______________________________________________________________________________________ 

11 

4.3  Engine Test Mode 

The ATS-380 is provided with a test pushbutton that 
simulates  a  loss  of  normal  source.  Pushing  the 
TEST key on the front of panel, the ATS-380 will run 
in  engine  test  mode.  The  TDES  and  TDNE 
programmed  time  delays  will  be  performed  as  part 
of the Test. There are two test modes: 

  With load engine test. 

  Without  load  engine  test.  (The  TDNE  time  delay 

will not be performed) 

When the user terminated the engine test mode by 
press the AUTO pushbutton, then the controller will 
return  to  automatic  mode.  When  normal  power  is 
available, the transfer switch automatically transfers 
back  from  standby  source  to  normal  source  and 
initiates  engine  shutdown  after  a  preset  engine 
cooling down time delay.   

When the user terminated the engine test mode by 
press  the  OFF  pushbutton,  the  ATS  will  keeps  the 
present  status  and  the  ATS-380  controller  initiates 
engine shutdown immediately without cooling down 
time delay and returns to off mode. 

4.4  Off Mode 

The off mode of the ATS-380 controller  will disable 
all  the  transferred  and  protected  functions,  and  all 
the status LEDs will be turned off in this mode. The 
real  time  clock  will  be  showed  on  the  front  display 
window.   

In  the  event  that  power  is  lost  from  the  normal 
source,  the  ATS-380  controller  will  not  start  the 
engine  and  the  ATS  can’t  transfer  the  load  to  the 
standby source automatically. 

When in program mode, pushing the off pushbutton 
allows the user to change the program line table and 
set  the  selected  parameter  using  decrease  (

)  or 

increase (

) button. 

4.5  Programming Mode 

The  ATS-380  controller  is  fully  programmable  from 
the  devices  faceplate  once  in  the  Programming 
Mode.  Any  operator  associated  with  programming 
the  ATS-380  controller  will  quickly  discover  that 
ATS-380  controller  programming  is  just  a matter  of 
simple.   

 

Begin  to  start  programming  mode,  set  the 
ATS-380on off mode, push the button “ increase (

& decrease (

) ” on the front panel for 4 seconds. 

The word “ Ver 1.0 ” will appear on the front display 
window  for  2  seconds.  This  number  indicates  the 
version of the software. 

You  are  now  ready  to  start  a  line  by  line 
programming sequence. To advance to the next line, 
push the OFF button on the front panel. To change 
each  line’s  programming  parameters,  press  the 
increase  (

)  and  decrease  (

)  buttons.  When 

pressing  and  releasing  the  increase  (

)  or 

decrease  (

)  key  the  displayed  parameter  can  be 

increased    or decreased by one. The Increase (

or decrease (

) pushbutton will continue to scroll if 

it is pressed and not released. 

Always push the “ OFF ” button to advance to next 
programming line or until the word “ END ” appears 
on the screen. To immediately end the programming 
mode, you can simply push the “ OFF ” button for 4 
seconds at any time. Then the word “ END ” on the 
display 

window 

indicates 

the 

end 

of 

the 

programming mode. 

Should  you  make  an  error  or  desire  to  return  to 
factory  settings,  stay  in  programming  mode  and 
simultaneously  press  all  3  buttons  :  increase  (

), 

decrease (

) and OFF for 4 seconds. The ATS-380 

controller  will  now  automatically  program  itself  to 
factory  settings  and  the  word  “  Au.Po  ”  will  appear 
on  the  display  window.  (  See  line  by  line 
programming table for ATS-380 factory settings. ) 

Содержание ATS-380

Страница 1: ...S 380 Ver1 0 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw ...

Страница 2: ...ear Access Area 6 SECTOIN 3 OPERATOR PANEL 3 1 General 9 3 2 Display Window 9 3 3 Operate Pushbuttons 9 3 4 Panel LED Outputs 9 SECTOIN 4 OPERATION 4 1 General 10 4 2 Automatic Mode 10 4 3 Engine Test Mode 11 4 4 Off Mode 11 4 5 Programming Mode 11 4 6 Specification Summary 13 SECTOIN 5 INSTALLATION INSTRUCTIONS 5 1 General 13 5 2 Panel Cut Out 13 5 3 Unit Dimensions 14 SECTOIN 6 TYPICAL WIRING 6 ...

Страница 3: ...nnect the load to the source of power 2 A transfer mechanism to affect the transfer of the main contacts from one source to another source 3 Intelligence control unit to constantly monitor the condition of the power sources and thus provide the intelligence necessary for the switch and related circuit operation This manual deals with the third basic element of the automatic transfer switch the req...

Страница 4: ...via friendly setting procedure depending upon customer requirements The specific variable set points associated with standard and factory activated features are stored in a nonvolatile memory Activated feature set points are available for customer adjustment Feature 1 Time Delay Normal to Emergency TDNE TDNE provides a time delay when transferring the Normal source to the Standby source It ensures...

Страница 5: ...range 1 99 sec Feature 9 Pre exerciser Signal Output When the auxiliary contactor was set to be a pre exerciser signal output The ATS 380 controller will provide a pre transfer signal output before exerciser the engine It is an advance warring to avoid person damaged before the generator auto start itself Refer to program line 30 32 Adjustable range 1 99 sec Feature 10 Transfer Fail Alarm Signal O...

Страница 6: ...ls concerning the kind of information that can be viewed in the display window refer to Paragraph 3 2 2 3 Operate Pushbuttons Refer to Figure 1 The front operator panel supports five long life pushbuttons Pushbuttons accomplish their function when pressed and released Refer to Paragraph 3 3 for information concerning the function of specific pushbuttons 2 4 Panel LEDs Outputs Refer to Figure 1 Thi...

Страница 7: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 7 Figure 1 Front Panel Display Window Operator Pushbutton ATS status LEDs ...

Страница 8: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 8 Figure 2 Rear Area TB1 TB2 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 ...

Страница 9: ...ach press of the Increase key will scroll through all available parameter When pressing and releasing the increase button the displayed parameter can be increased by one The Increase pushbutton will continue to scroll if it is pressed and not released 3 3 2 Decrease Pushbutton At the normal operate status each press of the decrease key will change the real parameter display between voltage and fre...

Страница 10: ...unavailable and the voltage is over the programmed parameters Standby Under Voltage Red Indicates that the standby source is unavailable and the voltage is below the programmed parameters Standby Over Frequency Red Indicates that the standby source is unavailable and the frequency is over the programmed parameters Standby Under Frequency Red Indicates that the standby source is unavailable and the...

Страница 11: ...llows the user to change the program line table and set the selected parameter using decrease or increase button 4 5 Programming Mode The ATS 380 controller is fully programmable from the devices faceplate once in the Programming Mode Any operator associated with programming the ATS 380 controller will quickly discover that ATS 380 controller programming is just a matter of simple Begin to start p...

Страница 12: ...urce frequency output 0 99sec 0 Without freq monitor function 10 Sec 15 Standby source over voltage setting 39 48 390V 480V 42 420V 16 Standby source under voltage setting 28 37 280V 370V 34 340V 17 Time delay if there is a problem with standby source voltage output 0 99sec 0 Without volt monitor function 10 Sec 18 Standby source over frequency setting 51 70Hz 55Hz 19 Standby source under frequenc...

Страница 13: ...VAC 50 60 HZ Frequency Measurement Range 40HZ to 70HZ Generator Start Relay 7A 250VAC Max Transfer to Normal Relay 7A 250VAC Max Transfer to Standby Relay 7A 250VAC Max Auxiliary Relay 0 5A 120VAC 1 0A 24VDC Operating Temperature 20 C 70 C Storage Temperature 35 C 85 C Operating Humidity 0 to 95 relative humidity SECTION 5 INSTALLATION INSTRUCTIONS 5 1 General The ATS 380 controller has been desig...

Страница 14: ...system voltage from 280 VAC t0 480 VAC at 50 or 60 Hz The ATS 380 allowed User to adjust the display voltage by key in the real voltage value of normal source L1 L3 The ATS 380 controller will follow the scale between input volt and key in volt and show the correct voltage on the display window refer to program line 1 The ATS 380 maximum transfer current is 6 Amps When the switch transfer current ...

Страница 15: ...Automatic Transfer Switch ______________________________________________________________________________________ 15 6 2 4P 380V Connecting Wire Diagram 6 2 1 MCCB Type Wiring Diagram ATS 380 CONTROL UNIT MOTOR ...

Страница 16: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 16 6 2 2 One Coil Double Throw Typical Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 17: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 17 6 2 3 Two Coils Double Throw Type Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 18: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 18 6 2 4 Magnetic Contactor Type Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 19: ...er Switch ______________________________________________________________________________________ 19 6 3 3P 380V Connecting Wire Diagram 6 3 1 MCCB Type Wiring Diagram Normal Phase N Emergency Phase N MOTOR ATS 380 CONTROL UNIT ...

Страница 20: ...atic Transfer Switch ______________________________________________________________________________________ 20 6 3 2 One Coil Double Throw Typical Wiring Diagram Normal Phase N Emergency Phase N ATS 380 CONTROL UNIT ...

Страница 21: ...matic Transfer Switch ______________________________________________________________________________________ 21 6 3 3 Two Coils Double Throw Type Wiring Diagram Emergency Phase N ATS 380 CONTROL UNIT Normal Phase N ...

Страница 22: ...tomatic Transfer Switch ______________________________________________________________________________________ 22 6 3 4 Magnetic Contactor Type Wiring Diagram ATS 380 CONTROL UNIT Normal Phase N Emergency Phase N ...

Страница 23: ...itch ______________________________________________________________________________________ 23 6 4 Single Phase 380V Connecting Wire Diagram 6 4 1 MCCB Type Wiring Diagram MOTOR ATS 380 CONTROL UNIT Normal Phase N Emergency Phase N ...

Страница 24: ...atic Transfer Switch ______________________________________________________________________________________ 24 6 4 2 One Coil Double Throw Typical Wiring Diagram ATS 380 CONTROL UNIT Normal Phase N Emergency Phase N ...

Страница 25: ...matic Transfer Switch ______________________________________________________________________________________ 25 6 4 3 Two Coils Double Throw Type Wiring Diagram Normal Phase N Emergency Phase N ATS 380 CONTROL UNIT ...

Страница 26: ...tomatic Transfer Switch ______________________________________________________________________________________ 26 6 4 4 Magnetic Contactor Type Wiring Diagram Normal Phase N Emergency Phase N ATS 380 CONTROL UNIT ...

Страница 27: ... Switch ______________________________________________________________________________________ 27 6 5 Connecting Wire Diagram When The Switch Transfer Current Over 6 Amps 6 5 1 MCCB Type Wiring Diagram MOTOR ATS 380 CONTROL UNIT ...

Страница 28: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 28 6 5 2 One Coil Double Throw Typical Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 29: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 29 6 5 3 Two Coils Double Throw Type Wiring Diagram ATS 380 CONTROL UNIT ...

Страница 30: ...ATS 380 Automatic Transfer Switch ______________________________________________________________________________________ 30 6 5 4 Magnetic Contactor Type Wiring Diagram ATS 380 CONTROL UNIT ...

Отзывы: