SECTION 3 : POTENTIOMETER ADJUSTMENT

 

 

0V, 110V

 

Power Supply 

and Sensing Input 

*  Over Excitation Current Limiting (O/C) 

When the excitation current is greater than or exceeds 5A the AVR will reduce the excitation output to limit the 
excitation current. At this time the generator output voltage will be in a very unable state (the greater the load the 
lower the voltage). Over current protection will not interrupt the excitation field output. 

 
*  LAM (Load Acceptance Module) Outline 

When  the  generator  experiences  momentary  increases  in  load  (more  40%  of  generator  capacity)  voltage  and 
engine speed will decrease. The process of recovering voltage and engine speed will produce a situation where 
output  voltage  and  engine  speed  fluctuates.  In  order  to  reduce  the  level  of  volatility,  after  a  load  is  added  the 
engine speed will slow, lowering the total power output of the generator and delaying recovery. 
 
The low frequency knee point setting should be below a nominal setting for 2 Hz to cause the output voltage and 
engine speed to have a smooth recovery. 
 

The LAM function allows choice of reduction settings of 13% and 25%. If the generator has a fluid drive (hydro) it 
is recommended not to use the LAM function.

 

E+, E-

 

Excitation Output 

VOLT

Voltage Adjustment 

STAB

Stability Adjustment 

O/C  LED

Over  Excitation 

Current 

Limiting 

Status 

Indicator. 
 
When  over  excitation  current 
limiting  function  is  operating 
(Excitation Current > 5A)

this 

LED will light up. 

U/F LED

Under Frequency 

Protection Status Indicator. 

1K ohm

 

External 

VR 

input, Must be 
shorted with a 
jumper  when 
not in use. 

U/F function and LAM potentiometer

 

See SECTION 4 for more detail 

110V

0V

E+

E-

1 KΩ

STAB

VOLT

U/F

O/C

0

1

2

3

4

5

6

7

8

9

ADVR-250

Figure 2 

Содержание ADVR-250

Страница 1: ...aiwan ADVR 250 Generator Automatic Voltage Regulator Operation Manual Analog Digital Single phase detection Excitation Current 3 5 Amps For use in brushless self excited shunt generators Compatible with Leroy Somer R250 R230 AVR All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Страница 2: ... Adjustment 1K ohm Under Frequency Knee Point Thermal Drift Max 14 1 K ohm 1 watt potentiometer Less than 0 1 Hz at 40 to 70 C Voltage Regulation Environment Less than 0 5 with 4 engine governing Operating Temperature 40 to 70 C Storage Temperature 40 to 85 C Build Up Voltage Relative Humidity Max 95 5 Vac 25 Hz residual volts at power input terminal Vibration 5 5 Gs 60 Hz Soft start ramp time Dim...

Страница 3: ...e and engine speed fluctuates In order to reduce the level of volatility after a load is added the engine speed will slow lowering the total power output of the generator and delaying recovery The low frequency knee point setting should be below a nominal setting for 2 Hz to cause the output voltage and engine speed to have a smooth recovery The LAM function allows choice of reduction settings of ...

Страница 4: ... function set to 25 Use when transient loads are greater than 70 of rated generator capacity 60 Hz Systems 3 Under Frequency knee point 58 Hz LAM function OFF Use when transient loads are below 40 of rated generator capacity 4 Under Frequency knee point 58 Hz LAM function set to 13 Use when transient loads are between 40 70 of rated generator capacity 5 Under Frequency knee point 58 Hz LAM functio...

Страница 5: ...e 5 ATTENTION 1 Before using a Megger or a Withstand Voltage Tester removes the wires connecting to the AVR to prevent high voltage damage to the regulator 2 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in load Avoid making any changes to the U F setting unless necessary Use only replacement fuses specified ...