3.6 Remote Communication Instruction
You can monitor and control the two gen-set on a
remote PC using the optional USB / RS485 / Ethernet
remote communication modules.
WARNING
A remote start signal can activate the ATS-33 and
the engines can start at anytime without warning.
Place a “Danger” warning sign next to the
generator, stating that this generator can start at
anytime! also install a warning buzzer or a flash
light. Unexpected engine starts can result in
serious injury or death. When performing service
or maintenance, always disconnect the remote
start signal input.
If you have an Ethernet module installed on your
ATS-33 you can remotely monitor and operate the ATS
and generator using the IPhone and Android mobile
phones. Free App software currently available for Apple
iOS5.1 system or above and android operating system.
Free software can be downloaded from App Store or
Google Play
by simply key in “Kutai” and hit search.
Free software can be downloaded from App Store or
Google Play
by simply key in “Kutai” and hit search.
You have the option of using one of these
communications modules.
KCU-01
– USB communication module
KCU-02
– RS-485 communications module
KCU-03
– Ethernet communications module
The corresponding program settings for ATS-33
installed with KCU-XX module includes item (23), (24),
(25) Programming item (23) is a must. When Item (23)
is set to "00", then the remote monitoring software is
restricted to read information only whereas remote
command is strictly forbidden.
If KCU-02 - RS485 communication module is installed,
additional program setting on lines (24) and (25) are
needed.
For more detail, information refers to the KCU-XX
manual.
NOTE
ATS-33 with KCU-02 module constitutes a closed
LAN network. Each controller address can be set
from 1 to 99 and not to be repeated. Same
transmission rate is a must !!
The installation for the KCU-XX communication
module on the ATS-33 controller is fairly simple.
Step 1
:
Remove cover on the back of the ATS-33.
Step 2
:
Plug in tighten the screw on the KCU-XX
module to the ATS-33 PCB.