WIRING AND POWER UP

The following wiring components are provided with the meter:

1 ea. Interface Box containing AC voltage 

         transformer and board            

2 ea. AC current transformers

1 ea. DC current shunt

2 ea. Tie Wraps 

1) Power Wiring (for operating the meter)

The VAAFH  is powered  from a source of 9.5 to 33.0 VDC. 

Attach power wiring per diagram, see FIG. 2 & 3. Fuse  

at source

2) Monitor Wiring

The meter receives voltage and amperage signals from 

the provided wiring interface box and current transformers. 

CAUTION:  DO NOT APPLY RAW AC VOLTAGE OR 

CURRENT DIRECTLY TO THE METER, THIS WILL 

DESTROY THE METER. Attach the signal data wiring to the 

meter as shown in FIG. 2

3) AC Current Transformer Wiring

Two C.T.’s are provided, each with 40” length two conductor 

(26 AWG) cable. Wire colors are black and yellow. The yellow 

and black wires can be connected to the Interface box PCB in 

either direction, there is no polarity for C.T. connection. Please 

disregard arrow on top of C.T., there is no current direction for 

the VAAFh installation. For new installations, we recommend 

passing the Line side cable of the current carrying source 

through the center opening in the C.T. (Dia.: .630”). For pre-

wired installations, the C.T. donut hole can be opened to allow 

the C.T. to clamp over the cable. To open C.T. use a small 

slotted screwdriver; pry up both ends, lift up the non-secured 

end, release top from plastic latches, clamp over cable and 

push the two C.T. halves back together and snap the plastic 

latches shut

 

The VAAFH is designed to operate with the provided interface 

box. Locate the interface close enough for the VAAFH cable to 

reach (2’ to 2.5’). The box also needs to be located a maximum 

of 3’ from L1 & L2 main feeds for the current transformer leads 

to reach the Interface box.

4) DC Current Shunt Wiring

A DC current shunt is provided with 16” length three conductor 

(20 AWG) cable. Wire colors used are black and red.  One end 

will have factory terminated QD’s which can be connected to 

the Interface box, see wiring diagram.  The opposite end must 

be terminated with ring-lugs, provided.  Please refer to the 

wiring diagram for wire color termination and chassis grond 

reference.  If the DC shunt wiring does not match the wiring 

diagram the display DC Amps will show a positive sign instead 

of a negative.  The wiring is configured to display a negative 

sign when the battery is supply power to a load (battery is 

power source and being drained).

5) Alarm Wiring (Optional)

This terminal produces a +5 VDC signal (100mA max.) 

with reference to DC when an alarm condition is detected. 

Maintenance alarm does not 5 VDC alarm output. This 

+5 VDC signal is compatible with Newmar model DIR 

(optional), solid state relay which can carry an AC or DC circuit 

up to 10 amps.

6) Powering Up

Once the meter wiring/installation is complete, double check 

DC power polarity and then connect 12, 24, or 32 VDC power 

to meter. It is normal for meter to take 20-30 seconds to start 

up before the display readings settle. Note: Display refreshes 

readings every 2 seconds.

MENU NAVIGATION AND CALIBRATION

A) Main Page

When the instrument is powered up it displays the “Main” page. 

The “Main” page displays: AC Volts, Frequency (HERTZ), AC 

AMPS #1, and AC AMPS #2. Values are displayed in GREEN 

if within acceptable alarm set limits or RED if out of limits 

condition exists.

From MAIN PAGE display:

• Pressing the 

p

 key for ½ second (longer than a quick press 

but shorter than 2 seconds) will cause a white ALARM bell 

symbol to be displayed and enable the alarms.

• Pressing the 

q

 key for ½ second (longer than a quick press 

but shorter than 2 seconds) will disable the alarms and remove 

the white alarm bell symbol.

• Pressing the 

+

 key for ½ second (longer than a quick press 

120V Screen

240V Screen

Current Transformer: Closed and Open

Secured End

Plastic Latches

170 Cherry Avenue

West Sayville, NY 11796

www.kussmaul.com

Ph: 800-346-0857

Fax: 631-567-5826

[email protected]

3

Содержание 091-247

Страница 1: ...he display can be remotely turned ON OFF All set up calibration and alarm values are saved to non volatile memory The system is complete with DC amp shunt voltage and current transformers and is facto...

Страница 2: ...e at source To AC distribution panel 2 2 5 max 3 max CT 1 CT 1 CT 1 CT 2 CT 2 DC DC 5 VDC alarm N U VAC VAC L 1 L 1 Tie wrap wire hold down point White Orange Black Red Orange White DC Interface box L...

Страница 3: ...AWG cable Wire colors used are black and red One end will have factory terminated QD s which can be connected to the Interface box see wiring diagram The opposite end must be terminated with ring lug...

Страница 4: ...fter 60 seconds from the last key press For each menu or sub menu item the following is true Pressing the q or p keys moves highlighted selection down or up Pressing the QUIT key returns you to the Ma...

Страница 5: ...d reading then press the accept button when done ATTENTION Calibration should only be performed by qualified personnel Published accuracies are based on proper calibration in conjunction with the 773...

Страница 6: ...is ever forgotten the instrument can be reset back to factory default see Reset to Default Caution Resetting to factory default will reset all alarm and calibration settings as well B Zero Generator...

Страница 7: ...system and causes the Main Page to be displayed SPECIFICATIONS Power Supply 9 50 to 33 00 VDC 100mA Operating Temperature 32 to 122 F 0 to 50 C Size 4 3 x 4 3 x 3 5 deep 110 x 110 x 89 mm Display Dat...