background image

Installation Instructions 

Installation of the Module 

 

 

   CompactRIO

 PROFIBUS DP

-Installation Instructions-V1.7/23.02.2017 

 

Business Confidential/

 Proprietary 

1  Installation of the Module 

The  cRIO  PB  module  is  a  PROFIBUS  DP  Master/Slave  module  for  National  Instruments 
CompactRIO, Single-Board RIO systems. The configuration entirely takes place by means of 
the delivered software. Thus, no jumpers or DIP-switch adjustments are necessary. 

To mount the module in the CompactRIO or Single-Board RIO proceed as follows: 

 

Switch off the CompactRIO or Single-Board RIO  

 

Plug the cRIO PB module into slot 1 until it snaps in. 
Pay attention to a proper adjustment of the board in the guidance (avoid canting !). 

Important note:

 The CompactRIO PROFIBUS DP modules require 2.5 W of power, so you 

must use it in Slot 1 while leaving Slot 2 empty. 

Important note:

 The CompactRIO PROFIBUS DP modules is supported only in 

CompactRIO reconfigurable chassis, such as an NI cRIO-911x, and NI Single-Board RIO 
devices. 

 

 

 

Figure 1: cRIO PB module 

Содержание cRIO PB

Страница 1: ...CompactRIO PROFIBUS DP Installation Instructions V1 7 23 02 2017 CompactRIO PROFIBUS DP Installation Instructions V1 7 23 02 2017...

Страница 2: ...ersion GmbH Robert Bosch Stra e 12A 76275 Ettlingen Phone 49 7243 51449 00 Copyright 2017 by GmbH Business Confidential KUNBUS Proprietary This document includes data that shall not be duplicated used...

Страница 3: ...02 2017 i Business Confidential Proprietary Contents 1 Installation of the Module 1 2 LEDs and Connectors 2 2 1 Position of LEDs and Connectors 2 2 2 LED s 3 2 3 Power connector 4 2 4 9 pin SUB D con...

Страница 4: ...ss Confidential Proprietary List of Figures Figure 1 cRIO PB module 1 Figure 2 LEDs and connectors 2 Figure 3 Profibus Terminator cable type B is no longer used 4 List of Tables Table 1 Meaning of the...

Страница 5: ...tch adjustments are necessary To mount the module in the CompactRIO or Single Board RIO proceed as follows Switch off the CompactRIO or Single Board RIO Plug the cRIO PB module into slot 1 until it sn...

Страница 6: ...17 Business Confidential Proprietary 2 LEDs and Connectors 2 1 Position of LEDs and Connectors Figure 2 LEDs and connectors SPI Activity LED PWR Power indication LED RUN PROFIBUS Activity LED BF PROFI...

Страница 7: ...active ON DP Slave initialized Flash fast DP Slave AutoSlaveMode waits for a DP Master to communicate Flash slow DP Slave AutoSlaveMode baud rate detection active BF Red Operation as DP Master OFF PR...

Страница 8: ...2 4 9 pin SUB D connector Pin Number Signal Function Direction 1 shielding 3 RxD TxD P Data Input Output 5 0V potential free 80 mA Feeding of bus terminator Input 6 5V potential free 80 mA Feeding of...

Страница 9: ...Port Sub D 9 pins Interface Physics RS485 isolated Profibus Data Rates 9600 Bit s 12000 Kbit s Data Size of Process Image max 8 KByte PROFIBUS Isolation Voltage 500 VDC Power Requirements 2 5 W Active...

Страница 10: ...dential Proprietary 4 CE Conformity Declaration We herewith declare that the CompactRIO Module cRIO PB corresponds to the requirements stated in the EU standards 2004 108 EG The device corresponds to...

Страница 11: ...t ni com patents You can find information about end user license agreements EULAs and third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni...