Probe-Contact EF -Detection (Single-pole):
For more precise indication of liv e wires, such as distinguishing
between Live and Ground connections, use one single test probe
to test via terminal
COM
for direct metal contact probing to achieve
the most distinctive indications.
18
Inputs are made via the test lead terminals
COM
/
+
.
DC
m
A
●Application notes:
The
DC A
function is designed especially
m
for HVAC/R flame sensor applications. The
0.1 A resolution is useful for identifying the
m
minute current changes in flame detector
applications. Flame signal current check
should indicate steady flame signal of at
least 2 A for a rectification type, or 1. 5
m
m
A for an ultraviolet type ( 8
A for self
m
checking systems). If a flame signal current
with inadequate strength or fluctuation
beyond 10%, check the following to avoid
the risk of unwanted flame relay dropout :
For gas or oil flames (Minipeeper):
Low supply voltage
Detector location
Defective detector wiring
Dirty viewing window
Faulty Minipeeper
●
●
●
●
●
●
●
●
●
For oil flames (Photocell):
Detector location & wiring
Smoky flame or poorly adjusted air shutter
Faulty Photocell
Temperature over 165 oF (74 C) at
For gas flames (Flame Rod):
Ignition interference (A fla me signal current difference with the
ignition both on and off greater than 0.5 A indicates the presence
m
of ignition interference)
●
photocell