ADVR-083
SECTION 1 : SPECIFICATION
Sensing Input (E1, E2, E3) Average Reading
Soft Start Ramp Time
Voltage and Frequency DIP switch settings
4 s/- 10%
1 phase
(E1, E2)
/ 3 phase
(E1, E2, E3)
90
130 Vac @ 110 Vac
Voltage Regulation
180
260 Vac @ 220 Vac
Less than +/- 0.5% (with 4% engine governing)
340
520 Vac @ 440 Vac
Frequency
50/60 Hz
Typical System Response
Less than 20 milliseconds
Power Input (X1, X2, Z2)
Voltage
60
300 Vac, 1 phase / 3 phase
EMI
1 phase ( X1, X2 ) / 3 phase ( X1, X2, Z2 )
Built-in Harmonic suppression
Frequency
40
500 Hz
Static Power Dissipation
Auxiliary Input (Z1, Z2)
Max. 6 watts
Voltage
60
300 Vac, 1 phase 2 wire
Frequency
40
500 Hz
Under Frequency Protection (Factory Preset)
50 Hz system preset knee point at 45 Hz
Excitation Output (F+, F-)
60 Hz system preset knee point at 55 Hz
110V 1 phase Continuous
63 Vdc
8A
Max. 90 Vdc 10A for 10 secs.
Over Excitation Protection
220V 1 phase Continuous
125 Vdc 8A
25
105% of Input Power (adjust with EXC pot.)
Max. 180 Vdc 10A for 10 secs.
O/E acts after 10 sec. delay. The OE function can be
220V 3 phase Continuous
150 Vdc 8A
turned OFF by adjusting EXC. clockwise to max.
Max. 215 Vdc 10A for 10 secs.
Resistance
Min.15 ohms, Max.100 ohms @ 220V
Voltage Thermal Drift
Fuse Spec.
Slow blow 5 x 20 mm 10A
Less than 3% from -
40 to +70 ˚C
External Voltage Adjustment (VR1, VR2)
Under-Frequency Knee Point Thermal Drift
Max. +/- 10% @ 1K ohm 1 watt potentiometer
Less than +/- 0.1 Hz from -
40 to +70 ˚C
Quadrature Droop Input (S1, S2)
Environment
CT N:5A or N:1A (DIP switch setting)
Operation Temperature
-40 to +60
˚C
Burden : greater than 5VA
Storage Temperature
-40 to +85
˚C
Sensi/- 7% @ PF +/- 0.5
Relative Humidity
Max. 95%
(Can be adjusted through Droop setting)
Vibration
5.5Gs @ 60 Hz
Analogue Voltage Input (A1, A2)
Dimensions
Input resistance greater than 2K ohms
150.0 (L) x 135.0 (W) x 61.0 (H) mm
Input Range +/- 5 Vdc or 0
10 Vdc
5.91 (L) x 5.31 (W) x 2.40 (H) inch
Sensitivity Max.1 Vdc = 5% change in output voltage
(Can be adjusted through Trim setting)
Weight
750 g +/- 2%
Build Up Voltage
1.654 lb +/- 2%
Greater than 5 Vac, 25 Hz residual volts input power
ATTENTION
In order to avoid permanent damage to the AVR confirm that the voltage sensing input setting matches
the generator before use (DIP switches SW5 and SW6)