___________________________________________________________________________________________
8
ATS-34
Free software can be downloaded from App Store or
Google Play by simply
key in “Kutai” and hit search.
You have the option of using one of these
communications modules.
KCU-01
– USB communication module
KCU-02
– RS-485 communications module
KCU-03
– Ethernet communications module
The corresponding program settings for ATS-34
installed with KCU-XX module includes item (22), (23),
(24) Programming item (22) is a must. When Item (22)
is set to "00", then the remote monitoring software is
restricted to read information only whereas remote
command is strictly forbidden.
If KCU-02 - RS485 communication module is installed,
additional program setting on lines (23) and (25) are
needed.
For more detail, information refers to the KCU-XX
manual.
WARNING
ATS-34 with KCU-02 module constitutes a closed
LAN network. Each controller address can be set
from 1 to 99 and not to be repeated. Same
transmission rate is a must !!
The installation for the KCU-XX communication module
on the ATS-34 controller is fairly simple.
Step 1 : Remove cover on the back of the ATS-34.
Step 2 : Plug in tighten the screw on the KCU-XX
module to the ATS-34 PCB.