SECTION 3 : DIP SWITCH PROGRAMMING & VR ADJUSTMENTS
VOLT
:
Voltage Adjustment
Sensing input voltage range set by DIP
switches SW5 and SW6
X1, X2
:
Single Phase Power Input
Z1, Z2
:
Auxiliary Power Input
X1, X2, Z2
:
Three Phase Power Input
Remark : X1 and Z1 are the same point
(internally shorted)
S1, S2
:
Quadrature Droop Input
Sensi/- 7% @ PF +/- 0.5
CT N : 5A or N : 1A set by DIP
switches SW3
VR1, VR2
:
External VR Input
Must be shorted when not in use
A1, A2
:
Analog Voltage Input
Max. Input +/- 5 Vdc or 0
– 10 Vdc
DROOP
:
DROOP Adjustment
(Parallel operation)
Droop Adjustment
Used only during parallel operation
F+, F-
:
Excitation Output
Connects to generator excitation field
E1, E2
:
Single Phase Sensing Input
E1, E2, E3
:
Three Phase Sensing Input
Single Phase / Three Phase sensing set by DIP
switch SW7
EXC.
:
Over Excitation Protection Adjustment
25
105% of Rated Excitation (Adjustable)
Adjust EXC. potentiometer clockwise to
Max. to turn OFF O/E protection
STAB
:
Stability Adjustment
Stability range set by DIP
switches SW1 and SW2
U/F
:
Under-Frequency LED
Under-Frequency Protection status
(ON = Activated)
DIP
:
U/F Protection Voltage Slope
Adjustment
When U/F protection is activated the voltage
drop ratio can be adjusted by DIP switch.
Adjustment range 3 to 6 V/Hz
UF
:
Under Frequency Adjustment
Under frequency knee point setting
50 Hz system
:
40 to 50 Hz adjustable
60 Hz system
:
50 to 60 Hz adjustable
O/E
:
Over Excitation LED
Over Excitation Protection status
(ON = Activated) Excitation Output
will be reduced after a 10 sec delay
TRIM
:
Analogue Voltage Input Adjustment
Max. Input +/- 5 Vdc or + 10 Vdc
Sensitivity 1 Vdc for 5% (adjustable)
51
40
(61)
(50)
F
S
ADVR-083
ON
OFF
SW
3
CT 5A
CT 1A
4
50 Hz
60 Hz
7
1Φ SENSING
3Φ SENSING
1. OFF
2. OFF
<90KW
1. OFF
2. ON
90-500KW
1. ON
2. ON
>500KW
5. OFF
6. OFF
110V
5. ON
6. OFF
220V
5. OFF
6. ON
440V