but shorter than 2 seconds) will increment the backlight level 

through four different intensities.

B) Generator Hours Page

While in the Main page, a quick press of both 

p

 and 

*

 keys 

at the same time will bring up the Generator Hours page which 

includes: Total Generator Hours and Hours till Maintenance 

Required. This page will revert back to Main page after 10 

seconds from the last key press. No access code required to 

view the Hours page. This page is for viewing of generator and 

service hours. There are no adjustments available on  

this page.The Main page is displayed ten seconds from 

entering the Generator/Maintenance screen or by quick 

pressing both the 

q

 and 

*

 keys at the same time.

C) Secured Access Pages

While in the Main page or Generator Hours page, a Quick 

press of the 

*

 key brings up the Security Access page and a 

default number 5000 is displayed in the ACCESS CODE box. 

Use the 

p

 and 

q

 keys to scroll to the correct access code 

and press “ACCEPT” to enter that number (default ACCESS 

CODE is 1234). The longer you hold down the 

p

 or 

q

 key, 

the faster the scrolling of numbers. False entry results in Main 

Page being displayed. Entry of correct access code unlocks 

the instrument and brings up the following menu:

After security access has been granted and you return to 

the Main page, you have 60 seconds to re-enter the secured 

pages by quickly pressing the 

*

 key or you

will have to re-enter the security code. You may toggle between 

the Main page and secured pages without reentering the 

security code, but will need to re-enter it after 60 seconds from 

the last key press.

For each menu or sub-menu item the following is true: 

Pressing the 

q

 or 

p

 keys moves highlighted selection down 

or up. Pressing the QUIT (

*

) key returns you to the Main 

Page. Pressing the ACCEPT key selects the highlighted menu 

item. Pressing no key for 60 seconds returns you to the Main 

Page and locks the security access.

D) Alarms

AC

Selecting the AC ALARMS menu brings up the following sub-

menu:

AC VOLTS HI (Adjustable from 90 to 300)

AC VOLTS LO (Adjustable from 90 to 300)

FREQUENCY HIGH (Adjustable from 30 to 100)

FREQUENCY LO (Adjustable from 30 to 100)

AC AMPS #1 HI  (Adjustable from 0 to 150)

AC AMPS #2 HI  (Adjustable from 0 to 150)

MAINTENANCE  (Adjustable from 0 to 5000)

f

 BACK 

(Returns to previous page)

Use the UP or DOWN button to move to the appropriate item 

then press the 

+

 (ACCEPT) key. Use the 

p

 or 

q

 keys to 

increase or decrease the number to the desired value then 

press the 

+

 (ACCEPT) key to set the value and return to the 

ALARMS menu or the 

*

 (QUIT) key to set the value and 

return to the Main page. 

DC

Selecting the DC ALARMS menu brings up the following sub-

menu:

DC VOLTS HI 

(Adjustable from 9.5 to 30)

DC VOLTS LO  (Adjustable from 9.5 to 30)

DC AMPS HIGH   (Adjustable from 0 to 300)

f

 BACK 

(Returns to previous page)

Use the UP or DOWN button to move to the appropriate item 

then press the 

+

 (ACCEPT) key. Use the 

p

 or 

q

 keys to 

increase or decrease the number to the desired value then 

press the 

+

 (ACCEPT) key to set the value and return to the 

ALARMS menu or the 

*

 (QUIT) key to set the value and 

return to the Main page.

 

E) Calibration AC

Selecting the CALIBRATE AC menu brings up the following 

sub-menu:

170 Cherry Avenue

West Sayville, NY 11796

www.kussmaul.com

Ph: 800-346-0857

Fax: 631-567-5826

[email protected]

4

Содержание 091-247

Страница 1: ...he display can be remotely turned ON OFF All set up calibration and alarm values are saved to non volatile memory The system is complete with DC amp shunt voltage and current transformers and is facto...

Страница 2: ...e at source To AC distribution panel 2 2 5 max 3 max CT 1 CT 1 CT 1 CT 2 CT 2 DC DC 5 VDC alarm N U VAC VAC L 1 L 1 Tie wrap wire hold down point White Orange Black Red Orange White DC Interface box L...

Страница 3: ...AWG cable Wire colors used are black and red One end will have factory terminated QD s which can be connected to the Interface box see wiring diagram The opposite end must be terminated with ring lug...

Страница 4: ...fter 60 seconds from the last key press For each menu or sub menu item the following is true Pressing the q or p keys moves highlighted selection down or up Pressing the QUIT key returns you to the Ma...

Страница 5: ...d reading then press the accept button when done ATTENTION Calibration should only be performed by qualified personnel Published accuracies are based on proper calibration in conjunction with the 773...

Страница 6: ...is ever forgotten the instrument can be reset back to factory default see Reset to Default Caution Resetting to factory default will reset all alarm and calibration settings as well B Zero Generator...

Страница 7: ...system and causes the Main Page to be displayed SPECIFICATIONS Power Supply 9 50 to 33 00 VDC 100mA Operating Temperature 32 to 122 F 0 to 50 C Size 4 3 x 4 3 x 3 5 deep 110 x 110 x 89 mm Display Dat...

Отзывы: