller includes a 4 digit 7-segment 
display is used to display all monitored parameters, 
setting  parameters  and  messages  in  easy  to  read 
formats. 

Different  displays  can  be  presented  via  the  display 
window: 

  Normal source voltage and frequency parameter 

display. 

  Standby source voltage and frequency parameter 

display. 

  TDEN,TDNE  and  TDEC  real  time  countdown 

display. 

  Program setting parameter display. 

NOTICE 

Although  a  wide  variety  of  parameters  and 

setting  can  be  displayed,  they  are  not 

displayed if they were not originally ordered 

and programmed.

 

3.3  Operate Pushbuttons 

There  are  five  front  panel  pushbuttons  accomplish 
their  function  when  pressed  and  released.  Certain 
pushbuttons,  like  the  increase(

)and  decrease(

pushbuttons,  will  also  continue  to  scroll  if  they  are 
pressed and not released at program procedure. 

3.3.1  Increase (

) Pushbutton 

When  the  ATS-380  controller  operated  at  normal 
status,  each  press  of  the  increase  (

)  key  will 

change  the  real  parameter  display  from  one  phase 
to  another  phase.  When  the  user  initiates  the 
program mode, each press of the Increase (

) key 

will  scroll  through  all  available  parameter.  When 
pressing and releasing  the increase (

) button the 

displayed parameter can be increased by one. The 
Increase (

) pushbutton will continue to scroll if it is 

pressed and not released. 

3.3.2  Decrease (

) Pushbutton 

At  the  normal  operate  status,  each  press  of  the 
decrease  (

)  key  will  change  the  real  parameter 

display  between  voltage  and  frequency.  When  the 
user  initiates  program  mode,  each  press  of  the 
decrease  (

)  key  will  scroll  through  all  available 

parameter.  When  pressing  and  releasing  the 
decrease  (

)  button  the  displayed  parameter  can 

be decreased by one. The decrease (

) pushbutton 

will  continue  to  scroll  if  it  is  pressed  and  not 
released. 

3.3.3  Auto Function Pushbutton 

Pushing the AUTO select key, the ATS-380 will run 
in automatic mode and a LED is provided to indicate 
the  auto  position.  The  ATS  transfer  and  retransfer 
from  source  to  source  as  dictated  by  the  features 
supplied and their programmed setting values. 

3.3.4  Test Function Pushbutton 

The ATS-380 is provided with a test pushbutton that 
simulates  a  loss  of  normal  source.  Pushing  the 
TEST select key, the ATS-380 will run in engine test 
mode  and  a  LED  is  provided  to  indicate  the  test 
position. 

3.3.5  Off Function Pushbutton 

Pushing the OFF select key, the ATS-380 will run in 
off mode. All the functions of the ATS-380 controller 
Will be disable. 

When in program mode, pushing the off pushbutton 
allows the user to change the program line table and 
set  the  selected  parameter  using  decrease  (

)  or 

increase (

) button. 

3.4  Panel LED Outputs 

Auto Position ( Green ) 

Indicates  that  the  ATS-380  controller  is  setting  to 
AUTO function.

Содержание ATS-380

Страница 1: ...S 380 Ver1 0 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw ...

Страница 2: ...ear Access Area 6 SECTOIN 3 OPERATOR PANEL 3 1 General 9 3 2 Display Window 9 3 3 Operate Pushbuttons 9 3 4 Panel LED Outputs 9 SECTOIN 4 OPERATION 4 1 General 10 4 2 Automatic Mode 10 4 3 Engine Test Mode 11 4 4 Off Mode 11 4 5 Programming Mode 11 4 6 Specification Summary 13 SECTOIN 5 INSTALLATION INSTRUCTIONS 5 1 General 13 5 2 Panel Cut Out 13 5 3 Unit Dimensions 14 SECTOIN 6 TYPICAL WIRING 6 ...

Страница 3: ...nnect the load to the source of power 2 A transfer mechanism to affect the transfer of the main contacts from one source to another source 3 Intelligence control unit to constantly monitor the condition of the power sources and thus provide the intelligence necessary for the switch and related circuit operation This manual deals with the third basic element of the automatic transfer switch the req...

Страница 4: ...via friendly setting procedure depending upon customer requirements The specific variable set points associated with standard and factory activated features are stored in a nonvolatile memory Activated feature set points are available for customer adjustment Feature 1 Time Delay Normal to Emergency TDNE TDNE provides a time delay when transferring the Normal source to the Standby source It ensures...

Страница 5: ...range 1 99 sec Feature 9 Pre exerciser Signal Output When the auxiliary contactor was set to be a pre exerciser signal output The ATS 380 controller will provide a pre transfer signal output before exerciser the engine It is an advance warring to avoid person damaged before the generator auto start itself Refer to program line 30 32 Adjustable range 1 99 sec Feature 10 Transfer Fail Alarm Signal O...

Страница 6: ...ls concerning the kind of information that can be viewed in the display window refer to Paragraph 3 2 2 3 Operate Pushbuttons Refer to Figure 1 The front operator panel supports five long life pushbuttons Pushbuttons accomplish their function when pressed and released Refer to Paragraph 3 3 for information concerning the function of specific pushbuttons 2 4 Panel LEDs Outputs Refer to Figure 1 Thi...

Страница 7: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 7 Figure 1 Front Panel Display Window Operator Pushbutton ATS status LEDs ...

Страница 8: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 8 Figure 2 Rear Area TB1 TB2 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 ...

Страница 9: ...ach press of the Increase key will scroll through all available parameter When pressing and releasing the increase button the displayed parameter can be increased by one The Increase pushbutton will continue to scroll if it is pressed and not released 3 3 2 Decrease Pushbutton At the normal operate status each press of the decrease key will change the real parameter display between voltage and fre...

Страница 10: ...unavailable and the voltage is over the programmed parameters Standby Under Voltage Red Indicates that the standby source is unavailable and the voltage is below the programmed parameters Standby Over Frequency Red Indicates that the standby source is unavailable and the frequency is over the programmed parameters Standby Under Frequency Red Indicates that the standby source is unavailable and the...

Страница 11: ...llows the user to change the program line table and set the selected parameter using decrease or increase button 4 5 Programming Mode The ATS 380 controller is fully programmable from the devices faceplate once in the Programming Mode Any operator associated with programming the ATS 380 controller will quickly discover that ATS 380 controller programming is just a matter of simple Begin to start p...

Страница 12: ...urce frequency output 0 99sec 0 Without freq monitor function 10 Sec 15 Standby source over voltage setting 39 48 390V 480V 42 420V 16 Standby source under voltage setting 28 37 280V 370V 34 340V 17 Time delay if there is a problem with standby source voltage output 0 99sec 0 Without volt monitor function 10 Sec 18 Standby source over frequency setting 51 70Hz 55Hz 19 Standby source under frequenc...

Страница 13: ...VAC 50 60 HZ Frequency Measurement Range 40HZ to 70HZ Generator Start Relay 7A 250VAC Max Transfer to Normal Relay 7A 250VAC Max Transfer to Standby Relay 7A 250VAC Max Auxiliary Relay 0 5A 120VAC 1 0A 24VDC Operating Temperature 20 C 70 C Storage Temperature 35 C 85 C Operating Humidity 0 to 95 relative humidity SECTION 5 INSTALLATION INSTRUCTIONS 5 1 General The ATS 380 controller has been desig...

Страница 14: ...system voltage from 280 VAC t0 480 VAC at 50 or 60 Hz The ATS 380 allowed User to adjust the display voltage by key in the real voltage value of normal source L1 L3 The ATS 380 controller will follow the scale between input volt and key in volt and show the correct voltage on the display window refer to program line 1 The ATS 380 maximum transfer current is 6 Amps When the switch transfer current ...

Страница 15: ...Automatic Transfer Switch ______________________________________________________________________________________ 15 6 2 4P 380V Connecting Wire Diagram 6 2 1 MCCB Type Wiring Diagram ATS 380 CONTROL UNIT MOTOR ...

Страница 16: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 16 6 2 2 One Coil Double Throw Typical Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 17: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 17 6 2 3 Two Coils Double Throw Type Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 18: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 18 6 2 4 Magnetic Contactor Type Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 19: ...er Switch ______________________________________________________________________________________ 19 6 3 3P 380V Connecting Wire Diagram 6 3 1 MCCB Type Wiring Diagram Normal Phase N Emergency Phase N MOTOR ATS 380 CONTROL UNIT ...

Страница 20: ...atic Transfer Switch ______________________________________________________________________________________ 20 6 3 2 One Coil Double Throw Typical Wiring Diagram Normal Phase N Emergency Phase N ATS 380 CONTROL UNIT ...

Страница 21: ...matic Transfer Switch ______________________________________________________________________________________ 21 6 3 3 Two Coils Double Throw Type Wiring Diagram Emergency Phase N ATS 380 CONTROL UNIT Normal Phase N ...

Страница 22: ...tomatic Transfer Switch ______________________________________________________________________________________ 22 6 3 4 Magnetic Contactor Type Wiring Diagram ATS 380 CONTROL UNIT Normal Phase N Emergency Phase N ...

Страница 23: ...itch ______________________________________________________________________________________ 23 6 4 Single Phase 380V Connecting Wire Diagram 6 4 1 MCCB Type Wiring Diagram MOTOR ATS 380 CONTROL UNIT Normal Phase N Emergency Phase N ...

Страница 24: ...atic Transfer Switch ______________________________________________________________________________________ 24 6 4 2 One Coil Double Throw Typical Wiring Diagram ATS 380 CONTROL UNIT Normal Phase N Emergency Phase N ...

Страница 25: ...matic Transfer Switch ______________________________________________________________________________________ 25 6 4 3 Two Coils Double Throw Type Wiring Diagram Normal Phase N Emergency Phase N ATS 380 CONTROL UNIT ...

Страница 26: ...tomatic Transfer Switch ______________________________________________________________________________________ 26 6 4 4 Magnetic Contactor Type Wiring Diagram Normal Phase N Emergency Phase N ATS 380 CONTROL UNIT ...

Страница 27: ... Switch ______________________________________________________________________________________ 27 6 5 Connecting Wire Diagram When The Switch Transfer Current Over 6 Amps 6 5 1 MCCB Type Wiring Diagram MOTOR ATS 380 CONTROL UNIT ...

Страница 28: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 28 6 5 2 One Coil Double Throw Typical Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 29: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 29 6 5 3 Two Coils Double Throw Type Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 30: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 30 6 5 4 Magnetic Contactor Type Wiring Diagram ATS 380 CONTROL UNIT ...

Отзывы: